| 2016-08-15 11:29:11 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DATE: 8/15/16 |
| | |
| | 1. VALUE APPEARS LOW. |
| | 2. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| | 3. PROVIDE ENERGY CALCULATIONS. |
| | 4. PROVIDE SOILS REPORT. |
| | 5. PROVIDE WINDOW AND DOOR SCHEDULE. |
| | 6. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND EXT. |
| | DOORS. |
| | 7. PROVIDE DESIGN WIND LOADS FOR OPENINGS. |
| | 8. PROVIDE ROOF FRAMINJG PLAN. |
| | 9. PROVIDE 2ND FLOOR PLAN. |
| | 10. PROVIDE FOUNDATION PLAN WITH FOOTING AND BEAM |
| | SCHEDULES. |
| | 11. PROVIDE SITE PLAN WITH SETBACKS OF NEW |
| | CONSTRUCTION. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY |
| | DELAY THE APPLICATION PROCESS. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| | |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | R401.4 SOIL TESTS. |
| | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL |
| | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, |
| | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE |
| | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL |
| | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE |
| | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. |
| | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN |
| | APPROVED METHOD. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| | WINDOW AND DOOR SUBMITTALS. |
| | |
| | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |