Plan Review Details - Permit 16080405
Plan Review Stops For Permit 16080405
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-21 Cont ID  
Sent By rmcdouga Date 2016-10-21 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2016-10-20 Time 18:41 Sent To  
Notes
2016-10-21 08:18:59A SEPARATE PERMIT IS REQUIRED FOR THE NEW FRENCH DOORS
 AS NOTED ON THE PLANS BY THE DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By rmcdouga Date 2016-09-14 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2016-09-14 Time 10:20 Sent To  
Notes
2016-09-14 10:31:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) MAIN HOUSE SHALL COMPLY WITH FBC-R314.3.1
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) MAIN HOUSE AND GUEST HOUSE SHALL COMPLY WITH
 FBC-R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 3) THE HEADING UNDER GENERAL NOTES ON DRAWING SHEET 1,
 SPECIFIES AN ADDITION. CLEARLY INDICATE THE ADDED SPACE
 ON THE PLANS AND PROVIDE AREA TABULATIONS. FBC 107.2.1
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW
 FRENCH DOORS. THE PLANS INDICATE THAT THE DOOR
 INSTALLATION IS TO BE UNDER A SEPARATE PERMIT, HOWEVER,
 THE OTHER PERMIT IS ONLY TO REPLACE THE WINDOWS IN THE
 GUEST HOUSE.
  
 5) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND
 COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO
 FBC-R301.2.
  
 6) YOU ARE REQUIRED TO PROVIDE A BOND BREAK BETWEEN THE
 EXTERIOR STUCCO AND THE WATER BARRIER PER FBC-R703.6.3
 WATER-RESISTIVE BARRIERS. WATER-RESISTIVE BARRIERS
 SHALL BE INSTALLED AS REQUIRED IN SECTION R703.2 AND,
 WHERE APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE
 A WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION R703.8) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 15:32 Rev Time 0.00
Received By albarran Date 2016-10-25 Time 13:32 Sent To I
Notes
2016-10-25 15:32:56CONDITIONAL APPROVAL BASED ON THE ADDITION OF A SMOKE
 DETECTOR AT THE FOOT OF THE STAIRS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By albarran Date 2016-08-11 Time 16:47 Rev Time 0.00
Received By albarran Date 2016-08-11 Time 15:54 Sent To  
Notes
2016-08-11 16:48:56ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 530 32ND ST.
 JOB ADDRESS: 530 32ND ST.
 DESCRIPTION: INTERIOR RENOVATION, RELOCATE KITCHEN, NEW
 MASTER BEDROOM EXISTING BATH.
 MASTER PERMIT: 16080405
 REVISION:
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW: MOST OF WHICH MAY BE ADDRESSED WITH A BLOCK
 NOTE.
  
 1. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
 2. FBC-R4001.15/NEC 404.2(C): WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 3. FBC-R404.1: A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS
 4. FBC-RE3902.12/NEC 210.12(B): ALL NEW OUTLETS TO BE
 AFCI PROTECTED.
 5. FBC-R4002.14 NEC 406.12: IN ALL AREAS SPECIFIED IN
 210.52, ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES
 SHALL BE LISTED TAMPER RESISTANT RECEPTACLES.
 6. FBC-RE4002.9/NEC 406.9(B): 15 AND 20 AMPERE, 125 AND
 250 VOLT RECEPTACLES INSTALLED IN A WET LOCATION SHALL
 HAVE AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT
 THE ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20
 AMPERE, 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL
 BE LISTED WEATHER-RESISTANT TYPE ?WR?.
 7. FBC-R 314: YOU SHALL COME INTO COMPLIANCE WITH SMOKE
 DETECTOR REQUIREMENTS AS FOR NEW HOMES.
 8. FBC-R 315: YOU SHALL INSTALL CARBON MONOXIDE
 DETECTORS AS PER CODE.
 9. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE
 EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS.
 10. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM
 SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE
 TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS.
 INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-10-20 Cont ID  
Sent By destabro Date 2016-10-20 Time 14:56 Rev Time 0.00
Received By destabro Date 2016-10-20 Time 14:56 Sent To B
Notes
2016-10-20 15:00:4510/20/2016 - APPROVED ON BEHALF OF FRIEDERIKE MITTNER,
 CITY HISTORIC PRESERVATION PLANNER. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-08-22 Cont ID  
Sent By fmittner Date 2016-08-22 Time 16:12 Rev Time 0.00
Received By fmittner Date 2016-08-22 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 15:45 Rev Time 0.00
Received By albarran Date 2016-09-29 Time 11:09 Sent To  
Notes
2016-10-25 15:48:1710/25/16 THIS PERMIT PASSED ALL TRADE REVIEWS BUT THE
 ACCOMPANYING PERMIT (16080412) FAILED BLDG. REVIEW.
 FILE SENT TO SMALL DENIED DRAWER B. MA
2016-09-30 11:09:49R12
 **TRAVELLING WITH 16080412**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2016-09-26 Time   Rev Time 0.00
Received By lmarchan Date 2016-09-23 Time 11:00 Sent To  
Notes
2016-09-26 11:00:43RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-14 Cont ID  
Sent By rmcdouga Date 2016-09-14 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2016-08-09 Time 09:12 Sent To  
Notes
2016-08-10 09:12:56R01
 **TRAVELLING WITH 16080412**

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-09-09 Cont ID  
Sent By hmoser Date 2016-09-09 Time 13:07 Rev Time 0.00
Received By hmoser Date 2016-09-09 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 07:50 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 07:32 Sent To E
Notes
2016-10-22 07:49:46PROVISO
 A CODE COMPLIANT SANITARY RISER SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL PRIOR TO THE UNDERGROUND ROUGH
 INSPECTION. WPB AMEND. SEC. 107.3.5.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By tklarge Date 2016-08-30 Time 02:55 Rev Time 0.00
Received By tklarge Date 2016-08-30 Time 02:29 Sent To  
Notes
2016-08-30 02:49:241) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL
 THE CHANGES, ADDITIONS AND RELOCATION OF THE PLUMBING
 PIPING AND FIXTURES. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 2) SUBMIT AN EXISTING FLOOR PLAN FOR THE SECOND FLOOR.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER.WPB AMEND. TO FBC SEC. 107.2.1.
 4) IF THE WASHER/ DRYER IS A STACKED UNIT, ACCESS SHALL
 BE PROVIDED TO THE WATER SUPPLY VALVES FOR THE WASHER.
 2014 FBCR SEC.P2903.9.3.
 5) INDICATE ON THE PLAN HOW HOT WATER IS BEING SUPPLIED
 TO THE GUEST HOUSE. SHOW THE HOT WATER SUPPLY SOURCE.
 6) SHT. 1 INDICATES THAT NEW FIXTURES WILL CONNECT TO
 EXISTING PLUMBING BUT THE FIXTURES ARE BEING RELOCATED.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-20 Cont ID  
Sent By destabro Date 2016-10-20 Time 15:00 Rev Time 0.00
Received By destabro Date 2016-10-20 Time 15:00 Sent To B
Notes
2016-10-20 15:01:1910/20/2016 - APPROVED ON BEHALF OF FRIEDERIKE MITTNER,
 CITY HISTORIC PRESERVATION PLANNER. DLE

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-22 Cont ID  
Sent By fmittner Date 2016-08-22 Time 16:13 Rev Time 0.00
Received By fmittner Date 2016-08-22 Time 16:13 Sent To  
Notes
***NONE***