Plan Review Details - Permit 16080345
Plan Review Stops For Permit 16080345
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2016-12-30 Cont ID  
Sent By spalmer Date 2016-12-30 Time 10:51 Rev Time 0.00
Received By spalmer Date 2016-12-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 09:34 Rev Time 0.00
Received By cthroop Date 2017-07-20 Time 07:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-04-24 Cont ID  
Sent By cthroop Date 2017-04-24 Time 11:09 Rev Time 0.00
Received By cthroop Date 2017-04-24 Time 10:16 Sent To  
Notes
2017-04-24 11:11:28BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT MAY BE REQUIRED. STATE PERCENTAGE OF
 EXISTING ROOF OR SQUARE FOOTAGE OF EXISTING ROOF
 REPAIRS.
 2. SEE PLAN PAGE A-4, CHANGE CODE REFERENCE FROM FBC
 2010 TO FBC 2014 5TH ED.
 3. PROVIDE WINDOW SCHEDULE.
 4. PROVIDE WINDOW AND DOOR PRODUCT APPROVALS.
 4A. IF NON-IMPACT DOORS OR WINDOWS ARE INSTALLED,
 PROVIDE SHUTTER SCHEDULE AND PRODUCT APPROVALS.
 5. SEE PLAN PAGE A-1, EXISTING BLDG. LEVEL III
 ALTERATION SECTION 401.4 DOES NOT EXIST. CHANGE CODE
 REFERENCE TO FBC2014 5TH ED. EXISTING BUILDING
 ALTERATION LEVEL III SECTION 505.1.
 6. PROVIDE DETAIL OF EXTERIOR WALL ASSEMBLY. SHOW
 TYPICAL FRAMING AT DOOR AND WINDOW OPENINGS, DRAINAGE
 PLANE AND FASTENER SCHEDULE FOR EXTERIOR SIDING.
 7. PROVIDE REPAIR DETAIL FOR ANY STRUCTURAL CONCRETE
 REPAIRS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-13 Cont ID  
Sent By cthroop Date 2017-01-13 Time 10:57 Rev Time 0.00
Received By cthroop Date 2017-01-13 Time 09:34 Sent To  
Notes
2017-01-13 11:02:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT IDENTIFY WHICH PERMIT APPLICATION APPLIES TO
 WHICH STRUCTURE.
 2. PROVIDE SITE PLAN WITH PROPERTY LINE SETBACKS AND
 DEMENSIONS BETWEEN STRUCTURES. INDICATE ADDRESS AND
 UNIT NUMBER ON EACH STRUCTURE.
 3. NO REVIEW PERFORMED AT THIS TIME.
  
 COMPLY WITH COMMENTS AND RE-SUBMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 10:34 Rev Time 0.00
Received By cthroop Date 2016-11-03 Time 15:46 Sent To Z
Notes
2016-11-04 10:43:05BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. SEPERATE PERMIT REQUIRED FOR EACH STRUCTURE.
 2. VALUE MAY BE PRORATED TO EACH STRUCTURE.
 3. PROVIDE SITE PLAN INDICATING REQUIRED SETBACKS.
 4. PROVIDE ENERGY SUBMITTAL FOR EACH STRUCTURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-04-17 Cont ID  
Sent By vperez Date 2017-04-17 Time 08:30 Rev Time 0.00
Received By vperez Date 2017-04-17 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 11:51 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 11:51 Sent To  
Notes
2017-01-25 11:52:052ND REVIEW-
  
