Plan Review Details - Permit 16080252
Plan Review Stops For Permit 16080252
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-23 Cont ID  
Sent By tklarge Date 2016-09-23 Time 10:18 Rev Time 0.00
Received By tklarge Date 2016-09-23 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-08 Cont ID  
Sent By tklarge Date 2016-08-08 Time 11:10 Rev Time 0.00
Received By tklarge Date 2016-08-08 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-23 Cont ID  
Sent By tklarge Date 2016-09-23 Time 10:18 Rev Time 0.00
Received By tklarge Date 2016-09-23 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By tklarge Date 2016-08-08 Time 11:10 Rev Time 0.00
Received By tklarge Date 2016-08-08 Time 11:04 Sent To  
Notes
2016-08-08 11:09:241) ) ALL BACKFLOW DEVICES MUST BE LEAD FREE.THE
 SUBMITTED DOCUMENTS DO NOT SHOW THE DEVICE IS LEAD
 FREE.
 2) IS THIS DEVICE TO BE USED AS AN ISOLATION
 INSTALLATION (OTHER LOCATION THAN AT WATER METER) OR IS
 TO BE USED AS A CONTAINMENT INSTALLATION (LOCATED AT
 WATER METER)? PLEASE NOTE SUCH ON THE APPLICATION.
 3) INDICATE THE SIZE OF THE DEVICE ON THE
 SPECIFICATIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  