Plan Review Details - Permit 16080477
Plan Review Stops For Permit 16080477
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-09 Cont ID  
Sent By cthroop Date 2016-09-09 Time 09:27 Rev Time 0.00
Received By cthroop Date 2016-09-09 Time 09:27 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-08-16 Cont ID  
Sent By jgomez Date 2016-08-16 Time 09:06 Rev Time 0.00
Received By jgomez Date 2016-08-16 Time 07:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-12 Cont ID  
Sent By vperez Date 2016-08-12 Time 07:20 Rev Time 0.00
Received By vperez Date 2016-08-12 Time 07:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By fmittner Date 2016-08-22 Time 16:00 Rev Time 0.00
Received By fmittner Date 2016-08-22 Time 16:00 Sent To  
Notes
2016-08-17 13:22:47ROUTED TO FREDERIKE MITTNER
2016-08-15 19:28:21REVISED DRAWINGS. SOUTH FACADE WAS CHANGED ON SECOND
 FLOOR PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-14 Cont ID  
Sent By jgomez Date 2016-09-14 Time 10:20 Rev Time 0.00
Received By jgomez Date 2016-09-14 Time 10:20 Sent To  
Notes
2016-09-14 10:20:56SUBMITTAL OF REVISED A/C PLAN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-13 Cont ID  
Sent By jgomez Date 2016-09-13 Time 15:27 Rev Time 0.00
Received By jgomez Date 2016-09-02 Time 08:45 Sent To  
Notes
2016-09-06 08:46:05JGOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-22 Cont ID  
Sent By jgomez Date 2016-08-22 Time 17:19 Rev Time 0.00
Received By jgomez Date 2016-08-11 Time 14:50 Sent To  
Notes
2016-08-11 14:50:43REVISION ROUTED TO VPEREZ

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-14 Cont ID  
Sent By jgomez Date 2016-09-14 Time 10:17 Rev Time 0.00
Received By jgomez Date 2016-09-14 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-09-13 Cont ID  
Sent By jgomez Date 2016-09-13 Time 15:27 Rev Time 0.00
Received By jgomez Date 2016-09-13 Time 15:27 Sent To  
Notes
2016-09-13 16:02:15RESIDENTIAL REVISION, THIRD MECHANICAL CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT.
 1- THE MASTER BEDROOM AND BEDROOM #1 ON THE SECOND
 FLOOR DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). THE
 TRANSFER GRILLES (14"X6") ARE TOO SMALL BASED ON THE
 SUPPLY AIR. NOTE: THE MASTER BEDROOM NEEDS TO CONSIDER
 ALL THE SUPPLY AIR, INCLUDING THE CLOSET AND BATHROOM.
 SEE EXCEPTIONS #2 AND #3 OF SEC M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE PLANS AS
 REQUIRED.
  
 RESPONSE:
 (1) ALL THE SUPPLY AIR INTO THE MASTER BEDROOM,
 INCLUDING CLOSET AND BATHROOM NEEDS TO BE CONSIDERED TO
 SIZE THE TRANSFER GRILL. 24"X6" TRANSFER GRILL DOESN'T
 COMPLY. SEE EXCEPTION #2 AND #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED.
  
 (2) TRANSFER GRILLES AND TRANSFER DUCTS ARE NOT THE
 SAME. TRANSFER GRILL SIZE IS NOT DETERMINED BY THE
 1-1/2 TIMES THE CROSS SECTIONAL AREA. SEE EXCEPTION #1
 AND #2 OF SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION
 (2014). 14"X6" TRANSFER GRILL SPECIFIED FOR BEDROOM #1
 DOESN'T COMPLY. REVISE SIZE OF TRANSFER GRILL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-22 Cont ID  
Sent By jgomez Date 2016-08-22 Time 17:19 Rev Time 0.00
Received By jgomez Date 2016-08-22 Time 17:17 Sent To  
Notes
2016-08-22 17:39:52RESIDENTIAL REVISION, MECHANICAL SECOND CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- THE SITTING ROOM ON THE FIRST FLOOR DOESN'T COMPLY
 WITH THE BALANCED RETURN AIR SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE PLAN AS
 REQUIRED.
  
 2- THE MASTER BEDROOM AND BEDROOM #1 ON THE SECOND
 FLOOR DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). THE
 TRANSFER GRILLES (14"X6") ARE TOO SMALL BASED ON THE
 SUPPLY AIR. NOTE: THE MASTER BEDROOM NEEDS TO CONSIDER
 ALL THE SUPPLY AIR, INCLUDING THE CLOSET AND BATHROOM.
 SEE EXCEPTIONS #2 AND #3 OF SEC M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE PLANS AS
 REQUIRED.
  
 3- A/C COMPRESSOR DETAIL SPECIFIES FLORIDA PRODUCT
 APPROVAL FL14239 FOR THE HOLD DOWN CLIPS. INFORMATION
 SPECIFIED DON'T MATCH INFORMATION SHOWN ON THE FLORIDA
 PRODUCT APPROVAL. REVISE CONNECTORS TYPE, SIZE,
 EMBEDMENT INTO CONCRETE AND CORNER DISTANCE. SEE
 PRODUCT APPROVAL AND REVISE AS REQUIRED. SEC.R301.1
 FBC-RESIDENTIAL.
  
 4- PLANS NEED THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By jgomez Date 2016-08-15 Time 19:28 Rev Time 0.00
Received By jgomez Date 2016-08-15 Time 19:24 Sent To Z
Notes
2016-08-15 19:30:39RESIDENTIAL REVISION, MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- ACCORDING TO THE DESCRIPTION ON THE REVISION FORM
 AND FLOOR PLANS SUBMITTED A/C DUCT WORK LAYOUT AND
 EQUIPMENT LOCATION WAS REVISED. NEED TO SUBMIT REVISED
 MECHANICAL PLANS FOR REVIEW. PROVIDE 2 COPIES. SEC.
 107.3.5.3(10) CITY AMENDMENTS.
  
 2- ACCORDING TO CITY RECORDS, THERE IS NO MECHANICAL
 PERMIT FOR THE A/C WORK. NEED MECHANICAL PERMIT AS
 REQUIRED BY SEC. 105.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-17 Cont ID  
Sent By tklarge Date 2016-08-17 Time 06:00 Rev Time 0.00
Received By tklarge Date 2016-08-17 Time 05:51 Sent To  
Notes
***NONE***