Plan Review Details - Permit 16080277
Plan Review Stops For Permit 16080277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-19 Cont ID  
Sent By jwitmer Date 2016-09-19 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2016-09-19 Time 11:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 08:59 Sent To  
Notes
2016-08-13 09:53:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080277
 ADD: 1555 PALM BEACH LAKES BLVD. SUITE # 1105
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 1) SHEET A.1 LIST THE SQUARE FOOTAGE OF THE TENANT
 SPACE AS 4557 SQ. FT. THERE ARE (2) AREAS OF CONCERN
 THAT CREATE AN ASSEMBLY OCCUPANCY. THE DINING/ BREAK
 ROOM AREA AN A2 (310 SQ. FT./ OCC. LOAD OF 21) AND THE
 CONFERENCE ROOM (392 SQ. FT./ OCC. LOAD OF27) WHERE THE
 OCCUPANCY TYPE WOULD BE AN A3. TO BE CONSIDERED A MIXED
 USE OCCUPANCY THE ACCESSORY OCCUPANCIES ARE THOSE
 OCCUPANCIES THAT ARE ANCILLARY TO THE MAIN OCCUPANCY.
 UNDER SECTION 508.2.1(AREA LIMITATION) OF THE 2014
 FBC-B. THE AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT
 OCCUPY MORE THAN 10 % OF THE BUILDING AREA OR STORY IN
 WHICH THEY ARE LOCATED. UNDER THE 2012 IBC-B THE BASE
 CODE AREA LIMITATION 509.3 IT STATES WHERE THERE ARE
 TWO OR MORE TENANTS LOCATED ON THE SAME STORY, THE 1O %
 LIMITATION IS PRESUMABLY BASED ON THE FLOOR AREA OF
 EACH INDIVIDUAL TENANT SPACE RATHER THAN ON THAT OF THE
 ENTIRE STORY. THIS CREATES A MIXED OCCUPANCY. THE
 DESIGNER OF RECORD WILL NEED TO DECLARE THE DESIGN
 PARAMETERS AS EITHER IN COMPLIANCE WITH;
 2014 FBC-B 508.3 NONSEPARATED USE.
 OR
 2014 FBC-B 508.3.3 SEPARATED USE.
  
 2) SHEET A1. PLEASE ALSO NOTE BECAUSE OF THE MIXED USE
 OCCUPANCY AND THE END USE OF THE CONFERENCE ROOM (27
 OCCUPANTS)AND THE BREAKROOM/ DINING ROOM AREAS (21
 OCCUPANTS.) FIGURED AT THE HIGHER 15 SQ. FT./ OCCUPANT
 THE TOTAL OCCUPANT LOAD FOR THE SPACE IS 3855 SQ.
 FT./100= 39+21+27= 87 OCCUPANTS. WITH OCCUPANT LOADS OF
 50 OR MORE THE EGRESS DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL SEE 2014 FBC-B 1008.1.2 DOOR
 SWING FOR DOORS NUMBERED 1 & 5.
  
 3) PLEASE NOTE THE SHEET A1 THE KEY PLAN IN THE
 CONFERENCE ROOM SHOWS A RECEPTION DESK BUT THE PLANS DO
 NOT PROVIDE ANY DETAILS ON THIS DESK. PLEASE PROVIDE
 DETAILS THAT WILL SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESS. CODE SECTIONS:
 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
  
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
  
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By vperez Date 2016-09-13 Time 11:59 Rev Time 0.00
Received By vperez Date 2016-09-13 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-24 Cont ID  
Sent By vperez Date 2016-08-24 Time 07:50 Rev Time 0.00
Received By vperez Date 2016-08-24 Time 07:50 Sent To  
Notes
2016-08-24 07:51:39PROVISO- INDICATE LOW VOLTAGE PERMIT TO BE UNDER
 SEPERATE PERMIT, PROVIDE 2ND SET TO STAMP ELECTRICAL
 APPROVAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-09 Cont ID  
Sent By wjolin Date 2016-09-09 Time 12:28 Rev Time 0.00
Received By wjolin Date 2016-09-09 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By wjolin Date 2016-08-10 Time 13:03 Rev Time 0.00
Received By wjolin Date 2016-08-10 Time 12:34 Sent To  
Notes
2016-08-10 13:03:311555 PALM BEACH LAKES BOULEVARD - SUITE #1105
 PERMIT #16080277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE AN OCCUPANT LOAD OF 46 PERSONS FOR THE
 SPACE; HOWEVER, THE CONFERENCE ROOM WILL ADD
 APPROXIMATELY 25 PERSONS WHEN USING AN OCCUPANT LOAD
 FACTOR OF 15 SQ.FT. PER PERSON. THIS OCCUPANT LOAD
 ADJUSTMENT WILL REQUIRE THE EXIT ACCESS DOORS (#1 AND
 #5) TO SWING IN THE OPPOSITE DIRECTION. PER NFPA 101
 SECTION 7.2.1.4.2, DOORS ARE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2016-09-07 Time 13:12 Sent To  
Notes
2016-09-07 13:12:42B24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-25 Cont ID  
Sent By gjohnson Date 2016-08-25 Time 15:08 Rev Time 0.00
Received By gjohnson Date 2016-08-05 Time 12:33 Sent To  
Notes
2016-08-08 12:34:05B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 14:50 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 08:14 Rev Time 0.00
Received By ccole Date 2016-08-16 Time 08:14 Sent To  
Notes
2016-08-16 08:16:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080277
 8/16/16
  
 1) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC-
 PLANS SHALL BE SUBMITTED IN TWO OR MORE SETS. ONLY ONE
 SET OF PLANS WAS SUBMITTED FOR REVIEW.
  
 2) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE
 FBC- THE MECHANICAL PLANS SHALL BE DESIGNED BY A FL.
 LICENSED ENGINEER OR THE THE INSTALLING AC CONTRACTOR.
  
 3) SHEET M-2: INDICATE HOW AIR IS BEING RETURNED FROM
 OFFICE #5, AND RECEPTION ROOM 100- SECTION 601.5.
  
 4) M-2: THE 24X12 (288 SQ, INCHES) RETURN AIR GRILL IN
 THE CONFERENCE ROOM IS UNDERSIZED FOR 760 CFMS.
 TYPICALLY RETURN GRILLS ARE SIZED CFM/2 ( 1 SQ. IN. OF
 GRILL AREA PER 2CFMS OF AIR). 760 CFMS REQUIRES 380 SQ.
 IN. OF RETURN.
  
 5) M-2: INDICATE THE SIZE OF THE EXISTING DUCT
 SUPPLYING OFFICE #5 AND CONFERENCE 101.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 14:07 Rev Time 0.00
Received By gjohnson Date 2016-09-28 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By gjohnson Date 2016-08-25 Time 14:40 Rev Time 0.00
Received By gjohnson Date 2016-08-25 Time 14:40 Sent To  
Notes
2016-08-25 15:07:491ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER AND SANITARY RISER. PER WPB
 AMEND TO FBC 107.3.5.1.3(11)
  
 2. PROVIDE TWO SETS OF PLANS WHEN RESUBBITING. PER WPB
 AMEND TO FBC 107.1
  
  


Account Summary | Usage Policy | Privacy Policy