 ORIGINAL COMMENTS 4 AND 5 ADDRESSED
  
 PENDING 1,2, 3,6,7 AND 8 PLEASE ADDRESS
 ZONING HAS DISSAPROVED MULTIPLE UNITS, PLEASE CLARIFY
 BEFORE RESUBMITTING
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-12 Cont ID  
Sent By albarran Date 2016-08-12 Time 09:12 Rev Time 0.00
Received By albarran Date 2016-08-11 Time 19:08 Sent To  
Notes
2016-08-12 09:12:45ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 801 BRADLEY
 JOB ADDRESS: 801 BRADLEY
 DESCRIPTION: REMODEL UNITS 1, 2 & 3 PER PLANS,
 INCLUDING ELECTRIC, & PLUMBING
 MASTER PERMIT: 16080345
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. YOU SHALL PROVIDE A SITE PLAN SHOWING THE PHYSICAL
 LOCATION OF EACH UNIT IN QUESTION WITH RELATION TO EACH
 OTHER.
 A. FBC-RE3601.2 (NEC 230.2) PERMITS A SINGLE SERVICE
 PER STRUCTURE AND THE ELECTRICAL PLANS AS SUBMITTED
 SHOW AN INDEPENDENT SERVICE FOR EACH UNIT. IF ANY OF
 THE UNITS IS ATTACHED TO THE OTHER, THE STRUCTURE CAN
 ONLY BE SERVED BY A SINGLE SERVICE.
 B. FBC-RE3601.7 (NEC 230.72) REQUIRES THAT ALL
 DISCONNECTS BE GROUPED.
 2. FBC-RE3609.3 (NEC 250.94) REQUIRES THAT YOU PROVIDE
 AN INTER-SYSTEM BONDING TERMINAL AT THE SERVICE. THE
 SERVICE RISERS PROVIDED ARE LACKING THIS.
 3. FBC-R 303.9 REQUIRES THAT YOU PROVIDE HEAT TO
 MAINTAIN 68 DEGREES IN ALL HABITABLE ROOMS WITHIN 3?
 FROM THE FLOOR. YOU INDICATE THAT YOU ARE PROVIDING
 FOUR WALL UNIT AIR CONDITIONERS IN EACH UNIT BUT FAIL
 TO INDICATE OF THE UNITS ARE REVERSE CYCLE AND IF THEY
 ARE THE INDIVIDUAL LOADS INDICATED ON THE PANEL
 SCHEDULE DO NOT REFLECT THAT.
 4. FBC-RE3901.7 (NEC 210.52(E)(3)) REQUIRES THAT THERE
 BE A GFCI PROTECTED OUTLET AT EVERY PORCH OR BALCONY.
 THE ELECTRICAL LAYOUT OF UNIT FAILS TO SHOW THIS.
 5. FBC-RE3903.4 (NEC 210.70(A)) REQUIRES THAT THERE BE
 A LIGHT CONTROLLED BY A WALL SWITCH IN THE LAUNDRY ROOM
 OF UNIT 3 AS WELL AS ON THE OUTSIDE OF THE LAUNDRY ROOM
 DOOR.
 6. THE MISSING SITE PLAN MAKES IT DIFFICULT TO
 DETERMINE THE USUAL POINT OF ENTRY FOR EACH UNIT. THE
 LIGHTING CONTROL SHALL BE AT THE USUAL POINT OF ENTRY.
 VERIFY LIGHTING CONTROL FOR UNIT 2.
 7. FBC-RE3703.3 (NEC 210.52(F)) REQUIRES THAT THERE BE
 A LAUNDRY ROOM CIRCUIT IN EVERY DWELLING UNIT. YOU FAIL
 TO SHOW THIS FOR UNIT 2.
 8. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2016-08-10 Cont ID  
Sent By wjolin Date 2016-08-10 Time 11:58 Rev Time 0.00
Received By wjolin Date 2016-08-10 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 09:34 Rev Time 0.00
Received By cthroop Date 2017-07-07 Time 13:58 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 17:04 Rev Time 0.00
Received By ccole Date 2017-03-29 Time 10:14 Sent To  
Notes
2017-03-31 10:14:44B28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 11:54 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 11:54 Sent To  
Notes
2016-12-30 11:37:30B28
 **TRAVELLING WITH 16120948 AND 16120953**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-29 Cont ID  
Sent By tklarge Date 2016-12-29 Time 10:55 Rev Time 0.00
Received By lmarchan Date 2016-08-09 Time 14:19 Sent To  
Notes
2016-08-09 14:19:37B35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 06:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-07-12 Cont ID  
Sent By cthroop Date 2017-07-20 Time 09:34 Rev Time 0.00
Received By ccole Date 2017-07-12 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-05-04 Cont ID  
Sent By ccole Date 2017-05-04 Time 17:05 Rev Time 0.00
Received By ccole Date 2017-05-04 Time 17:05 Sent To  
Notes
2017-05-04 17:06:124TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16080345
 5/4/17
  
 1) THE ENERGYGAUGE FORM R405-2014 IS INDICATING A NEW
 17.5 SEER AC SYSTEM, HOWEVER IT IS LISTED AS 16 SEER ON
 THE PLAN- PLEASE CORRECT.
  
 2) PROVIDE A MAIN RETURN GRILL FOR THE AIR HANDLER IN
 THE CLOSET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-05 Cont ID  
Sent By ccole Date 2017-01-05 Time 07:18 Rev Time 0.00
Received By ccole Date 2017-01-04 Time 16:56 Sent To  
Notes
2017-01-05 07:53:142ND REVIEW FBC-2014 RESIDIENTIAL MECHANICAL
 PERMIT #16080345
 1/5/17
  
 1) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS
 INDICATING MAKES, MODELS, COOLING AND HEATING
 CAPACITIES, AND EFFICIENCY RATINGS. THE SUBMIITTED AC
 AND ENERGY CALCULATIONS CANNOT BE REVIEWED IN ENTIRETY
 WITHOUT SYSTEMS' INFORMATION. PLEASE NOTE THAT THE
 SYSTEM IS LISTED AS "GENERIC" UNDER THE EQUIPMENT
 SUMMARY ON THE AC CALCULATIONS.
  
 2) THE COOLING AND HEATING SYSTEM COMPLIANCE DATA ON
 THE SUBMITTED ENERGYGAUGE FORM R405-2014 DOES NOT MATCH
 THE PLANS: A) THE THROUGH THE WALL SYSTEMS SHOWN ON THE
 PLAN ARE LISTED AS ONE "CENTRAL UNIT" ON THE FORM. B)
 THE REVERSE CYCLE HEATING SYSTEMS SHOWN ON THE PLAN ARE
 LISTED AS HEAT STRIPS ON THE FORM.
  
 3) THE ENERGYGAUGE FORM MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 4) THE PLANS MUST BE REVISED TO SHOW THE INSULATION
 R-VALUES IN THE WALLS AND CEILING IN ORDER TO VERIFY
 THE VALUES LISTED ON THE ENERGY FORM R405-2014 ARE
 ACCURATE.
  
 5) THE ENERGY FORM R405 IS LISTING EITHER NEW OR
 EXISTING DOUBLE-PANED WINDOWS AT 0.29 U-FACTOR/0.23
 SHGC. PLEASE PROVIDE A WINDOW SCHEDULE ON THE PLAN AND
 SUBMIT MANUFACTURER'S DATA SHEET FOR REVIEW.
  
 6) PROVIDE A DRYER VENTING PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 14:50 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 14:48 Sent To  
Notes
2016-08-15 14:52:041ST REVIEW FBC-2014 RESIDENTIAL, ENERGY CONSERVATION
 CODES
 PERMIT #16080345
 8/15/16
  
 1) PROVIDE MECHANICAL PLANS AND SPECIFICATIONS
 INCLUDING A SCOPE OF WORK FOR THE PROPOSED ALTERATION,
 AC EQUIPMENT SCHEDULES, AND AC SIZING CALCULATIONS PER
 SECTION R403.6.1 FBC-14 ENERGY CONSERVATION.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY CONSERVATION
 AND SUBMIT ENERGY CALCULATIONS. SEE SECTION R401.2 FOR
 COMPLIANCE PATH OPTIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By gjohnson Date 2017-07-21 Time 10:50 Rev Time 0.00
Received By gjohnson Date 2017-07-21 Time 10:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-04-20 Cont ID  
Sent By gjohnson Date 2017-04-20 Time 09:04 Rev Time 0.00
Received By gjohnson Date 2017-04-20 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-23 Cont ID  
Sent By gjohnson Date 2017-01-23 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2017-01-23 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-29 Cont ID  
Sent By tklarge Date 2016-08-29 Time 09:04 Rev Time 0.00
Received By tklarge Date 2016-08-29 Time 06:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-07-20 Cont ID  
Sent By cthroop Date 2017-07-20 Time 09:16 Rev Time 0.00
Received By cthroop Date 2017-07-20 Time 09:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2017-04-18 Cont ID  
Sent By njwira Date 2017-04-18 Time 16:16 Rev Time 0.00
Received By njwira Date 2017-04-18 Time 16:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2017-04-18 Cont ID  
Sent By njwira Date 2017-04-18 Time 16:16 Rev Time 0.00
Received By njwira Date 2017-04-18 Time 16:16 Sent To  
Notes
2017-03-20 08:22:10PASS IT

Review Stop Z ZONING
Rev No 3 Status F Date 2017-01-17 Cont ID  
Sent By njwira Date 2017-01-17 Time 14:55 Rev Time 0.00
Received By njwira Date 2017-01-17 Time 14:55 Sent To  
Notes
2017-01-27 09:27:43162-74 GREEN CARD 3 UNITS PERMITTED PLEASE RETURN
2017-01-17 14:56:301/17/17- FAILED
  
 ONLY ONE UNIT PERMITTED ON THE SITE.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By njwira Date 2017-01-03 Time 16:57 Rev Time 0.00
Received By njwira Date 2017-01-03 Time 15:54 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By njwira Date 2016-11-09 Time 11:30 Rev Time 0.00
Received By njwira Date 2016-11-04 Time 15:54 Sent To AD
Notes
2016-11-09 11:32:5711/9/16- FAILED
  
 SF-7 NON-HISTORIC
  
 MISSING SURVEY SHOWING SETBACKS
 PROPOSED TWO(2) UNITS AND IS ONLY ALLOWED ONE(1)UNIT ON
 THE PROPERTY
 DID NOT PROVIDE ELEVATION DRAWINGS
 TREES MAY NOT BE MOVED WITHOUT A TREE ALTERATION PERMIT
 WHERE IS THE ELECTRICAL EQUIPMENT GOING?
 WHAT IS THE ROOF PROJECTIONS.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  