Plan Review Details - Permit 16080447
| Plan Review Stops For Permit 16080447 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-08-17 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-08-17 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-08-17 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-08-11 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-08-11 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-08-11 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2016-08-11 16:07:39 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PROVIDE NEW PANEL SCHEDULES WITH AVALIUABLE FAULT | | | CURRENTS NEC 110.24, SHORT CIRCUIT RATINGS NEC 110.10 & | | | 110.9, AND LOAD DEMANDS 6LA, 6LB, 6TR. FBC 107 MINIMUM | | | PLAN REVIEW | | | | | | - TRANSFORMER SECONDARY CONDUCTORS SHALL TERMINATE TO | | | AN OCPD IN A PANEL-BOARD PER NEC 408.36(B) OTHERWISE | | | CLARIFY COMPLIANCE WITH NEC 450.3 & 240.21(C). | | | | | | - VALUATION SEEMS TO LOW PROVIDE OWNER SIGNED CONTRACT | | | IN ACCORDANCE WITH FBC-109. | | | | | | - NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL | | | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO | | | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED | | | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-08-17 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-08-17 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-08-16 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2016-08-16 13:24:54 | RESUB ROUTED TO MVALDES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-08-11 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-08-11 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-08-10 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2016-08-10 13:01:27 | ELEC <5K |
|
|
|