2016-08-12 14:09:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080135
 ADD: 801 S. OLIVE AVE. SUITE # 1411
 CONT: AMERICAN CONSTRUCTION SERVICES
 TEL: 954-590-8005
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 12/ 2016
 ACTION: DENIED
  
 1) SHEET A102 INDICATES IN THE GUEST BATHROOM THE
 REMOVAL OF FLOOR FINISHES AND NEW FLOOR TILE. FOR TILE,
 STONE, MARBLE AND WOOD FLOORING ALL NEED TO HAVE HAD
 THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 14:04 Rev Time 0.00
Received By mvaldes Date 2016-09-08 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By mvaldes Date 2016-08-08 Time 17:37 Rev Time 0.00
Received By mvaldes Date 2016-08-08 Time 16:49 Sent To  
Notes
2016-08-08 17:44:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) CLARIFY PANEL SCHEDULE "A" CIRCUIT # 13,15
 REFLECTING A 30 AMP DOUBLE POLE BREAKER FOR LIVING &
 BEDOOM ?
  
 2) ADD A GFCI 20 AMP RECEPTACLE FOR NEW VANITY IN
 MASTER BATHROOM, THE OUTLET SHALL BE WITHIN 3' OF SINK
 EDGE. NEC 210.8(A)(1) & 210.11(C)(3).
  
 3) SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314 &
 315. IF EXISTING MAKE A NOTE.
  
 4) ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT PER NEC 406.12. A NOTE WILL SUFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By pleduc Date 2016-08-31 Time   Rev Time 0.00
Received By pleduc Date 2016-08-31 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-11 Cont ID  
Sent By pleduc Date 2016-08-12 Time   Rev Time 0.00
Received By pleduc Date 2016-08-10 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-08-26 Time 11:07 Sent To  
Notes
2016-08-29 11:08:12B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-24 Time 12:50 Rev Time 0.00
Received By gjohnson Date 2016-08-03 Time 11:16 Sent To  
Notes
2016-08-04 11:16:36B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2016-08-12 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By gjohnson Date 2016-09-12 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2016-09-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-24 Cont ID  
Sent By gjohnson Date 2016-08-24 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2016-08-24 Time 12:43 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved