Plan Review Details - Permit 16080511
Plan Review Stops For Permit 16080511
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-22 Cont ID  
Sent By jwitmer Date 2016-12-22 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2016-12-22 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-21 Cont ID  
Sent By jwitmer Date 2016-10-21 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2016-10-21 Time 11:29 Sent To  
Notes
2016-10-21 11:54:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080511
 ADD: 2471 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????????? NOT PROVIDED
 E-MAIL: ???????????NOT PROVIDED
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT. 21/ 2016
 ACTION: DENIED
  
 1) PLEASE SEE FIRE COMMENTS 2ND REOUND COMMENTS AND
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By jwitmer Date 2016-08-22 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2016-08-22 Time 07:02 Sent To  
Notes
2016-08-22 10:42:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080511
 ADD: 2471 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????????? NOT PROVIDED
 E-MAIL: ???????????NOT PROVIDED
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUG. 22/ 2016
 ACTION: DENIED
  
 1) SHEET A1.00 PLEASE REVIEW THE SIGNAGE REQUIREMENTS
 ARE TO THE ADA. PLEASE REVIEW THE 2014
 FBC-ACCESSIBILITY CODE 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES (1220 MM) MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND SURFACE, MEASURED FROM THE BASELINE OF
 THE LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER.
  
 2) DISCREPANCY IN PLANS, SEE SHEET A1.01 NOTE # 4 THE
 REMOVAL OF DOOR AND FRAME AND SHEET A2.01 NOTE # 28
 THIS DOOR IS TO BE PERMANENTLY SHUT AND THE HANDLES
 REMOVED. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 2014 FBC-B 1008.1 MEANS OF EGRESS DOORS SHALL BE
 READILY DISTINGUISHABLE FROM THE ADJACENT CONSTRUCTION
 AND FINISHES SUCH THAT THE DOORS ARE EASILY
 RECOGNIZABLE AS DOORS. MIRRORS OR SIMILAR REFLECTING
 MATERIALS SHALL NOT BE USED ON MEANS OF EGRESS DOORS.
 MEANS OF EGRESS DOORS SHALL NOT BE CONCEALED BY
 CURTAINS, DRAPES, DECORATIONS OR SIMILAR MATERIALS.
  
 3A)KEYNOTE# 28/ DOORS TO BE REMOVED AND TURNED INTO
 STOREFRONT GLAZING PLEASE PROVIDE COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS/ STOREFRONT
  
 3B) KEYNOTE # 28. FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) KEYNOTE # 28 DOOR TO BE REMOVED THEN SUPPLY
 COMPLIANCE WITH 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 5) SHEET A2.01 THE EXISTING DOOR 104 DOES NOT HAVE THE
 REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2014
 FBC-ACCESS. CODE 404.2.4.1 MANEUVERING CLEARANCES.
 6) THE CONTRACTORS PROJECT COST IS APPROXIMATELY
 $550,000.00 DOLLARS, UP TO 20% OF THE BUDGET CAN GO
 TOWARDS ACCESSIBLE UPGRADES GETTING THE TENANT SPACE TO
 BE IN COMPLIANCE WITH THE 2014 ACCESSIBILITY CODE.
 PLEASE SUBMIT AN ITEMIZED LETTER WHERE THESE FUNDS WILL
 BE SPENT AND IN THE ORDER THAT IS STATED BELOW.
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 7) SHEET A2.01 DOES SHOW THERE TO BE 3 CASH REGISTERS
 BUT THERE ARE NO DETAILS SHOWING COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE 904.3 CHECK-OUT AISLES.
 CHECK-OUT AISLES SHALL COMPLY WITH 904.3.
  
 904.3.1 AISLE.
 AISLES SHALL COMPLY WITH 403.
  
 904.3.2 COUNTER.
 THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER.
 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 14:31 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By mvaldes Date 2016-08-15 Time 15:13 Rev Time 0.00
Received By mvaldes Date 2016-08-15 Time 12:28 Sent To  
Notes
2016-08-15 15:15:05JOB PERMIT NUMBER: 16080511
 JOB ADDRESS: 2471 OKEECHOBEE BLVD
 WEST PALM BEACH FLORIDA, SUITE PS
 DATE: AUGUST 15, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) FIRE ALARM AND LOW VOLTAGE SHALL BE UNDER A SEPARATE
 PERMIT WITH SEPARATE SHOP DRAWINGS. [ INFORMATIONAL
 NOTE ]
 2) PROVIDE FPL AVAILABLE FAULT CURRENT LETTER AND
 DEMONSTRATE AIC RATING OF OVERCURRENT DEVICES PLUS SC
 RATING OF EQUIPMENT TO WITHSTAND L+L, L+N, AND GROUND
 FAULTS LIKELY TO BE IMPOSED ONTO THE ELECTRICAL SYSTEM.
 NEC 110.9, 110.10, 110.24(A)(B)
 3) SHEET E-1, CLARIFY HOW PANEL ??DP?? SHOWS A 60 AMP
 PROTECTIVE DEVICE FOR PANEL ?A? WHEN THE DEMANDED LOAD
 IS 69 AMPS ? FBC-107
 4) SHEET E-1, SHOW EXISTING SERVICE CONDUCTOR SIZE WITH
 INSULATION RATING AND SPECIFY HOW THE CONNECTION WITHIN
 THE EXISTING SERVICE DISCONNECT IS GOING TO BE
 MECHANICALLY MADE, FURTHERMORE APPLY ADEQUATE WARNING
 LABELING TO THE ENCLOSURE FOR FEED THRU UNFUSED LINES.
 FBC-107, NEC 110.12
 5) SHEET E-1, FEEDER SCHEDULE REFLECTS THE SERVICE
 BEING PARALLELED IN 3 RACEWAYS, IS THE INTENT 2
 RACEWAYS ? IF NOT SPECIFY EQUIPMENT TO BE IDENTIFIED
 FOR MULTI-TERMINAL PARTS TO ENSURE A GOOD CONNECTION
 WITHOUT DAMAGING THE CONDUCTORS. NEC 110.14(A)
 6) PROVIDE LIGHT DENSITY CHART FOR MAXIMUM ENERGY
 ALLOWANCES IN THE BUILDING SPACE. FBC-E SECTION C405.5
 INTERIOR LIGHTING POWER REQUIREMENTS.
 7) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP. ADD THIS CODE LANGUAGE ON
 SHEET E-3 GENERAL NOTE G.
 8) FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL 125V,
 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES,
 COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. [ ADD A
 NOTE TO COMPLY. ]
 9) NEC 406.3(D) RECEPTACLES INCORPORATING AN ISOLATING
 GROUNDING CONDUCTOR CONNECTION INTENDED FOR THE
 REDUCTION OF ELECTRICAL NOISE SHALL BE IDENTIFIED BY AN
 ORANGE TRIANGLE ON THE FACE OF THE FACEPLATE. [ A NOTE
 WILL SUFFICE ]
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED TO
 PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING EACH
 ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER?S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF
 YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-12-20 Cont ID  
Sent By wjolin Date 2016-12-20 Time 12:26 Rev Time 0.00
Received By wjolin Date 2016-12-20 Time 12:25 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-09-23 Cont ID  
Sent By wjolin Date 2016-09-23 Time 15:49 Rev Time 0.00
Received By wjolin Date 2016-09-23 Time 15:44 Sent To  
Notes
2016-09-23 15:49:472471 OKEECHOBEE BOULEVARD
 PERMIT #16080511
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 ADDITIONAL INFORMATION: FOR ISSUANCE OF A GENERAL
 BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS. PER FBC SECTION 907.1.1
 CONSTRUCTION DOCUMENTS - CONSTRUCTION DOCUMENTS FOR
 FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION
 CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-19 Cont ID  
Sent By wjolin Date 2016-08-19 Time 10:54 Rev Time 0.00
Received By wjolin Date 2016-08-19 Time 10:16 Sent To  
Notes
2016-08-19 10:54:112471 OKEECHOBEE BOULEVARD
 PERMIT #16080511
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-22 Cont ID  
Sent By jwitmer Date 2016-12-22 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2016-12-16 Time 10:34 Sent To  
Notes
2016-12-19 10:34:55RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-21 Cont ID  
Sent By jwitmer Date 2016-10-21 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2016-09-21 Time 10:06 Sent To  
Notes
2016-09-22 10:07:13C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-31 Cont ID  
Sent By gjohnson Date 2016-08-31 Time 09:04 Rev Time 0.00
Received By gjohnson Date 2016-08-11 Time 10:05 Sent To  
Notes
2016-08-12 10:05:29C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By jwitmer Date 2016-08-22 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2016-08-22 Time 07:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-28 Cont ID  
Sent By ccole Date 2016-09-28 Time 16:50 Rev Time 0.00
Received By ccole Date 2016-09-28 Time 16:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 15:14 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 15:14 Sent To  
Notes
2016-08-23 15:46:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080511
 8/23/16
  
 1) THE INSTALLED EFFICIENCIES LISTED ON THE SUBMITTED
 ENERGY FORM C402 DO NOT MATCH EFFICIENCIES LISTED IN
 THE EQUIPMENT SCHEDULES.
  
 2) FORM C402 MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 3) THE COOLING AND HEATING CAPACITIES OF RTU'S 5 & 6
 EXCEED THE CALCULATED LOADS SUBMITTED- SEE SECTION
 C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 4) M-1: PLEASE ENLARGE THE RTU DETAILS SO THAT THE
 SMOKE DETECTOR AND CO2 DETECTORS ARE VISIBLE.
  
 5) M-2: INDICATE HOW THE SD'S AND CO2 SENSORS WILL BE
 INSTALLED IN THE STEP DOWN DIFFUSER DETAIL.
  
 6) PROVIDE A SEQUENCE OF OPERATION FOR THE CO2 SENSORS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH APPROVAL
 SIGNATURE BY THE EOR.
  
 7) PROVIDE WIND LOAD DESIGN CRITERIA AND COMPLETE
 DETAILS FOR ANCHORING THE RTU'S, CURBS, AND CURB
 ADAPTERS TO THE ROOF STRUCTURE- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-21 Cont ID  
Sent By gjohnson Date 2016-10-21 Time 09:20 Rev Time 0.00
Received By gjohnson Date 2016-10-20 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-31 Cont ID  
Sent By gjohnson Date 2016-08-31 Time 09:02 Rev Time 0.00
Received By gjohnson Date 2016-08-31 Time 09:02 Sent To  
Notes
***NONE***