| 2016-09-07 11:56:09 | BUILDING PLAN REVIEW |
| | NORTON MUSEUM |
| | W. P. B. PERMIT: 16080215 FOUNDATION & STRUCTURAL |
| | PERMIT |
| | W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| | ADD: 1451 S. OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052 |
| | E-MAIL: [email protected] MICHAEL IZZO |
| | E-MAIL: [email protected] MICHAEL J BEAUMIER |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES-WED. SEPT. 6-7TH / 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A ARCHITECTURAL SHEET OR LIFE SAFETY |
| | SHEET THAT PROVIDES THE CODE ANALYSIS OF THE BUILDING. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5. MINIMUM PLAN REVIEW CRITERIA |
| | 107.3.5.1. COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | OCCUPANCY TYPES AND SQUARE FOOTAGE OF BUILDING PER |
| | FLOOR. |
| | TYPE OF CONSTRUCTION |
| | AREA INCREASES TAKEN FOR FRONTAGE AND FIRE SPRINKLERS |
| | FIRE RESISTANCE RATING OF STRUCTURAL MEMBERS |
| | LIFE SAFETY FLOOR PLAN / OCCUPANT LOADS |
| | |
| | 2) PLEASE PROVIDE AN UPDATED INDEX OF THE STRUCTURAL |
| | PAGES NOT FOUND ON THE ORIGINAL BUILDING PERMIT |
| | (16050912). 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) PLEASE BE AWARE THIS SCOPE OF WORK REQUIRES A |
| | THRESHOLD INSPECTOR, SEE F.S. THRESHOLD BUILDING FL S. |
| | S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 3A)SEMI-COMPLIED. THE WRITTEN INSPECTION PLAN IS |
| | WRITTEN BY THE ENGINEER OF RECORD. THE SUBMITTED PLAN |
| | DID NOT HAVE A DIGITAL SIGNATURE. THIS DOCUMENT IS ALSO |
| | MULTIPLE PAGES AND WOULD NEED TO IDENTIFY HOW MANY |
| | PAGES ARE WITHIN THE DOCUMENT. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| | |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) COMPLIED. THRESHOLD INSPECTOR FORMS: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 3D) COMPLIED. FOR THE SPECIAL INSPECTOR PROVIDED A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 3F) NOTICE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 3G)NOTICE: PLEASE CALL THE CITY OF WEST PALM BEACHS |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3H) NOTICE. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 4) SHEET 0277_S003 HEADING FOUNDATIONS INDICATES THERE |
| | WAS A GEOTECHNICAL REPORT COMPLETED BY ARDAMAN |
| | 12/16/2014. THE SUBMITTED REPORT DOES NOT HAVE AN |
| | ELECTRONIC SIGNATURE AND SEAL. NOTE WHEN SUBMITTED |
| | ELECTRONICALLY THE SOILS ENGINEER WILL NEED TO SUBMIT |
| | UNDER AN ELECTRONIC SEAL PER 61G15-23.005 PROCEDURES |
| | FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | (ELECTRONIC SEALS). |
| | OTHERWISE ONE PAPER ORIGINAL SIGNED AND SEALED DOCUMENT |
| | WILL BE RETAINED AND SCANNED INTO THE SYSTEM. |
| | |
| | 5A) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT |
| | (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING. |
| | THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND |
| | TUNNEL TEST THAT WERE COMPLETED. THE WIND TUNNEL TEST |
| | IS AN EXCEPTION TO SECTION 1609.1.1 WHEN THE TEST WAS |
| | IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7. THIS REVIEW NO |
| | SUCH DOCUMENTS WERE SUBMITTED ELECTRONICALLY (SHEET |
| | 0284_S010 WIND STUDY REPORT FROM WIND DESK-TOP STUDY |
| | REPORT FROM EWDI 12/17/2015). A SIGNED AND SEALED PAPER |
| | ORIGINAL CAN BE SUBMITTED ON THE NEXT REVIEW. THE CITY |
| | WILL THEN SCAN IN THE DOCUMENT FOR RECORD RETENTION. |
| | |
| | 5B) COMMENT # 17 FROM THE ORIGINAL BUILDING PERMIT |
| | (16050912) DEALT WITH WIND PRESSURES FOR THE BUILDING. |
| | THE RESPONSE INDICATES THERE WERE SITE SPECIFIC WIND |
| | TUNNEL TEST THAT WERE COMPLETED. SHEETS S008, S009,& |
| | S010 ALL PROVIDE THE POSITIVE AND NEGATIVE PRESSURES |
| | FOR ALL OPENINGS BUT THE PRESSURES CA NOT BE VALIDATED |
| | SINCE THE WIND STUDY REPORT FROM WIND DESK-TOP STUDY |
| | REPORT FROM EWDI 12/17/2015 HAS NOT BEEN SUBMITTED FOR |
| | REVIEW. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE WIND |
| | TUNNEL TEST IS AN EXCEPTION TO SECTION 1609.1.1 WHEN |
| | THE TEST WAS IN ACCORDANCE WITH CHAPTER 31 OF ASCE 7. |
| | |
| | 5C) UNDER THE STRUCTURE ONLY PERMIT THE PRESSURES ARE |
| | GIVEN FOR THE EXTERIOR OPENINGS BUR THERE ARE NEITHER |
| | SIZES WIDTH AND HEIGHT OF THE WINDOWS, DOORS, ROOF |
| | OPENINGS FOR MECHANICAL EQUIPMENT NOR SKYLIGHTS |
| | OPENINGS IN THE ROOF. HEADER AND SILL HEIGHTS FOR |
| | WINDOWS AND DOORS ARE ALSO AN UNKNOWN? |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDING |
| | BUILDING ENVELOPE |
| | WALL SYSTEMS |
| | |
| | 5D) THE STRUCTURE AND FOUNDATION ONLY PERMIT DOES NOT |
| | INDICATE IF THE CONTRACTOR IS ALSO INCLUDING THE |
| | EXTERIOR COMPONENTS AND CLADDING TO BE ABLE TO SEAL OUT |
| | WIND AND RAIN SINCE THE PRESSURES ARE PROVIDED FOR THE |
| | WINDOWS AND DOORS? ARE EXTERIOR BLOCK WALLS AND COLUMNS |
| | AND BEAMS TO BE INCLUDED? |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS/ MULLIONS. |
| | |
| | (B) WINDOWS/ MULLIONS FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. |
| | |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES. FOR ALL ROOFING |
| | PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND |
| | THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW |
| | THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING |
| | IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| | SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET |
| | AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. |
| | |
| | (F) SKYLIGHTS |
| | |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5E) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | 5F) FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS |
| | 1013.6 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 6) THE SOILS REPORT BY ARDAMAN & ASSOCIATES ON PAGE 3OF |
| | 19 RECOMMENDS THE USE OF 18 INCH DIAMETER AUGER CAST |
| | PILE ATTACHED TO GRADE BEAMS IN THE NORTHWEST CORNER OF |
| | THE BUILDING. SHEET 285_A120.7 IS THE NORTHWEST CORNER |
| | OF THE BUILDING THE FOUNDATION PLANS. IT APPEARS THE |
| | RECOMMENDATION OF THE SOILS ENGINEER WAS NOT TAKEN |
| | SINCE THE PLANS DO NOT SHOW AUGER-CAST PILE AND GRADE |
| | BEAMS. FOR THE LOADS TO BE SUPPORTED BY THE SPREAD |
| | FOUNDATIONS THE SOILS REPORT WILL NEED AN ADDENDUM |
| | PROVIDING WHAT THE MINIMUM SAFE BEARING VALUE WILL BE |
| | FOR THE SOIL PER SQUARE FOOT AND THE MINIMUM WIDTHS FOR |
| | THE VARIOUS FOUNDATIONS FOR THE GRAVITY LOADS TO BE |
| | RESISTED. FBC-B 1803.5.2 QUESTIONABLE SOILS. |
| | |
| | 7) THE SHEET 0285_S120.7 SHOWS A ELEVATION CHANGE IN |
| | THE FINISH FLOOR LEVELS BUT THE PLANS DO NOT PROVIDE AT |
| | WHAT ELEVATION EACH FLOOR LEVEL WILL BE. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8) SHEET 0285_S120.7 DETAIL # 20 INDICATES THE EXISTING |
| | WALL AND FOUNDATION ARE GOING TO REQUIRE UNDER PINNING |
| | BUT THE PLANS DO NOT INDICATE HOW THE UNDER PINNING IS |
| | TO OCCUR. THE SECOND ISSUE IS THE DETAIL AS SHOWN DOES |
| | NOT HAVE THE MATERIALS USED FOR UNDER PINNING CENTERED |
| | ON THE FOUNDATION THAT WILL CREATE A ECCENTRIC LOADING |
| | ? HOW WILL THE SOILS ON THE BACKSIDE OF THE |
| | UNDERPINNING BE STABILIZED TO NOT ALLOW CAVE INS DURING |
| | THE UNDERPINNING PROCESS? THE SOILS REPORT SECTION |
| | 5.3.3 REFERS TO VARIOUS PROCESSES THAT COULD BE USED IN |
| | THIS TYPE SITUATION. FBC-B 3307.1 PROTECTION REQUIRED. |
| | |
| | 9) SHEET 0285_S120.7 DETAIL #17 SHOWS A DETAIL OF THE |
| | DROPPED FLOOR SECTION BUT THE DETAIL DOES NOT INDICATE |
| | THE STAIRS AND TIERED SEATING. 107.2.1.3. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 10) SHEETS 0295_S124.7 THRU 0298_S125.8 EACH OF THE |
| | SHEETS INDICATE THEY ARE TO 1/8 INCH EQUALS A FOOT BUT |
| | THERE IS NO SCALE OR MEASUREMENTS ON THESE SHEETS TO BE |
| | ABLE TO SEE WHAT THE CENTER TO CENTER SPACING OF THE |
| | FRAMING MEMBERS ARE? THE SPACING OF THE FRAMING MEMBERS |
| | FOUND ON SHEET 0295_S124.7 BETWEEN GRID LINES 1.1 & 1.2 |
| | AND BETWEEN 2 & 3 IS QUITE A BIT LARGER THAN FOUND ON |
| | THE OTHER FRAMING SHEETS. DEPENDING ON THE TYPE OF ROOF |
| | DECK AND ROOFING MATERIAL SELECTED THE SPAN LIMITATION |
| | MAY BE MAXED OUT IN THE ROOFING DECK AS WELL AS THE |
| | ROOFING PRODUCT APPROVAL THAT NORMALLY COMES IN AT A |
| | LATER DATE. 107. 2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |