Plan Review Details - Permit 16080322
Plan Review Stops For Permit 16080322
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 16:31 Rev Time 0.00
Received By albarran Date 2016-10-25 Time 16:00 Sent To I
Notes
2016-10-25 16:33:52CONDITIONAL APPROVAL DEPENDENT ON HAVING THE REQUIRED
 LIGHT & OUTLET FOR THE HVAC EQUIPMENT INSIDE THE ATTIC.
 OTHER THAN THAT ALL PREVIOUSLY MENTIONED DEFICIENCIES
 HAVE BEEN SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-04 Cont ID  
Sent By albarran Date 2016-10-04 Time 07:55 Rev Time 0.00
Received By albarran Date 2016-10-03 Time 17:53 Sent To I
Notes
2016-10-04 07:58:082ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: SACCO RESIDENCE
 JOB ADDRESS: 836 ARDMORE ROAD
 DESCRIPTION: PARTIAL REWIRE OF HOUSE.
 MASTER PERMIT: 1608032
  
 BELOW PLEASE FIND A LIST OF ADDITIONAL CORRECTIONS TO
 THE PLANS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE DRAWN
 TO A MINIMUM OF 1/8" SCALE. PLEASE INDICATE THE SCALE
 TO WHICH THESE DRAWING WERE CREATED.
 2. THE WORD ROMEX AS USED IN THIS NOTE IS TO IDENTIFY A
 TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE OF
 CABLE, REFER TO CABLE TYPES NM, NMC OR NMS.
 3. YOU WERE ASKED ONCE BEFORE TO INCLUDE/DESCRIBE YOUR
 SCOPE OF WORK ON THE PLANS. THIS IS A REQUIREMENT OF
 THE CODE AS WELL AS A TOOL FOR THE FIELD INSPECTOR TO
 SEE WHAT HAS BEEN APPROVED.
 4. FBC-RE3406.5: ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 AND PANELBOARDS. THIS LIGHT SHALL NOT BE CONTROLLED BY
 AUTOMATIC MEANS ONLY. THE REMOTE CONTROL LIGHT OF THE
 GARAGE DOOR OPENER DOES NOT MEET THESE REQUIREMENTS.
 5. FBC-RE3901.4.2: A GFI OUTLET IS MISSING ON THE
 KITCHEN COUNTER ADJACENT TO REFRIGERATOR.
 6. FBC-RE3901.10: WITHOUT KNOWING THE SCALE OF THE
 DRAWINGS IT IS IMPOSSIBLE TO PROPERLY ASCERTAIN
 RECEPTACLE PLACEMENT REQUIREMENTS, BUT IF THE CORRIDOR
 TO THE BEDROOMS IS 10' OR GREATER, AN OUTLET IS
 REQUIRED IN THE HALLWAY.
 7. FBC-RE3903.3: A LIGHTING OUTLET SHALL BE INSTALLED
 ON THE EXTERIOR OF THE LAUNDRY ROOM AND THE GARAGE
 DOOR.
 8. FBC-R315: YOU SHALL INSTALL CARBON MONOXIDE
 DETECTION WITHIN 10 FT. OF THE BEDROOM DOORS. THIS
 APPLIES TO THE DEVICE IN THE HALLWAY, IT SHALL BE A
 COMBINATION UNIT CAPABLE OF DETECTING BOTH, HIGH LEVELS
 OF SMOKE AND CARBON MONOXIDE.
 9. IN THE INTEREST OF LIFE SAFETY, OWNER CONVENIENCE
 AND ENERGY CONSERVATION, PLEASE LET ME SUGGEST THAT YOU
 INSTALL ADDITIONAL LIGHTING CONTROLS FOR THE DINING
 ROOM AND THE EXISTING ENTRY PORCH LEADING INTO THE
 GARAGE ENTRANCE. SEE MARK ON PLANS OR CALL ME FOR
 FURTHER DETAILS.
 10. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS
 11. YOU SHALL SHOW THE LOCATION OF ALL HVAC EQUIPMENT
 AND ALL ASSOCIATED EQUIPMENT ON THE PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By albarran Date 2016-08-11 Time 13:52 Rev Time 0.00
Received By albarran Date 2016-08-11 Time 13:13 Sent To  
Notes
2016-08-11 13:53:18ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: SACCO RESIDENCE
 JOB ADDRESS: 836 ARDMORE RD.
 DESCRIPTION: PARTIAL REWIRE OF HOUSE; INSTALL ARC-FAULT
 MASTER PERMIT: 16080322
 REVISION:
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. FBC-R 107.2.1: THE SCOPE IS TOO VAGUE TO ACCEPT. YOU
 HAVE TO BE MORE SPECIFIC WITH THE SCOPE OF WORK.
 2. FBC-B 109.3: YOU NEED TO PROVIDE A COPY OF THE
 ACCEPTED CONTRACT.
 3. FBC-R 107.2.1: YOU SHALL INCLUDE ON THE PLANS THE
 NAME AND ADDRESS OF THE JOB LOCATION.
 4. FBC-R 3701.2: YOU SHALL PROVIDE A FEEDER SCHEDULE
 (RISER DIAGRAM) SHOWING THE LOCATION OF BOTH PANEL AND
 THEIR RESPECTIVE DISCONNECTS.
 5. FBC-R 3604: YOU SHALL SUBMIT A SITE DIAGRAM
 INDICATING THE LOCATION OF THE METER AND DISCONNECTS ON
 THE PREMISES.
 6. ON THE PLANS MARK WHAT IS NEW AND WHAT IS EXISTING
 TO REMAIN.
 7. FBC-R 3902.11/.12: ALL NEW WORK SHALL COMPLY WITH
 THE GFCI & ARC-FAULT REQUIREMENTS.
 8. FBC-R3706.2: YOU SHALL PROVIDE A PANEL SCHEDULE OR
 CIRCUIT DIRECTORY LEGIBLY INDICATING THE SPECIFIC
 PURPOSE OF EVERY CIRCUIT.
 9. FBC-R4002.14: ALL NEW RECEPTACLES IN ALL AREAS
 SPECIFIED IN 210.52, ALL 125-VOLT, 15 AND 20 AMPERE
 RECEPTACLES SHALL BE LISTED TAMPER RESISTANT
 RECEPTACLES.
 10. FBC-R 314/315: YOU SHALL COME INTO COMPLIANCE
 W/SMOKE DETECTOR REQUIREMENTS AS FOR NEW CONSTRUCTION.
 IF THERE ARE ANY FOSSIL FUEL (GAS) BURNING APPLIANCES
 ON SITE YOU SHALL ABIDE BY THE CARBON MONOXIDE
 REQUIREMENT AS WELL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 16:41 Rev Time 0.00
Received By albarran Date 2016-10-21 Time 12:48 Sent To  
Notes
2016-10-25 16:42:5810/25/16 CONDITIONAL ELECTRICAL APPROVAL AS NOTED.
 CONTRACTOR NOTIFIED VIA EMAIL. FILES SENT TO SMALL
 READY BIN M. MA
2016-10-24 12:49:03RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-04 Cont ID  
Sent By albarran Date 2016-10-04 Time 08:12 Rev Time 0.00
Received By albarran Date 2016-09-30 Time 14:49 Sent To  
Notes
2016-10-04 08:38:4810/4/16 FAILED SECOND ELECTRICAL REVIEW AS NOTED. MR
 SPARKEY NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED M
 DRAWER. MA
2016-09-30 14:49:46RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-11 Cont ID  
Sent By albarran Date 2016-08-11 Time 13:58 Rev Time 0.00
Received By albarran Date 2016-08-08 Time 09:45 Sent To  
Notes
2016-08-11 13:55:458/11/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED DRAWER
 "M". MA
2016-08-09 09:46:45ELECTRICAL INBOX