Plan Review Details - Permit 16080549
Plan Review Stops For Permit 16080549
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By mvaldes Date 2016-08-24 Time 09:52 Rev Time 0.00
Received By mvaldes Date 2016-08-24 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By mvaldes Date 2016-08-15 Time 16:33 Rev Time 0.00
Received By mvaldes Date 2016-08-15 Time 16:14 Sent To  
Notes
2016-08-15 16:41:24REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT
  
 3) CLARIFY THE EXTENT OF THE SCOPE OF WORK ? THE WORK
 BEING DONE ISN'T JUST ELECTRICAL SO THEREFORE MARK ON
 THE PLANS SEPERATE PERMITS FOR MECH, PLUMBING &
 BUILDING IF APPLICABLE.
  
 4) PLANS MUST BE SIGNED AND SEALED BY DESIGN
 PROFFESIONAL IN ACCORDANCE WITH FLORIDA STATUE 471 &
 481. PHOTO COPY NOT ACCEPTABLE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-24 Cont ID  
Sent By mvaldes Date 2016-08-24 Time 09:38 Rev Time 0.00
Received By mvaldes Date 2016-08-19 Time 15:15 Sent To  
Notes
2016-08-19 15:15:20RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-15 Cont ID  
Sent By mvaldes Date 2016-08-15 Time 16:41 Rev Time 0.00
Received By mvaldes Date 2016-08-12 Time 12:52 Sent To  
Notes
2016-08-12 12:52:47ROUTED TO ELECTRICAL INBOX