Plan Review Details - Permit 16080445
Plan Review Stops For Permit 16080445
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 15:39 Rev Time 0.00
Received By mvaldes Date 2016-08-17 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By mvaldes Date 2016-08-11 Time 16:16 Rev Time 0.00
Received By mvaldes Date 2016-08-11 Time 16:16 Sent To  
Notes
2016-08-11 16:17:34REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE NEW PANEL SCHEDULES WITH AVALIUABLE FAULT
 CURRENTS NEC 110.24, SHORT CIRCUIT RATINGS NEC 110.10 &
 110.9, AND LOAD DEMANDS 13LA, 13LB, 13TR. FBC 107
 MINIMUM PLAN REVIEW
  
 - TRANSFORMER SECONDARY CONDUCTORS SHALL TERMINATE TO
 AN OCPD IN A PANEL-BOARD PER NEC 408.36(B) OTHERWISE
 CLARIFY COMPLIANCE WITH NEC 450.3 & 240.21(C).
  
 - VALUATION SEEMS TO LOW PROVIDE OWNER SIGNED CONTRACT
 IN ACCORDANCE WITH FBC-109.
  
 - NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 15:39 Rev Time 0.00
Received By mvaldes Date 2016-08-16 Time 13:53 Sent To  
Notes
2016-08-16 13:53:27RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-11 Cont ID  
Sent By mvaldes Date 2016-08-11 Time 16:17 Rev Time 0.00
Received By mvaldes Date 2016-08-10 Time 13:01 Sent To  
Notes
2016-08-10 13:04:33ELEC <5K