| 2016-09-12 10:19:23 | |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN |
| | SIGNATURE IS REQUIRED ON THE STRUCTURAL DRAWINGS, |
| | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC |
| | 61G15 - 23.002 |
| | |
| | 2) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN |
| | PURSUANT TO R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 3) SHOW COMPLIANCE WITH R302.12 DRAFTSTOPPING. IN |
| | COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE |
| | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A |
| | FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED |
| | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE |
| | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. |
| | WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE |
| | ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL |
| | BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE |
| | FOLLOWING CIRCUMSTANCES: |
| | 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. |
| | 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB |
| | OR PERFORATED MEMBERS. |
| | |
| | 4) PROVIDE A DETAIL OF THE STEEL POST CAP ON THE PLANS. |
| | FBC 107.2.1 |
| | |
| | 5) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATIONS. FBC ENERGY CONSERVATION - SECT. 103.1.1.2 |
| | CODE COMPLIANCE CERTIFICATION. THE BUILDING?S OWNER, |
| | THE OWNER?S ARCHITECT, OR OTHER AUTHORIZED AGENT |
| | LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE |
| | BUILDING IS IN COMPLIANCE WITH THE CODE, AS PER SECTION |
| | 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING THE |
| | PERMIT TO BEGIN CONSTRUCTION OR RENOVATION. |
| | |
| | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | OUT DOOR BBQ AND HOOD. FBC 107.2.1 |
| | |
| | 7) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORTS |
| | WITH INSTALLATION REQUIREMENTS FOR THE ICYENE SPRAY |
| | FOAM INSULATION. FBC R316 |
| | |
| | 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE ROOFING MATERIALS, AS WELL AS, THE DECK AND BALCONY |
| | WATERPROOFING SYSTEMS. |
| | |
| | 9) THE DOOR SCHEDULE ON SHEET A-6 OF THE PLANS |
| | SPECIFIES CGI ( NOA NO. 16-0303.01 ) FOR THE SLIDING |
| | GLASS DOOR AND ( NOA NO. 15-1013.15 ) FOR PGT SLIDING |
| | GLASS DOORS WAS SUBMITTED. |
| | |
| | 10) THE DOOR SCHEDULE ON SHEET A-6 OF THE PLANS |
| | SPECIFIES CGI ( NOA NO. 14-1103.08 ) FOR THE FRENCH |
| | DOORS AND ( NOA NO. 14-1117.05 ) FOR PGT GLAZED FRENCH |
| | DOORS WAS SUBMITTED. |
| | |
| | 11) PRODUCT APPROVALS WERE SUBMITTED FOR PGT CA-740 |
| | FIXED CASEMENT WINDOWS (NOA NO. 15-0519.15 ). THIS |
| | PRODUCT APPROVALS IS NOT LISTED IN THE WINDOW SCHEDULE |
| | ON SHEET A-6. THE WINDOW AND DOOR SCHEDULES SPECIFY CGI |
| | WINDOWS AND DOORS. |
| | |
| | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |