Plan Review Details - Permit 16080296
Plan Review Stops For Permit 16080296
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 09:34 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-10-26 Cont ID  
Sent By albarran Date 2016-10-26 Time 17:26 Rev Time 0.00
Received By albarran Date 2016-10-26 Time 15:36 Sent To  
Notes
2016-10-26 17:40:09THIS FILE WAS INADVERTENTLY PLACED ON MY DESK FOR
 REVIEW. I OPENED THE PACKET AND NOTICED THAT NOTHING
 HAS BEEN DONE ABOUT ADDRESSING THE COMMENTS. WHAT I DID
 NOTICE IS THAT THERE IS ONLY ONE COMPLETE SPEC PACKET.
 THERE HAS TO BE A MINIMUM OF TWO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-12 Cont ID  
Sent By albarran Date 2016-10-12 Time 09:00 Rev Time 0.00
Received By albarran Date 2016-10-11 Time 19:19 Sent To FIRE
Notes
2016-10-12 09:01:042ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, 2010 NFPA 72 & NFPA 70 2011 (NEC)
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 MR. PICKERING, I HAVE GONE OVER YOUR RESUBMITTAL AND
 AGREE WITH ALL YOUR RESPONSES EXCEPT NUMBER 8. IN MY
 INITIAL REVIEW I ASKED THAT THE PULL STATION BE
 RELOCATED OR THAT YOU ADD A PULL STATION TO COMPLY WITH
 THE REQUIREMENTS OF NFPA 72, SECTION 17.14.6 WHICH
 CLEARLY STATES THAT THERE SHALL BE A MANUAL PULL
 STATION WITHIN 5? OF EVERY EXIT. THIS IS SO CRUCIAL TO
 THE INTENT OF LIFE SAFETY THAT IN THE FOLLOWING
 SECTION, NFPA 72, SECTION 17.14.7 LARGER OPENINGS ARE
 REQUIRED TO HAVE A DEVICE AT BOTH ENDS AND ALSO WITHIN
 5? OF THE OPENING.
 PLEASE NOTE THAT IT IS OUR POLICY TO HAVE ALL FIRE
 ALARM WORK PERFORMED UNDER A PERMIT OF ITS OWN AND NOT
 AS A PART OF THE ELECTRICAL PERMIT SUB-PERMIT. I
 RESEARCHED THE DETAILS OF YOUR RESPONSE AND FOUND THAT
 THE INITIAL BUILDING PERMIT FOR THESE PREMISES WAS
 APPLIED FOR IN 2008 UNDER PERMIT NUMBER 08500795 WHICH
 WAS FOR SOME REASON REVOKED AND LATER IN 2010 RE-ISSUED
 AS PERMIT NUMBER 10010548. IT WAS NOT UNTIL 2013 THAT
 AN ELECTRICAL SUB PERMIT WAS ISSUED (13120581). I FAIL
 TO FIND A FIRE ALARM PERMIT.
 IN SUMMATION, I AM NOT IN A POSITION TO ALLOW YOU TO
 CIRCUMVENT THE CODE. MY POSITION IS ONLY TO MAKE
 CERTAIN THAT THE CODE IS FOLLOWED. FURTHERMORE, A PRIOR
 REVIEW APPROVED OR OTHERWISE, HAD THERE BEEN ONE IS NOT
 AN APPROVAL OR AUTHORIZATION TO VIOLATE OR CIRCUMVENT
 THE CODE.
 IN THIS CASE, WITHOUT ATTEMPTING TO DESIGN OR REDESIGN
 THE SYSTEM, YOU HAVE A CHOICE OF EITHER TO RELOCATE THE
 EXISTING STATION TO A POINT MIDWAY BETWEEN BOTH EXITS
 OR SIMPLY ADD A DEVICE TO ASCERTAIN COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By albarran Date 2016-08-17 Time 15:30 Rev Time 0.00
Received By albarran Date 2016-08-16 Time 17:55 Sent To I
Notes
2016-09-13 18:47:049/13/16 RESPONDED TO CHRIS' EMAIL ADDRESSING MY PLAN
 REVIEW NOTES. SEE EMAIL IN SENT FOLDER DATED 9/13/16 TO
 CHRIS.
2016-08-17 15:31:29ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: UB KINSEY EDUCATIONAL & COMMUNITY CENTER
 JOB ADDRESS: 720 8TH STREET
 DESCRIPTION: LOW VOLTAGE FIRE ALARM INSTLLATION
 MASTER PERMIT: 10010548
 SUB PERMIT: 16080296
  
 THE SYSTEM AS DESIGNED DOES NOT COMPLY WITH THE
 OCCUPANCY CLASSIFICATION OF THE PROTECTED PREMISES.
 YOUR PLANS INCORRECTLY DETERMINED THAT THE OCCUPANCY IS
 BUSINESS, WHEN IN-FACT IT IS EDUCATIONAL. SEE FBC-B
 SECTION 453, FBC-B 907.2.3, AND THE APPROVED MASTER
 PERMIT LIFE SAFETY PLANS. CHECK THE SYSTEM DESIGN AND
 CORRECT ACCORDINGLY. NEVER THE LESS, BELOW PLEASE FIND
 A LIST OF REQUIRED CORRECTIONS REQUIRED WITH THE PLANS
 AS SUBMITTED. ADDITIONAL CORRECTIONS MAY BE REQUIRED
 AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PER SECTION FBC-B 453.7.6 THE F/A SHALL SHUT OFF GAS
 AND FUEL OIL SUPPLIES WHICH SERVE STUDENT OCCUPIED
 SPACES OR PASS THROUGH SUCH SPACES. THIS MAY BE
 APPLICABLE TO LAB CLASSROOMS IF ANY.
 2. PER SECTION FBC-B 453.7.6.1 KITCHEN FUEL GAS SHALL
 BE SHUT OFF BY ACTIVATION OF HOOD SYSTEM.
 3. THE PLANS SHALL BE MARKED WITH THE ACTUAL CODE TO
 WHICH THE SYSTEM IS BEING DESIGNED.
 4. THE FCPS SPEC SHEET PROVIDED IS FOR THE 6 AMP MODEL,
 YET YOUR BATTERY CALCULATIONS CHART ADDRESSES BOTH THE
 6 & THE 8 AMP MODEL. INDICATE WHICH MODEL WILL BE USED.
 5. YOU PROVIDED SPEC SHEETS FOR ALL BUT THE BATTERIES;
 EACH APPARATUS REQUIRES A DIFFERENT BATTERY. IDENTIFY
 WHAT BATTERY WILL BE IN EACH.
 6. CORRECT THE MATH FOR THE WATT LOSS CALCULATIONS.
 7. ADD A BLOCK NOTE ADDRESSING THE NFPA 70 SECTION
 760.41(B) OR 760.121(B) & NFPA 72 SECTION 10.5.5.2 ?
 10.5.5.3.
 8. RELOCATE MANUAL PULL STATION IN THE LOBBY TO COMPLY
 WITH NFPA SECTION 17.14.6.
 9. PER THE APPROVED LIFE SAFETY PLAN SHEET LS1, THERE
 IS AN EXIT OUT OF STAIRWAY 2 THAT IS MISSING FROM THE
 DRAWING. CORRECT ACCORDINGLY AND INCLUDE REQUIRED
 DEVICE.
 10. IF GAZEBO IS LESS THAN 10? FROM THE BLDG.
 STRUCTURE, AN INITIATION DEVICE SHALL BE REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-20 Cont ID  
Sent By albarran Date 2016-10-26 Time 17:49 Rev Time 0.00
Received By   Date 2016-10-18 Time   Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-16 Cont ID  
Sent By J.Walker Date 2016-08-16 Time   Rev Time 0.25
Received By   Date 2016-08-15 Time   Sent To E
Notes
2016-08-15 17:23:26WILL REQUIRE 24 HOUR BATTERY TEST AT TIME OF
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 09:35 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-26 Cont ID  
Sent By albarran Date 2016-10-26 Time 17:47 Rev Time 0.00
Received By albarran Date 2016-09-19 Time 15:30 Sent To  
Notes
2016-10-26 17:49:0810/26/16 THIS FILE CONTINUES TO FAIL THE ELECTRICAL
 REVIEW. NOTHING WAS DONE TO CORRECT THE ISSUE AT HAND.
 FILE SENT TO SMALL DENIED DRAWER C. MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-17 Cont ID  
Sent By albarran Date 2016-08-17 Time 15:35 Rev Time 0.00
Received By albarran Date 2016-08-08 Time 15:22 Sent To  
Notes
2016-08-17 16:23:258/17/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "C".
 MA
2016-08-08 15:23:06ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy