Plan Review Details - Permit 16080576
Plan Review Stops For Permit 16080576
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-07 Cont ID  
Sent By cthroop Date 2016-09-07 Time 10:38 Rev Time 0.00
Received By cthroop Date 2016-09-07 Time 10:38 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By destabro Date 2016-08-31 Time 13:55 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 11:56 Sent To  
Notes
2016-08-31 14:01:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS
 (INCLUDING OVERHEAD GARAGE DOOR).
 2. PROVIDE DESIGN WIND LOADS FOR ALL NEW OPENINGS.
 3. PROVIDE LANDINGS AT ALL EXT DOORS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND
 DOOR SUBMITTALS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-07 Cont ID  
Sent By mvaldes Date 2016-09-07 Time 13:20 Rev Time 0.00
Received By mvaldes Date 2016-09-07 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 10:23 Rev Time 0.00
Received By mvaldes Date 2016-08-17 Time 08:41 Sent To  
Notes
2016-08-17 10:25:25JOB PERMIT NUMBER: 16080576
 JOB ADDRESS: 925 39TH COURT
 WEST PALM BEACH FLORIDA
 DATE: AUGUST 17, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) SMOKE ALARMS REQUIRED IN EACH SLEEPING ROOM, OUTSIDE
 OF EACH SLEEPING AREA, AND ON ANY ADDITIONAL HABITABLE
 STORY OF A DWELLING. REFLECT LOCATION ON PLANS, THEY
 SHALL BE INTERCONNECTED AND PROTECTED BY AN ARC-FAULT
 BKR UNLESS EXCEPTIONS APPLY. FBC-R314
 2) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF EACH
 SLEEPING ROOM WHERE A FOSSIL FUEL APPLIANCE, FIREPLACE,
 OR AN ATTACHED GARAGE IS PRESENT. REFLECT LOCATION ON
 PLANS, THEY SHALL BE INTERCONNECTED AND PROTECTED BY AN
 ARC-FAULT BKR UNLESS EXCEPTIONS APPLY. FBC-R315
 3) SHEET E-1.0, IF ON THE MASTER BATH 2 SEPARATE OR A
 DOUBLE SINK IS GONA BE USED ADD A 20 AMP GFCI OUTLET
 WITHIN 3' OF THE BASIN EDGE AS PER FBC-R SECTION
 E3901.6
 4) SHEET E-1.0, INSTALL A 20 AMP GFCI OUTLET WITHIN
 12'' OF THE TOP OF THE COUNTER-TOP ON THE KITCHEN
 ISLAND. FBC-R SECTION E3901.4.2
 5) SHEET E-1.0, GARAGE DOOR OPENER OUTLET NOT SHOWN,
 KEEP IN MIND THE RECEPTACLE SHALL BE GFCI PROTECTED PER
 FBC-R SECTION E3902.2
 6) SHEET E-1.0, ADD A GFCI OUTLET IN THE FRONT AND BACK
 OF THE HOUSE, PLUS THE OUTSIDE LOGGIA REQUIRES 1
 RECEPTACLE ACCESSIBLE WITHIN 6.5' FROM GRADE. FBC-R
 SECTION E3901.7
 7) SHEET E-1.0, LAUNDRY ROOM DOESN'T SHOW LOCATION OF
 WASHER AND DRYER OUTLETS. KEEP IN MIND ANY ADDITIONAL
 RECEPTACLE WITHIN THE LAUNDRY ROOM SHALL BE GFCI
 PROTECTED. FBC-107 MINIMUM PLAN REVIEW
 8) PROVIDE LOCATION OF THE NEW 200 AMP PANEL ''A'' ON
 THE FLOOR PLAN TO VERIFY WORKING CLEARANCE AND A PANEL
 SCHEDULE WITH MATCHING CIRCUITS. FBC-107 MINIMUM PLAN
 REVIEW.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A
 QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING
 EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL
 FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By destabro Date 2016-09-08 Time 08:53 Rev Time 0.00
Received By destabro Date 2016-09-08 Time 08:53 Sent To B
Notes
2016-09-08 08:54:229/8/16 - ALL REVISION COMMENTS ADDRESSED AND CORRECTED.
 APPROVED PERMIT RETURNED TO BOX R03. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By destabro Date 2016-08-25 Time 15:01 Rev Time 0.00
Received By destabro Date 2016-08-25 Time 15:01 Sent To Z
Notes
2016-08-25 15:44:398/25/16 - NONCONTRIBUTING HOUSE TO NORTHWOOD HILLS HD.
 WORK APPROVED BY HISTORIC PRESERVATION BOARD ON JUNE
 29, 2016. MOST CHANGES FOLLOWED ON THE PLANS BUT THE
 FOLLOWING TWO ITEMS MUST BE ADDRESSED FOR RESUBMITTAL:
 1.) CURRENT PLANS SHOW ROLLING METAL GARAGE DOORS
 WHEREAS THE HPB APPROVED CARRIAGE-STYLE DOORS, IN
 KEEPING WITH THE DESIGN GUIDELINES OF THE HISTORIC
 DISTRICT.
 2.) PROVIDE PRODUCT APPROVALS FOR THE NEW WINDOWS AND
 DOORS. THE CONFIGURATIONS PRESENTED ON THE PLANS ARE
 ACCURATE, BUT NO PRODUCT APPROVALS WERE SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-16 Cont ID  
Sent By cthroop Date 2016-09-16 Time 14:54 Rev Time 0.00
Received By cthroop Date 2016-09-15 Time 12:42 Sent To  
Notes
2016-09-16 12:42:35IMPACT FEES ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-14 Cont ID  
Sent By skennedy Date 2016-09-14 Time 07:48 Rev Time 0.00
Received By skennedy Date 2016-09-07 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-01 Cont ID  
Sent By gjohnson Date 2016-09-01 Time 10:26 Rev Time 0.00
Received By gjohnson Date 2016-08-12 Time 11:16 Sent To  
Notes
2016-08-31 18:26:19ROUTED TO GEORGE J. - 8/31/2014 - JORGE VALIDO
2016-08-15 11:16:20R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-09-16 Cont ID  
Sent By cthroop Date 2016-09-16 Time 14:54 Rev Time 0.00
Received By cthroop Date 2016-09-16 Time 14:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-09-07 Cont ID  
Sent By cthroop Date 2016-09-07 Time 10:22 Rev Time 0.00
Received By cthroop Date 2016-09-07 Time 10:22 Sent To  
Notes
2016-09-07 10:23:45BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By cthroop Date 2016-08-31 Time 13:39 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 13:39 Sent To  
Notes
2016-08-31 13:40:37BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. PALM BEACH COUNTY IMPACT FEES APPLY.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By jvalido Date 2016-09-13 Time 16:41 Rev Time 0.00
Received By jvalido Date 2016-09-13 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By jvalido Date 2016-08-31 Time 18:18 Rev Time 0.00
Received By jvalido Date 2016-08-31 Time 17:59 Sent To  
Notes
2016-08-31 18:15:19WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ON PLANS SIZE OF DUCT FEEDING DISTRIBUTION
 BOX FOR DUCTS FEEDING THE LAUNDRY AND CABANA BATH.
 (2) PROVIDE FLEX DUCT SIZE FOR 2" X 48" SIDEWALL
 FEEDING FOYER & SITTING ROOM.
 (3) PROVIDE FLEX DUCT SIZE FOR 2" X 48" SIDEWALL
 FEEDING THE LIVING ROOM
 (4) PROVIDE ALL EXHAUST FANS IN BATHROOMS CFM & EXHAUST
 DUCT SIZES.
 (5) SHOW TERMINATION OF DRYER EXHAUST.
 (6) SHOW LOCATION OF CONDENSING UNIT.
 (7) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014.
 (8) IS THERE A KITCHEN EXHAUST??? IF THERE IS PROVIDE
 KITCHEN EXHAUST DUCT SIZING, TERMINATION AND TOTAL CFM.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (9) FORM R405-2014 MUST BE SIGNED BY OWNER/AGENT.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By gjohnson Date 2016-09-13 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2016-09-13 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By gjohnson Date 2016-09-01 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2016-09-01 Time 10:03 Sent To  
Notes
2016-09-01 10:25:371ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. LABE THEL P-TRAP LOCATED DOWN STEAM OF MASTER
 BATHROOM ON RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 2. KITCHEN SINK IS NOT VENTED IT SHALL COMPLY WITH FBC
 PL P3101.2.1 VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 3. A CLEANOUT IS REQUIRED WHERE THE 4IN BRANCH FOR KIT
 , LAUNDRY EXITS BUILDING BEFORE IT CONNECTS TO
 SEWER.PER FBC PL P3005.2.7
  
 4. A TRAP PRIMER IS REQUIRED ON ALL FLOOR DRAINS. PER
 FBC PL P3201.2 TRAP SEALS AND TRAP SEAL PROTECTION.
 TRAPS SHALL HAVE A LIQUID SEAL NOT LESS THAN 2 INCHES
 (51 MM) AND NOT MORE THAN 4 INCHES (102 MM). TRAPS FOR
 FLOOR DRAINS SHALL BE FITTED WITH A TRAP PRIMER OR
 SHALL BE OF THE DEEP SEAL DESIGN. TRAP SEAL PRIMER
 VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE
 LEVEL OF THE TRAP SEAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-09-07 Cont ID  
Sent By cthroop Date 2016-09-07 Time 10:38 Rev Time 0.00
Received By cthroop Date 2016-09-07 Time 10:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-31 Cont ID  
Sent By cthroop Date 2016-08-31 Time 13:40 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 13:40 Sent To  
Notes
2016-08-31 13:54:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By njwira Date 2016-08-25 Time 17:12 Rev Time 0.00
Received By njwira Date 2016-08-25 Time 15:48 Sent To  
Notes
2016-08-25 17:16:078/25/16- PASSED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL HISTORIC
  
 NO TREES CAN BE REMOVED WITHOUT A TREE ALTERATION
 PERMIT
 DRIVEWAY NOT INCLUDED
  
 1 KITCHEN MAKES THIS ONE UNIT WHICH IS PERMITTED IN
 THIS ZONING DISTRICT
 FRONT SETBACK IS 36FT. MEETING THE 25FT. SETBACK
 REQUIREMENT
  
 SIDE SETBACK IS 30FT 5FT. MINIMUM MEETING THE 15FT. 5FT
 MINIMUM REQUIREMENT
 REAR SETBACK IS 15 FT. MEETING THE 15FT. REQUIREMENT
  
 MEETS LOT SIZE REQUIREMENTS
  
 PORCH IS NOT IS A REQUIRED SETBACK
  
 BUILDING HEIGHT IS 20FT MEETING THE 30FT. HEIGHT LIMIT
  
 NO ACCESSORY STRUCTURES
  