| 2016-08-11 14:44:52 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: TOUB RESIDENCE/REMODEL |
| | JOB ADDRESS: 221 POTTER ROAD |
| | DESCRIPTION: REMOVE EXISTING GENERATOR & RELOCATE W/NEW |
| | GENERATOR PER PLANS |
| | MASTER PERMIT: 16080116 |
| | REVISION: |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: |
| | |
| | 1. NEC 702.4(B): PROVIDE LOAD CALCS IN ACCORDANCE W/NEC |
| | 220. |
| | 2. NEC 702.4(B)(2): STANDBY GENERATOR SHALL BE CAPABLE |
| | OF SUPPLYING THE FULL LOAD APPLIED, OR ATS NOT |
| | PERMITTED W/O ACCEPTABLE LOAD SHED PROVISIONS. |
| | 3. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE |
| | EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS. |
| | 4. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM |
| | SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE |
| | TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS. |
| | INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING. |
| | 5. NEC 250.104(B): SHOW ON PLANS WHERE THE GAS LINE IS |
| | BONDED. EQUIPMENT BONDING CONDUCTOR PER NEC 250.122. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |