| 2016-08-11 16:48:56 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 530 32ND ST. |
| | JOB ADDRESS: 530 32ND ST. |
| | DESCRIPTION: INTERIOR RENOVATION, RELOCATE KITCHEN, NEW |
| | MASTER BEDROOM EXISTING BATH. |
| | MASTER PERMIT: 16080405 |
| | REVISION: |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: MOST OF WHICH MAY BE ADDRESSED WITH A BLOCK |
| | NOTE. |
| | |
| | 1. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE |
| | BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED & |
| | UNCONDITIONED SPACES. |
| | 2. FBC-R4001.15/NEC 404.2(C): WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. |
| | 3. FBC-R404.1: A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS |
| | 4. FBC-RE3902.12/NEC 210.12(B): ALL NEW OUTLETS TO BE |
| | AFCI PROTECTED. |
| | 5. FBC-R4002.14 NEC 406.12: IN ALL AREAS SPECIFIED IN |
| | 210.52, ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES |
| | SHALL BE LISTED TAMPER RESISTANT RECEPTACLES. |
| | 6. FBC-RE4002.9/NEC 406.9(B): 15 AND 20 AMPERE, 125 AND |
| | 250 VOLT RECEPTACLES INSTALLED IN A WET LOCATION SHALL |
| | HAVE AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT |
| | THE ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL |
| | BE LISTED WEATHER-RESISTANT TYPE ?WR?. |
| | 7. FBC-R 314: YOU SHALL COME INTO COMPLIANCE WITH SMOKE |
| | DETECTOR REQUIREMENTS AS FOR NEW HOMES. |
| | 8. FBC-R 315: YOU SHALL INSTALL CARBON MONOXIDE |
| | DETECTORS AS PER CODE. |
| | 9. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE |
| | EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS. |
| | 10. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM |
| | SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE |
| | TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS. |
| | INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |