| 2016-08-22 16:19:10 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080368 |
| | ADD: 5800 CORPORATE WAY |
| | CONT: GEN-X CONSTRUCTION |
| | TEL: 561-963-4490 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 22/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE PERMIT APPLICATION INDICATES THIS IS |
| | AN INTERIOR BUILD OUT AND RENOVATION OF THE MAIN |
| | BUILDING ONLY. THE SHEET 0.2 THE DEMO PLAN INCLUDES THE |
| | DEMOLITION OF THE INTERIOR OUT BUILDING AND WINDOWS. |
| | THIS SHOULD BE STRUCK FROM THE SCOPE OF WORK TO BE |
| | COVERED UNDER THIS PERMIT. DISCREPANCY IN THE SCOPE OF |
| | WORK, ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) PLEASE NOTE THIS STRUCTURE IS BUILT IN AN A8 FLOOD |
| | ZONE. FBC BUILDING 1612 AND CITY OF WPB CODE OF |
| | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| | "A8" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY |
| | REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF |
| | ELEVATION. BASE FLOOD FOR THE A8 FLOOD ZONE IS 14.0 FT. |
| | NGVD PLUS AN ADDITIONAL 6 INCH FREEBOARD REQUIRED BY |
| | AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | |
| | PLEASE NOTE THIS STRUCTURE WILL ALSO HAVE TO MEET THE |
| | REQUIREMENTS OF SUBSTANTIAL IMPROVEMENTS. THE P.B.C. |
| | PROPERTY APPRAISERS OFFICE LIST THE VALUE FOR THE |
| | STRUCTURE AS $489,474.00 THE VALUE OF THE PROJECT IS |
| | $424,000.00 IN VALUE WELL OVER THE 50 % OF THE VALUE |
| | FOR THE STRUCTURE. ANY FLOORS AND OR ATTENDANT |
| | EQUIPMENT PADS WILL NEED TO BE ABOVE THE 14.5 FEET |
| | NGVD. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3) PLEASE ALSO NOTE UNDER THE ENERGY CODE THE BUILDING |
| | ALSO MEETS THE DEFINITION OF RENOVATION UNDER THE 2014 |
| | FBC-ENERGY CODE. RENOVATED BUILDING. A RESIDENTIAL OR |
| | NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT |
| | VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER |
| | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. |
| | C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING |
| | COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE. |
| | THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE |
| | WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR |
| | MATERIALS THAT MEET THE INTENT OF THIS CODE. |
| | C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING |
| | SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS |
| | MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN |
| | APPENDIX C. |
| | C401.2.1 APPLICATION TO EXISTING BUILDINGS. ADDITIONS, |
| | ALTERATIONS AND REPAIRS TO EXISTING BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. SECTIONS C402, C403, C404 AND C405; OR |
| | 2. ANSI/ASHRAE/IESNA 90.1. |
| | |
| | 4) SHEET 04: |
| | 4A) THE LIFE SAFETY PLAN HAS A DISCREPANCY IN THE TYPE |
| | OF OCCUPANCY. UNDER THE HEADING OF FLORIDA BUILDING |
| | CODE 2014 EDITION THE OCCUPANCY IS LISTED AS AN A2 |
| | OCCUPANCY. WHEREAS UNDER THE HEADING ALLOWABLE HEIGHT |
| | AND AREA THE OCCUPANCY IS LISTED AS A BUSINESS. PLEASE |
| | CORRECT THE DISCREPANCY IN THE PLANS. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4B) THE SECOND ISSUE WITH THE LIFE SAFETY PLAN IS THE |
| | LOCATION OF KATHLEEN?S OFFICE VERSES SHEET 03 THIS SAME |
| | AREA IS A 4 BED RECOVERY AREA. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 4C) SHEET 04 THE LIFE SAFETY SHEET DOES NOT DEFINE WHAT |
| | TYPE OF MEDICAL CARE UNIT THIS TENANT SPACE HOUSES. THE |
| | TERM PACU IS DEFINED AS AN AREA ADJOINING THE OPERATING |
| | ROOM TO WHICH PATIENTS WHO RECEIVES SEDATIVE, GENERAL |
| | AND REGIONAL ANESTHETICS ARE TAKEN FOR NURSING |
| | ASSESSMENT AND CARE WHILE RECOVERING FROM ANESTHESIA. |
| | CURRENTLY FOR THIS REVIEW THERE IS NOT ENOUGH |
| | INFORMATION PROVIDED TO KNOW IF THIS PLAN SHOULD BE |
| | REVIEWED UNDER THE 2014 FBC-B SECTION 422 AS AN |
| | AMBULATORY CARE FACILITY OR UNDER SECTION 469 AN OFFICE |
| | SURGERY SUITE? WITH THERE BEING 4 BEDS IN THE PACU AREA |
| | IT WOULD APPEAR THIS SUITE WILL NEED TO FALL UNDER |
| | AMBULATORY HEATH CARE OCCUPANCIES AS DESCRIBED IN NFPA |
| | 101, LIFE SAFETY CODES AND THIS CODE. |
| | 2014 FBC-B 469.3.1 OFFICE SURGERY SUITES THAT PROVIDE |
| | SERVICES OR TREATMENT, ON AN OUTPATIENT BASIS, TO FOUR |
| | OR MORE PATIENTS AT THE SAME TIME THAT EITHER RENDERS |
| | THE PATIENTS INCAPABLE OF TAKING ACTION FOR |
| | SELF-PRESERVATION UNDER EMERGENCY CONDITIONS WITHOUT |
| | THE ASSISTANCE FROM OTHERS OR THAT PROVIDE SURGICAL |
| | TREATMENT REQUIRING GENERAL ANESTHESIA TO FOUR OR MORE |
| | PATIENTS AT THE SAME TIME, SHALL MEET THE REQUIREMENTS |
| | OF AMBULATORY HEALTH CARE OCCUPANCIES AS DESCRIBED IN |
| | NFPA 101, LIFE SAFETY CODE AND THIS CODE. |
| | PLEASE NOTE THERE IS NOT SUFFICIENT INFORMATION TO BE |
| | ABLE TO COMPLETE THE REVIEW UNDER EITHER 422 A |
| | AMBULATORY CARE FACILITY NOR 469 OFFICE SURGERY SUITE. |
| | |
| | 5) THE PLANS SHEET 02 HAS A NOTE THAT ALL EXTERIOR |
| | WINDOWS AND DOORS ARE TO BE REMOVED, SHEET 07 ONLY |
| | SHOWS THE NORTH & EAST ELEVATIONS WHERE THE WINDOWS AND |
| | DOORS ARE BEING REPLACED, PLEASE PROVIDE THE OTHER |
| | ELEVATIONS AS WELL. PLEASE NOTE THERE ARE NO |
| | ARCHITECTURAL OR STRUCTURAL SHEETS PROVIDING THE WIND |
| | DESIGN CRITERIA AND PRESSURES FOR THE OPENINGS. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 5.2. RISK CATEGORY. |
| | |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) SHEET 08 SHOWS INSULATION LAYING DIRECTLY ON DROPPED |
| | CEILINGS. PLEASE BE AWARE INSULATION INSTALLED ON A |
| | SUSPENDED CEILING WITH REMOVABLE CEILING TILES SHALL |
| | NOT BE CONSIDERED PART OF THE MINIMUM THERMAL |
| | RESISTANCE OF THE ROOF INSULATION. 2014 FBC-ENERGY CODE |
| | C402.2.1. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |