| 2016-08-11 11:18:44 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. ELECTRICAL SUB PERMIT REQUIRED. |
| | 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE |
| | REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM |
| | COVER REQUIREMENTS FOR CONDUITS. A NOTE WILL SUFFICE |
| | 3. RISER DIAGRAM AND PANEL SCHEDULE- PLEASE PROVIDE |
| | AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE. |
| | ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT |
| | INDICATING AIC. SHOW AIC CALCULATION BASED ON |
| | INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC |
| | 110.24 FBC 107 |
| | 4. ONE-LINE DIAGRAM TO REFLECT CONDUIT, ELECTRODE |
| | CONDUCTOR, RATINGS AMPS, AND SERVICE AND FEEDERS |
| | CONDUCTOR SIZES THROUGHOUT, FUSE RATINGS ETC. SHOW A |
| | COMPLETE ONE-LINE. FBC 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA |
| | 5. PROVIDE A SUPPLEMENTAL GROUND ROD (2) 6FT APART AT |
| | SERVICE PER NEC 250.50 PART 3 |
| | 6. LABEL SERVICE EQUIPMENT TO BE RATED FOR SERVICE |
| | ENTRANCE AND IN COMPLIANCE WITH NEC 230.79 FOR MINIMUM |
| | SERVICE CAPACITY. |
| | 7. SHOW LOADS CALCULATIONS PER NEC 220 |
| | 8. PROVIDE A GFCI/WP RECEPTACLE AT THE SERVICE FOR |
| | TEMPORARY POWER. |
| | 9. PROVIDE AN INTERSYSTEM BONDING TERMINAL AT THE |
| | SERVICE. NEC 250.94 |
| | 10. PER NEC 110.16 ARC FLASH HAZARD WARNING- PROVIDE A |
| | GENERAL NOTE ON PLANS. SEE VERBIAGE IN CODE. |
| | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |