| 2016-08-09 17:12:16 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 1383 10TH ST. |
| | JOB ADDRESS: 1383 10TH ST. |
| | DESCRIPTION: SERVICE CHANGE |
| | MASTER PERMIT: 16080355 |
| | |
| | 1. NEC 408.3: PANEL RATING OF 125 AMP IS NOT SUFFICIENT |
| | TO COMPLY WITH CODE REQUIREMENTS. |
| | 2. RISER DIAGRAM & PANEL DESCRIPTION AS SUBMITTED DO |
| | NOT MATCH. CORRECT ACCORDINGLY. |
| | 3. NEC 230.6: YOU SHALL PROVIDE A SITE/FLOOR PLAN SHOW |
| | THE LOCATION OF THE PANELS AND THE METER AND MAIN |
| | DISCONNECT IF ANY. |
| | 4. NEC 230.70: YOU ARE REQUIRED TO PROVIDE A DISCONNECT |
| | FOR THE SERVICE CONDUCTORS BEFORE THEY ENTER THE |
| | PREMISES; THE PANEL AS DESCRIBED IS A MLO. CORRECT |
| | ACCORDINGLY. |
| | 5. FBC-107.1: THE CITY OF WEST PALM BEACH AMENDMENTS TO |
| | THE FBC SECTION 107.2.1 REQUIRE THAT ALL SUBMITTED |
| | DRAWINGS FOR PERMIT APPROVAL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. THE |
| | PLANS FOR THE ABOVE MENTIONED JOB DO NOT HAVE THE NAME |
| | OR SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | 6. FBC-R314: YOU SHALL COME INTO COMPLIANCE WITH THE |
| | SMOKE DETECTOR REQUIRMENTS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |