Plan Review Details - Permit 16080560
Plan Review Stops For Permit 16080560
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-17 Cont ID  
Sent By cthroop Date 2016-11-17 Time 14:39 Rev Time 0.00
Received By cthroop Date 2016-11-17 Time 14:38 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-21 Cont ID  
Sent By cthroop Date 2016-10-21 Time 13:06 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 13:06 Sent To E
Notes
2016-10-21 13:08:02BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
  
 1. COMMENTS FROM 1ST REVIEW NOT ADDRESSED.
 2. VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR STATED VALUE APPEARS LOW.
 THE STATED VALUATION OF $1,100 IS TOO LOW FOR THE
 PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By cthroop Date 2016-08-18 Time 10:09 Rev Time 0.00
Received By cthroop Date 2016-08-18 Time 10:09 Sent To E
Notes
2016-08-18 10:11:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/18/16
  
 1. VALUE APPEARS LOW.
  
 [A] 109.3 BUILDING PERMIT VALUATIONS.
 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED
 PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS
 SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS
 AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH
 AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND
 PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-17 Time 16:25 Rev Time 0.00
Received By mvaldes Date 2016-11-17 Time 15:57 Sent To Z
Notes
2016-11-17 16:28:49ROUTED TO ZONING BIN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-24 Cont ID  
Sent By mvaldes Date 2016-10-24 Time 14:21 Rev Time 0.00
Received By mvaldes Date 2016-10-24 Time 14:13 Sent To  
Notes
2016-10-24 14:21:342ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - APPLICANT HAS NOT ADDRESSED INTIAL PLAN REVIEW
 COMMENTS. IF ANY QUESTIONS PLEASE CALL OR EMAIL.
  
 1] FBC-E SEC C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
  
 2] THE STATED VALUATION OF $1,100.00 IS TOO LOW FOR THE
 INSTALLATION OF PROPOSED SIGNAGE. THE PERMIT VALUATION
 AND PERMIT FEE MUST BE EQUIVALENT WITH THE VALUATION
 AND FEE THAT A LICENSED CONTRACTOR WOULD PROVIDE.
 PLEASE INCREASE THE VALUATION ACCORDINGLY. FBC-109.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By mvaldes Date 2016-08-18 Time 19:22 Rev Time 0.00
Received By mvaldes Date 2016-08-18 Time 19:13 Sent To  
Notes
2016-08-18 19:21:57REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. ( A NOTE WILL
 SUFFICE )
  
 2] COMPLY WITH BUILDING COMMENTS FOR PERMIT AND JOB
 COST EVALUATION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-17 Time 16:25 Rev Time 0.00
Received By mvaldes Date 2016-11-16 Time 10:46 Sent To  
Notes
2016-11-17 10:46:32RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-24 Cont ID  
Sent By mvaldes Date 2016-10-24 Time 14:24 Rev Time 0.00
Received By mvaldes Date 2016-10-11 Time 11:30 Sent To  
Notes
2016-10-11 11:30:33RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By mvaldes Date 2016-08-18 Time 19:22 Rev Time 0.00
Received By mvaldes Date 2016-08-12 Time 13:07 Sent To  
Notes
2016-08-12 13:07:54ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status F Date 2016-11-22 Cont ID  
Sent By kmartin Date 2016-11-22 Time 10:10 Rev Time 0.00
Received By kmartin Date 2016-11-22 Time 10:09 Sent To I
Notes
2016-11-22 10:10:36NO RACEWAYS ALLOWED.
2016-11-18 13:52:19ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 2 Status F Date 2016-10-20 Cont ID  
Sent By   Date 2016-10-20 Time   Rev Time 0.00
Received By kmartin Date 2016-10-20 Time 08:48 Sent To B
Notes
2016-10-20 08:48:39STARBUCKS COFFEE
 1. RACEWAYS ARE NOT PERMITTED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].
2016-10-11 13:42:12ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-16 Cont ID  
Sent By kmartin Date 2016-08-16 Time   Rev Time 0.00
Received By kmartin Date 2016-08-15 Time 08:30 Sent To  
Notes
2016-08-16 13:33:50STARBUCKS COFFEE
 1. RACEWAYS ARE NOT PERMITTED.
 2. SIGN BANDS SHALL NOT EXCEED 60% OF BUILDING FA?ADE,
 PROVIDE ELEVATIONS WITH SIGN LOCATION AND SIZE DETAILS.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].