| 2016-08-12 06:15:45 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080066 |
| | ADD: 303 BANYAN BLVD. 3RD FLOOR/ NEW CONFERENCE ROOM. |
| | CONT: IBIS BUILDING |
| | TEL: 561-568-2570 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. AUGUST 12/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE (3) A1.1 FLOOR PLANS WERE SUBMITTED ONLY |
| | ONE WAS SIGNED AND SEALED BY THE DESIGNER OF RECORD. |
| | PLEASE NOTE ON THE OTHER TWO SHEETS ONE MECHANICAL |
| | SYSTEMS WAS DRAWN IN THE OTHER ELECTRICAL SYSTEMS WERE |
| | DRAWN IN. IF THIS IS NOT WORK COMPLETED BY THE DESIGNER |
| | OF RECORD, THE AUTHOR OF THESE SHEETS ARE VIOLATING |
| | COPYRIGHT LAWS. PLEASE NOTE THERE ARE NO ELECTRICAL NOR |
| | MECHANICAL CONTRACTORS SIGNED ON AS SUB-PERMITS. ONLY |
| | THE QUALIFIER FOR EACH OF THOUGHS COMPANIES ELECTRICAL |
| | & MECHANICAL CAN DEVELOP THEIR OWN PLAN UNDER THERE |
| | LICENSE. THEY WILL NEED TO PRINT THEIR NAME SIGN THEIR |
| | NAME AND PRINT THEIR LICENSE NUMBER ON THE DOCUMENT |
| | THEY CREATED. THEY CAN NOT CREATE A DOCUMENT FOR |
| | ANOTHER CONTRACTOR IT HAS TO BE THE PROPOSED WORK THEIR |
| | COMPANY IS LICENSED FOR AND WORK THEY WILL BE |
| | PREFORMING UNDER THEIR LICENSE. 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.1. |
| | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| | UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| | STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| | PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| | CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| | STATUTES. |
| | |
| | 2) PLANS NEED TO BE BOUND TOGETHER INTO ONE SET OF |
| | DOCUMENTS BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| | IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. |
| | |
| | 3) SHEET A1.1 INDICATES 6 UL WALL PENETRATION SYSTEMS |
| | BUT DOES NOT PROVIDE THE UL DOCUMENTATION FOR EACH |
| | SYSTEM WHAT MAKES UP EACH SYSTEM. THE FIELD INSPECTORS |
| | NEED THIS INFORMATION TO SEE WHAT COMPONENTS EACH |
| | SYSTEM IS MADE FROM, AND THE LIMITATIONS ON EACH |
| | SYSTEM. PROVIDE DOCUMENTATION. |
| | 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 4) WITH THIS NEW TENANT SPACE THERE WILL BE MORE LIKELY |
| | A NEW FIRE SPRINKLER LAYOUT REQUIRED. PLEASE NOTE WHEN |
| | LESS THAN 50 SPRINKLER HEADS ARE BEING MOVED, THE PLANS |
| | CAN BE CREATED BY THE FIRE SPRINKLER CONTRACTOR. |
| | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| | UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| | STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| | PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| | CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| | STATUTES. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |