Plan Review Details - Permit 16080543
Plan Review Stops For Permit 16080543
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 07:20 Rev Time 0.00
Received By shill Date 2017-02-15 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date   Cont ID  
Sent By shill Date 2017-01-05 Time 17:58 Rev Time 0.00
Received By shill Date 2017-01-05 Time 12:14 Sent To  
Notes
2017-01-06 09:53:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A VIOLATION WAS ISSUED FOR THIS PROPERTY (2200
 AUSTRALIAN AVE). PLEASE ADVISE AS TO THE STATUS OF THIS
 VIOLATION. ALL PERMIT APPEAR TO BE ON THE MAIN ADDRESS.
  
 PROVIDE INFORMATION VIA EMAIL TO ADVISE HOW THE
 VIOLATION HAS BEEN RESOLVED: BLDG 2200 1ST & 2ND FLOOR
 DRYWALL CORRIDOR + APTS
  
 2. ADDRESS FIRE COMMENTS. A BUILDING REVIEW IS REQUIRED
 FOR NEW SHEETS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2016-10-24 Time 14:42 Sent To  
Notes
2016-10-24 15:20:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080543
 ADD: 2210 N. AUSTRALIAN AVE.
 CONT: MONROE CONTRACTING
 TEL: 561-455-6600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 24/2016
 ACTION: DENIED
  
 1) SHEET A102.1 THE 1ST FLOOR OF A I-2 OCCUPANCY DOES
 NOT SHOW THE I-2 OCCUPANCY SEPARATED INTO 2 OR MORE
 SMOKE COMPARTMENTS. SEE THE 2014 FBC-B 407.5. THE SMOKE
 BARRIER SHALL BE CONSTRUCTED IN ACCORDANE WITH 709.1-
 709.8.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 11:59 Rev Time  
Received By jwitmer Date 2016-08-25 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By vperez Date 2017-02-15 Time 07:49 Rev Time 0.00
Received By vperez Date 2017-02-15 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 09:39 Rev Time 0.00
Received By mvaldes Date 2017-01-18 Time 08:48 Sent To  
Notes
2017-01-18 09:39:593RD REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] COMPLY WITH FIRE COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-13 Cont ID  
Sent By mvaldes Date 2016-10-13 Time 15:55 Rev Time 0.00
Received By mvaldes Date 2016-10-13 Time 15:25 Sent To  
Notes
2016-10-13 16:05:342ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE EMERGENCY LIGHTING FOR MEANS OF EGRESS IN
 EXIT STAIRS AND HALLWAYS. THE ILLUMINATION LEVEL SHALL
 NOT BE LESS THAN 1' CANDLE AT THE WALKING SURFACE.
 FBC-1006
 NOT ADDRESSED, SHOW EMERGENCY LIGHTS ON FLOORS 1-6.
  
 2] EXIT SIGNS PLACEMENT SHALL BE SUCH THAT NO POINT IN
 AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS MORE THAN
 100'. ADD DIRECTIONAL ARROWS WHERE NECCESSARY. FBC-1011
 NOT ADDRESSED, SHOW EXITS ON FLOORS 1-6.
  
 3] THIS COMMENT WAS ADDRESSED WITH BLOCK NOTE.
  
 4] NEW COMMENT, PLEASE COMPY WITH FIRE REVIEWERS
 REQUEST TO SHOW FIRE ALARM DEVICE LOCATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By mvaldes Date 2016-08-22 Time 10:02 Rev Time 0.00
Received By mvaldes Date 2016-08-22 Time 08:14 Sent To  
Notes
2016-08-22 10:11:17REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] PROVIDE EMERGENCY LIGHTING FOR MEANS OF EGRESS IN
 EXIT STAIRS AND HALLWAYS. THE ILLUMINATION LEVEL SHALL
 NOT BE LESS THAN 1' CANDLE AT THE WALKING SURFACE.
 FBC-1006
  
 2] EXIT SIGNS PLACEMENT SHALL BE SUCH THAT NO POINT IN
 AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS MORE THAN
 100'. ADD DIRECTIONAL ARROWS WHERE NECCESSARY. FBC-1011
 (RED-LINED ON PLANS)
  
 3] NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 11:09 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 10:53 Sent To  
Notes
2017-02-15 11:09:492210 NORTH AUSTRALIAN AVENUE
 PERMIT #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
 *****PROVISO***** SUBMIT REVISION
  
 4TH REVIEW COMMENTS:
 REPEAT (X3) COMMENT - THE FIRST FLOOR ALF SLEEPING
 AREAS ARE NOT DIVIDED INTO TWO SMOKE COMPARTMENTS ON
 THE MECHANICAL PLAN AND FIRE SPRINKLER PLANS
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2017-01-04 Cont ID  
Sent By wjolin Date 2017-01-04 Time 10:44 Rev Time 0.00
Received By wjolin Date 2016-12-22 Time 11:14 Sent To  
Notes
2017-01-04 09:57:012210 NORTH AUSTRALIAN AVENUE
 PERMIT #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 3RD REVIEW COMMENTS:
 REPEAT COMMENT - THE FIRST FLOOR ALF SLEEPING AREAS ARE
 NOT DIVIDED INTO TWO SMOKE COMPARTMENTS. THIS WILL
 AFFECT ALL TRADES.
  
 FIRE ALARM: HOW WILL 75DB AT THE PILLOW BE ACHIEVED
 WITH NOTIFICATION APPLIANCES LOCATED ONLY IN THE COMMON
 CORRIDORS?
  
 SHEET FA-5: DESIGN INDICATES THE BUILDING WILL BE
 EVACUATED DURING GENERAL FIRE ALARM. THIS EVACUATION
 CONCEPT IS NOT SUPPORTED BY THE LIFE SAFETY CODE. THE
 CODE REQUIRES ASSISTED LIVING FACILITIES TO BE PROVIDED
 WITH AT LEAST TWO SMOKE COMPARTMENTS PER FLOOR TO ALLOW
 "DEFEND IN PLACE" WHEREBY RESIDENTS ARE RELOCATED TO AN
 ADJACENT SMOKE COMPARTMENT DURING A FIRE ALARM. THE
 FIRE ALARM DRAWINGS NEED GREATER DETAIL TO SHOW
 COMPLIANCE WITH THIS CONCEPT. HOW IS THE FIRE ALARM,
 FIRE SPRINKLER (FLOW SWITCHES) AND HVAC (FIRE/SMOKE
 DAMPERS) BEING INTEGRATED TO ALLOW DEFEND IN PLACE
 SMOKE COMPARTMENTATION?
  
 SHEET FA-5: PLANS INDICATE THIS IS A NEW MERCANTILE
 OCCUPANCY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-10-12 Cont ID  
Sent By wjolin Date 2016-10-12 Time 14:59 Rev Time 0.00
Received By wjolin Date 2016-10-12 Time 13:34 Sent To  
Notes
2016-10-12 14:59:422210 NORTH AUSTRALIAN AVENUE
 PERMIT #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW COMMENTS
 THESE DRAWINGS ARE PUBLIC RECORD FOR SHOWING COMPLIANCE
 AS A NEW ASSISTED LIVING FACILITY. WHILE MANY FIRE AND
 LIFE SAFETY FEATURES MAY BE EXISTING, A FULL AND
 COMPLETE SET OF ARCHITECTURAL AND ENGINEERING PLANS ARE
 NEEDED (ELECTRICAL, MECHANICAL, FIRE ALARM, FIRE
 SPRINKLER, ETC.). IT IS HIGHLY RECOMMENDED THAT THE
 DESIGN TEAM HAS EXPERIENCE WITH THIS TYPE OF OCCUPANCY.
  
 THE FIRST FLOOR ALF SLEEPING AREAS ARE NOT DIVIDED INTO
 TWO SMOKE COMPARTMENTS.
  
 THE FIRE ALARM, FIRE SPRINKLER AND HVAC SYSTEMS ARE
 REQUIRED TO BE ZONED WITH EACH SMOKE COMPARTMENT.
  
 TO OBTAIN A GENERAL BUILDING PERMIT, SIGNED AND SEALED
 ENGINEERING CONSTRUCTION DOCUMENTS ARE NEEDED TO SHOW
 EMERGENCY LIGHTING LOCATIONS AND MODIFICATIONS TO THE
 SMOKE ALARMS, FIRE ALARM, FIRE SPRINKLER AND HVAC
 SYSTEMS.
  
 SOME WALL REFERENCES INDICATE "FIRE AND SMOKE BARRIER
 PARTITION." THIS DESCRIPTION IS INCORRECT. IT IS EITHER
 A PARTITION OR A BARRIER.
  
 HVAC DAMPERS AND DOORS IN SMOKE BARRIERS ARE REQUIRED
 TO RESIST THE PASSAGE OF SMOKE IN ADDITION TO HAVING A
 FIRE RESISTANCE RATING.
  
 UL ASSEMBLIES: THE UL ASSEMBLY DETAILS ARE BARELY
 READABLE AND THE WALL TYPES AND LOCATIONS ARE NOT
 REFERENCED ON THE PLANS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
  
 ORIGINAL REVIEW COMMENTS
 PER FFPC 101-32.3.3.4.7 APPROVED SMOKE ALARMS SHALL BE
 INSTALLED INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
 PER FFPC 101-32.3.3.4.8.1 CORRIDORS AND SPACES OPEN TO
 THE CORRIDORS SHALL BE PROVIDED WITH SMOKE DETECTORS
 THAT COMPLY WITH NFPA 72, NATIONAL FIRE ALARM AND
 SIGNALING CODE, AND ARE ARRANGED TO INITIATE AN ALARM
 THAT IS AUDIBLE IN ALL SLEEPING AREAS.
  
 PER FFPC 101-32.3.3.7 BUILDINGS SHALL BE SUBDIVIDED BY
 SMOKE BARRIERS. EVERY STORY SHALL BE DIVIDED INTO NOT
 LESS THAN TWO SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL
 HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING,
  
 PER FFPC 101-32.3.3.7.15 CROSS-CORRIDOR OPENINGS IN
 SMOKE BARRIERS SHALL BE PROTECTED BY A PAIR OF SWINGING
 DOORS OR A HORIZONTAL-SLIDING DOOR. VISION PANELS
 CONSISTING OF FIRE-RATED GLAZING OR WIRED GLASS PANELS
 IN APPROVED FRAMES SHALL BE PROVIDED IN EACH
 CROSS-CORRIDOR SWINGING DOOR AND IN EACH CROSS-CORRIDOR
 HORIZONTAL-SLIDING DOOR IN A SMOKE BARRIER.
  
 BUILDING IS PROTECTED WITH AN AUTOMATIC SPRINKLER
 SYSTEM. SPRINKLERS ARE REQUIRED TO BE QUICK RESPONSE OR
 RESIDENTIAL STYLE. PLEASE CONFIRM.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By wjolin Date 2016-08-26 Time 15:49 Rev Time 0.00
Received By wjolin Date 2016-08-26 Time 14:10 Sent To  
Notes
2016-08-26 15:23:452210 NORTH AUSTRALIAN AVENUE
 PERMIT #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER FFPC 101-32.3.2.3.3 THE WIDTH OF CORRIDORS SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD SERVED BUT SHALL BE
 NOT LESS THAN 60-INCHES. THE PLANS STATE THE CORRIDORS
 ARE 60-INCHES WIDE; HOWEVER, THE SCALED PLANS INDICATE
 THE CORRIDORS ARE SMALLER.
  
 PER FFPC 101-33.3.3.2 LAUNDRY AND STORAGE ROOMS LARGER
 THAN 100 SQUARE FEET SHALL HAVE A 1-HOUR FIRE
 RESISTANCE RATING.
  
 PER FFPC 101-32.3.3.4.3 A FIRE ALARM ANNUNCIATOR PANEL,
 CONNECTED TO THE FIRE ALARM SYSTEM, SHALL BE PROVIDED
 AT A LOCATION READILY ACCESSIBLE FROM THE PRIMARY POINT
 OF ENTRY FOR EMERGENCY RESPONSE PERSONNEL.
  
 PER FFPC 101-32.3.3.4.7 APPROVED SMOKE ALARMS SHALL BE
 INSTALLED INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
 PER FFPC 101-32.3.3.4.8.1 CORRIDORS AND SPACES OPEN TO
 THE CORRIDORS SHALL BE PROVIDED WITH SMOKE DETECTORS
 THAT COMPLY WITH NFPA 72, NATIONAL FIRE ALARM AND
 SIGNALING CODE, AND ARE ARRANGED TO INITIATE AN ALARM
 THAT IS AUDIBLE IN ALL SLEEPING AREAS.
  
 PER FFPC 101-32.3.3.6.2 SLEEPING ROOMS SHALL BE
 SEPARATED FROM CORRIDORS, LIVING AREAS, AND KITCHENS BY
 SMOKE PARTITION WALLS HAVING A MINIMUM 30-MINUTE FIRE
 RESISTANCE RATING.
  
 PER FFPC 101-32.3.3.7 BUILDINGS SHALL BE SUBDIVIDED BY
 SMOKE BARRIERS. EVERY STORY SHALL BE DIVIDED INTO NOT
 LESS THAN TWO SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL
 HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING,
  
 PER FFPC 101-32.3.3.7.15 CROSS-CORRIDOR OPENINGS IN
 SMOKE BARRIERS SHALL BE PROTECTED BY A PAIR OF SWINGING
 DOORS OR A HORIZONTAL-SLIDING DOOR. VISION PANELS
 CONSISTING OF FIRE-RATED GLAZING OR WIRED GLASS PANELS
 IN APPROVED FRAMES SHALL BE PROVIDED IN EACH
 CROSS-CORRIDOR SWINGING DOOR AND IN EACH CROSS-CORRIDOR
 HORIZONTAL-SLIDING DOOR IN A SMOKE BARRIER.
  
 BUILDING IS PROTECTED WITH AN AUTOMATIC SPRINKLER
 SYSTEM. SPRINKLERS ARE REQUIRED TO BE QUICK RESPONSE OR
 RESIDENTIAL STYLE. PLEASE CONFIRM.
  
 WHAT TYPE OF DOOR SECURITY IS BEING PROPOSED?
  
 **FIRE INSPECTOR HAS FIELD VERIFIED THAT WORK HAS
 ALREADY BEEN PERFORMED WITHOUT A PERMIT. END UNITS ON
 FLOORS 5 AND 6 HAVE BEEN CONVERTED RESIDENTAL UNITS
 INTO LOUNGE TYPE ROOMS AND NURSE STATIONS. WHY AREN'T
 THESE CHANGES DOCUMENTED ON THE PLANS?**
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 07:20 Rev Time 0.00
Received By shill Date 2017-02-01 Time 10:17 Sent To  
Notes
2017-02-02 10:18:24C12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 09:40 Rev Time 0.00
Received By mvaldes Date 2016-12-16 Time 11:04 Sent To  
Notes
2016-12-19 11:04:24C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-24 Cont ID  
Sent By   Date 2016-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2016-09-27 Time 15:51 Sent To  
Notes
2016-09-27 15:52:04C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-16 Cont ID  
Sent By cpuell Date 2016-09-16 Time 14:21 Rev Time 0.00
Received By cpuell Date 2016-08-11 Time 11:11 Sent To  
Notes
2016-09-16 14:22:23NATHAN FORGOT TO PUT RESULTS IN BUT PERMIT IS READY TO
 BE RESUBMITTED. CP
2016-08-12 11:11:18C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By jwitmer Date 2016-08-25 Time 11:59 Rev Time  
Received By jwitmer Date 2016-08-25 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-02-06 Cont ID  
Sent By ccole Date 2017-02-06 Time 15:51 Rev Time 0.00
Received By ccole Date 2017-02-06 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 15:39 Rev Time 0.00
Received By ccole Date 2016-12-29 Time 15:14 Sent To  
Notes
2016-12-29 16:25:253RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080543
 12/28/16
  
 1) SHEET M-1: PLEASE CLEARLY IDENTIFY THE SMOKE BARRIER
 AND CLARIFY WHY THERE IS A FS SYMBOL AT THE EMERGENCY
 CALL PANEL LOCATION. I AM NOT SEEING A DUCT OR A
 TRANSFER ALTHOUGH THE NOTE ON THE SHEET IS INDICATING
 TWO DUCT PENETRATIONS. CLARIFY HOW AIR IS BEING
 RETURNED FROM THE CORRIDOR, AND PLEASE NOTE THE
 FOLLOWING A) NO RETURN GRILLS OR SUPPLY DIFFUSERS ARE
 SHOWN IN THE
  
 CEILING PLAN ON A106.1 B) THE SMOKE BARRIER WALLS ARE
 NOT SHOWN ON THE CEILING PLAN. C) CORRIDORS SHALL NOT
 BE USED AS RETURN AIR DUCTS- SECTION 601.2.
  
 2) SHOW THE AC SHAFTS ON THE ARCHITECTURAL PLANS AND
 PROVIDE HOURLY FIRE RATING AND ASSEMBLY DETAILS.
  
 3) M-2: SHOW THE THE EXISTING DRYER EXHAUST DUCT RUN
 AND TERMINATION LOCATION. PLEASE NOTE AN INDEPENDENT
 SHAFT IS REQUIRED AND THE EXHAUST DUCTS SHALL NOT RUN
 THROUGH A PLENUM SPACE- SEE SECTION 504.
  
 4) M-4: PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION
 FOR THE FIRE/SMOKE DAMPERS. INDICATE IF THE DAMPERS ARE
 STANDARD OR DYNAMIC AND PROVIDE SEQUENCES OF OPERATION.
  
 5) AC COOLING AND HEATING CALCULATIONS NOT PROVIDED FOR
 THE 4TH-6TH FLOOR LOBBIES ALTHOUGH THE PLANS SHOW
 SUPPLY AIR TO THOSE AREAS.
  
 6) PROVIDE EQUIPMENT SCHEDULES FOR ALL AC SYSTEMS SHOWN
 OR REFERENCED ON THE PLANS.
  
 7) SHOW THE LOCATION OF THE AIR HANDLER SUPPLYING THE
 LOBBIES AND STORAGE ROOMS, AND PROVIDE SUPPLY CFMS AT
 ALL DIFFUSERS ND GRILLS SHOWN IN THOSE AREAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-12 Cont ID  
Sent By ccole Date 2016-10-12 Time 11:58 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 11:58 Sent To  
Notes
2016-10-12 12:28:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080543
 10/12/16
  
 1) SHEET A102.1: THE REVISED PLAN INDICATES A
 VENTILATION RATE OF 5 CFM PER PERSON FOR AN ( I-1
 DORMITORY), HOWEVER THE CLASSIFICATION (I-1 DORMITORY)
 IS NOT FOUND IN TABLE 403.3. DORMITORY IS GROUPED WITH
 HOTELS AND MOTELS IN THE TABLE. PLEASE REFER TO TO
 SECTION 308.3 FBC-14 BUILDING WHERE EXAMPLES OF I-1
 FACILITES ARE SHOWN TO INCLUDE ASSISTED LIVING,
 CONGREGATE CARE, AND CONVALESCENT CARE FACILITIES.
 PLEASE PROVIDE THE APPROPRIATE VENTILATION RATE FOR THE
 NEW I-1 FACILITY THAT IS MOST SIMILAR TO THE USE
 CLASSIFICATIONS IN THE TABLE I.E. PATIENT ROOMS AT 25
 CFMS PER PERSON OR RESIDIENTIAL LIVING AREAS AT 15 CFM
 PER PERSON. PLEASE THEN PROVIDE THE CALCULATIONS FOR
 ALL ROOMS AND SPACES ON THE PLAN INCLUDING A SCHEDULE
 THAT INDICATES THE "REQUIRED" AND "PROVIDED" CFMS OF
 OUTDOOR AIR AND EXHAUST. IDENTIFY WHICH SYSTEMS ARE
 PROVIDING THE AIR AND EXHAUST INCLUDING COOLING AND
 HEATING AND SUPPLY CFM CAPACITIES FOR EACH AC SYSTEM,
 AND CFM CAPACITIES FOR ALL EXHAUST SYSTEMS.
  
 2) PLEASE SHOW THE EXISTING AC DUCT LAYOUTS ON ALL
 FLOORS INCLUDING: A) DUCT, DIFFUSER, AND GRILL SIZES.
 B) LOCATIONS OF ALL FIRE AND FIRE/SMOKE DAMPERS, AND
 DUCT SMOKE DETECTORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 17:03 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 17:03 Sent To  
Notes
2016-08-23 17:20:271ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CODES
 PERMIT #16080543
 8/23/16
  
 1) THE PLANS INDICATE A CHANGE OF OCCUPANCY AS DEFINED
 IN SECTION 202 FBC-14 EXISTING BUILDING CODE. PLEASE
 SEE SECTION 1009.1 FBC-14 AND PROVIDE VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES, INCLUDING
 EXHAUST VENTILATION WHERE REQUIRED.
  
 2) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 PLEASE NOTE ENERGY CALCULATIONS MAY BE REQUIRED- SEE
 SECTION C101.5.1 FOR COMPLIANCE MATERIALS.
  
 3) PROVIDE MECHANICAL PLANS INDICATING ALL PROPOSED
 ALTERATIONS TO THE EXISTING SYSTEMS (IF APPLICABLE).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-02-14 Cont ID  
Sent By gjohnson Date 2017-02-14 Time 15:02 Rev Time 0.00
Received By gjohnson Date 2017-02-14 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 16:20 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 16:20 Sent To  
Notes
2017-01-13 16:22:301ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1. COMPLY WITH ALL TRADE COMMENTS. WPB AMEND TO FBC
 107.2.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By gjohnson Date 2016-10-24 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2016-10-21 Time 16:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-09 Cont ID  
Sent By gjohnson Date 2016-09-09 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2016-09-09 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2017-02-07 Cont ID  
Sent By njwira Date 2017-02-07 Time 17:10 Rev Time 0.00
Received By njwira Date 2017-02-07 Time 13:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By njwira Date 2017-01-13 Time 15:13 Rev Time 0.00
Received By njwira Date 2017-01-13 Time 14:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-11 Cont ID  
Sent By njwira Date 2016-10-11 Time 15:59 Rev Time 0.00
Received By njwira Date 2016-09-30 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-24 Cont ID  
Sent By llouie Date 2016-10-24 Time   Rev Time 0.00
Received By njwira Date 2016-09-12 Time 14:21 Sent To  
Notes
2016-09-15 15:30:25ROUTED TO ANGELA VANN