Plan Review Details - Permit 16080448
Plan Review Stops For Permit 16080448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-29 Cont ID  
Sent By cthroop Date 2016-09-29 Time 14:40 Rev Time 0.00
Received By cthroop Date 2016-09-29 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By cthroop Date 2016-08-18 Time 10:58 Rev Time 0.00
Received By cthroop Date 2016-08-18 Time 10:58 Sent To  
Notes
2016-08-18 11:05:56BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/18/16
  
 1. PROVIDE DESIGN WIND LOAD CALCULATIONS.
 2. PROVIDE DIRECT BURIAL AUGER DEMENSIONS (W X D) BASED
 ON WIND LOADS.
  
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-29 Cont ID  
Sent By mvaldes Date 2016-09-29 Time 14:07 Rev Time 0.00
Received By mvaldes Date 2016-09-29 Time 14:07 Sent To  
Notes
2016-09-29 14:07:37ROUTED TO CT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By mvaldes Date 2016-08-18 Time 10:32 Rev Time 0.00
Received By mvaldes Date 2016-08-18 Time 09:50 Sent To  
Notes
2016-08-18 10:36:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PROVIDE PHOTOMETRICS TO COMPLY WITH MINIMUM
 ILLUMINATION LEVELS AND EXTERIOR BUILDING LIGHTING
 ENERGY ALLOWANCES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-29 Cont ID  
Sent By cthroop Date 2016-09-29 Time 14:26 Rev Time 0.00
Received By cthroop Date 2016-09-28 Time 14:10 Sent To  
Notes
2016-09-28 14:10:54RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-17 Cont ID  
Sent By cpuell Date 2016-08-17 Time 13:51 Rev Time 0.00
Received By cpuell Date 2016-08-10 Time 13:00 Sent To  
Notes
2016-08-10 13:00:55ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2016-08-17 Time   Rev Time 0.00
Received By njwira Date 2016-08-10 Time 17:15 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved