Plan Review Details - Permit 16080482
| Plan Review Stops For Permit 16080482 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-08-15 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-08-15 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-08-15 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-09-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-08-29 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-08-10 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-09-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-08-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-23 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-23 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2016-08-23 14:03:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080482 | | | 8/23/16 | | | | | | 1) SHEET 3.0 MP:THE 14X6" SUPPLY TRUNKS ARE UNDERSIZED | | | FOR 600 CFMS EACH- MINIMUM SIZE REQUIRED IS 14X8" BASED | | | ON THE ASHRAE HANDBOOK OF FUNDAMENTALS. | | | | | | 2) 3.0 MP: PLEASE CORRECT THE FRESH AIR CALCULATION | | | SPECIFYING 2000 CFMS REQUIRED FOR THE KITCHEN. REFER TO | | | TABLE 403.3 WHICH REQUIRES A 0.7 CFM PER SQ. FT. | | | EXHAUST RATE FOR THE KITCHEN. | | | | | | 3) 3.0 MP: PLEASE CLARIFY THE PURPOSE OF THE 6" | | | MOTORIZED DAMPER SHOWN IN THE DINNIG ROOM. WHICH SYSTEM | | | IS THE DAMPER CONNECTED TO. | | | | | | 6) 3.0 MP: BASED ON ASHRAE STANDARD RETURN GRILL SIZING | | | - 2CFMS PER SQ. IN., THE 30X8" RETURN GRILL HAS AN | | | INSUFFICIENT CAPACITY OF 580 CFMS- PLEASE ENLARGE THE | | | GRILL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-09-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-09-01 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-08-29 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-08-26 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2016-08-29 09:06:44 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE A CODE COMPLAINT SET OF PLANS THAT | | | SHOWS THE EXACT SCOPE OF WORK THAT WAS DONE. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |