Plan Review Details - Permit 16080350
Plan Review Stops For Permit 16080350
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-15 Cont ID  
Sent By vperez Date 2016-08-15 Time 10:11 Rev Time 0.00
Received By albarran Date 2016-08-15 Time 09:37 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-12 Cont ID  
Sent By pleduc Date 2016-08-12 Time   Rev Time 0.00
Received By pleduc Date 2016-08-11 Time 12:05 Sent To E
Notes
2016-08-11 12:06:42PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FIRE INSPECTOR SHALL VERIFY PROPER CODE COMPLIANT
 OPERATION OF EXIT DORRS AND STAIRWELL SIGNAGE.
  
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
  
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE THAN FOUR STORIES, UNLESS PERMITTED BY
 7.2.1.5.8.2, SHALL MEET ONE OF THE
 FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF THE BUILDING FIRE ALARM SYSTEM SHALL BE
 PROVIDED TO UNLOCK ALL STAIR ENCLOSURE DOOR ASSEMBLIES
 TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH 7.2.1.5.8.1.
  
  
 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL
 BE PERMITTED TO BE EQUIPPED WITH HARDWARE THAT PREVENTS
 RE-ENTRY INTO THE INTERIOR OF THE BUILDING, PROVIDED
 THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER
 EXIT.
 (2) THERE SHALL BE NOT MORE THAN FOUR STORIES
 INTERVENING BETWEEN STORIES WHERE IT IS POSSIBLE TO
 LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT.
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR
 NEXT-TO-TOP STORY SERVED BY THE STAIR ENCLOSURE, AND
 SUCH STORY SHALL ALLOW ACCESS TO ANOTHER EXIT.
 (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF.
 (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE
 PROVIDED WITH A SIGN ON THE STAIR SIDE INDICATING THE
 LOCATION OF THE NEAREST DOOR OPENING, IN EACH DIRECTION
 OF TRAVEL, THAT ALLOWS RE-ENTRY OR EXIT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-15 Cont ID  
Sent By albarran Date 2016-08-15 Time 10:14 Rev Time 0.00
Received By albarran Date 2016-08-09 Time 14:03 Sent To  
Notes
2016-08-15 10:16:078/15/16 APPROVED REVIEWS AND READY TO ISSUE. IN LIEU OF
 MISSING EMAIL, CONTRACTOR NOTIFIED VIA PHONE CALL. FILE
 SENT TO SMALL READY BIN "A". MA
2016-08-09 14:03:32REVISION ROUTED TO FIRE INBOX