Plan Review Details - Permit 16080213
Plan Review Stops For Permit 16080213
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-09-02 Cont ID  
Sent By mgonzale Date 2016-09-02 Time   Rev Time 1.00
Received By mgonzale Date 2016-09-02 Time   Sent To I
Notes
2016-09-02 11:06:58NO OBJECTION TO LOCATION OF GREASE SEPARATORS.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-19 Cont ID  
Sent By tklarge Date 2017-04-19 Time 11:41 Rev Time 0.00
Received By tklarge Date 2017-04-14 Time 10:54 Sent To  
Notes
2017-04-17 10:54:17RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-02 Cont ID  
Sent By cpuell Date 2016-09-02 Time 13:50 Rev Time 0.00
Received By cpuell Date 2016-08-04 Time 11:21 Sent To  
Notes
2016-08-05 11:21:17ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-19 Cont ID  
Sent By tklarge Date 2017-04-19 Time 11:36 Rev Time 0.00
Received By tklarge Date 2017-04-18 Time 06:16 Sent To  
Notes
2017-04-19 11:40:55PLANS ARE NOT REQUIRED FOR THIS PERMIT. ALL INFORMATION
 FOR THE GREASE TRAPS IS SHOWN ON THE MASTER PLAN
 (16041215 ). THE ONLY THING REQUIRED TO ISSUE THIS
 PERMIT IS THE PERMIT APPLICATION SIGNED BY THE OWNER.
 T.LARGE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 06:53 Rev Time 0.00
Received By tklarge Date 2016-08-11 Time 06:40 Sent To  
Notes
2016-08-11 06:53:061) THE PERMIT APPLICATION IS FOR GREASE TRAPS BUT THE
 PLANS DO NOT HAVE ANY GREASE TRAP DTAILS. THERE IS A
 WATER AND WASTEWATER SHEET #8 THAT SHOWS THE LOCATION
 OF THE TWO GREASE INTERCEPTORS AND THAT IS IT. THERE IS
 A NOTE ON THE PLAN BY THE GREASE INTERCEPTORS THAT
 READS "REFER TO MEP PLANS FOR DETAILS" BUT THERE ARE NO
 MEP SHEETS IN THE PLANS.CLARIFY.
 2) THERE ARE PAVING, GRADING AND DRAINAGE PLANS IN THE
 PLAN SET BUT THE APPLICATION NOTES THAT THE PERMIT
 APPLICATION IS FOR THE INSTALLATION OF GREASE
 TRAPS.CLARIFY.
 3) SUBMIT TWO SETS OF PLANS AND CALCULATIONS FOR THE
 SIZING OF THE GREASE TRAPS. 2014 WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  