Plan Review Details - Permit 16080035
Plan Review Stops For Permit 16080035
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 12:03 Rev Time 0.00
Received By albarran Date 2016-08-25 Time 11:44 Sent To I
Notes
2016-08-25 12:03:49ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By albarran Date 2016-08-16 Time 14:36 Rev Time 0.00
Received By albarran Date 2016-08-16 Time 11:11 Sent To M
Notes
2016-08-16 14:41:232ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010 & NFPA 70 2008 (NEC)
  
 PROJECT:
 JOB ADDRESS: 1220 ORTEGA RD.
 DESCRIPTION: MECHANICAL & ELECTRICAL CHANGES
 MAST. PERMIT: 15060911
 REVISION: 16080035
  
 BELOW IS A COPY OF MY PREVIOUS COMMENTS ALONG WITH
 NOTES OF THE CORRECTIONS REQUIRED. THE BLANK LINE ITEMS
 HAVE BEEN SATISFACTORILY COMPLIED WITH.
  
 THE LACK OF A NARRATIVE PROMPTED ME TO REVIEW THE
 COMPLETE SUBMITTAL TO FIND THAT THERE WERE ELECTRICAL
 CHANGES BEYOND THE CORRECTIONS REQUIRED FROM PREVIOUS
 REVIEW. BELOW ARE THE CORRECTIONS REQUIRED FOR A
 SUCCESSFUL ELECTRICAL REVIEW.
  
 1. YOU WERE PREVIOUSLY INFORMED OF THE SIGN OUTLET
 REQUIREMENT OF NEC 600.5 WHICH WAS NOT COMPLIED WITH ON
 THE RESUBMITTAL.
  
 A) NEC 600.5 REQUIRES THAT THERE BE A SIGN OUTLET AT
 EACH ENTRY DOOR WITH ONLY ONE EXCEPTION, THE DOOR TO A
 SERVICE CORRIDOR. YOU ADDED THE SIGN OUTLET AT ONLY ONE
 DOOR. THERE IS A DOORWAY ADJACENT TO PANEL F; THERE IS
 ANOTHER DOOR ON THE N.E. END AS WELL AS ONE ON THE WEST
 SIDE OF THE BLDG. ALL OF WHICH REQUIRE SIGN OUTLETS.
  
 2. THERE IS AN EXIT OUT OF THE MAIN WAREHOUSE AREA
 LEADING INTO AN EXISTING OFFICE. THERE IS NO INDICATION
 OF EXISTING EXIT OR EMERGENCY LIGHTING IN THAT AREA.
 PLEASE INDICATE IF THERE IS AN EMERGENCY AND EXIT
 LIGHTING IN THAT SPACE AND IF THERE IS NOT, PLEASE
 CORRECT TO INCLUDE. SEE FBC 2010 SECTIONS 1006 & 1011.
 (W/O A COMPASS POINT ON THE PLANS IT IS DIFFICULT TO
 IDENTIFY THE LOCATION. IN THE FUTURE PLEASE INCLUDE A
 COMPASS POINT ON ALL PLANS).
  
 A) YOU ADDED THE REQUIRED EXIT LIGHTS BUT ACCORDING TO
 THE NOTE ON THE CIRCUIT DIRECTORY FOR PANEL F, THEY ARE
 RUN THRU THE TIMER. EMERGENCY OR EXIT LIGHTS SHALL NOT
 BE RUN THRU THE TIMER.
  
 3. COMPLIED
  
 4. COMPLIED
  
 5. CORRECT THE CIRCUIT DIRECTORY OF PANEL A TO MATCH
 CIRCUIT DESIGNATION ON THE FLOOR PLANS FOR THE NEW
 EVAP. UNITS.
  
 A) EVAP UNITS FORMERLY ASSIGNED TO PANEL A HAVE BEEN
 REASSIGNED TO PANEL F, BUT THE CIRCUIT DESIGNATIONS AND
 THE FLOOR PLAN DO NOT MATCH.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE?SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561?805?6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By albarran Date 2016-08-02 Time 15:17 Rev Time 0.00
Received By albarran Date 2016-08-02 Time 14:18 Sent To  
Notes
2016-08-02 15:19:06ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010 & NFPA 70 2008 (NEC)
  
 PROJECT:
 JOB ADDRESS: 1220 ORTEGA RD.
 DESCRIPTION: MECHANICAL & ELECTRICAL CHANGES
 MAST. PERMIT: 15060911
 REVISION: 16080035
  
 THE LACK OF A NARRATIVE PROMPTED ME TO REVIEW THE
 COMPLETE SUBMITTAL TO FIND THAT THERE WERE ELECTRICAL
 CHANGES BEYOND THE CORRECTIONS REQUIRED FROM PREVIOUS
 REVIEW. BELOW ARE THE CORRECTIONS REQUIRED FOR A
 SUCCESSFUL ELECTRICAL REVIEW.
 1. YOU WERE PREVIOUSLY INFORMED OF THE SIGN OUTLET
 REQUIREMENT OF NEC 600.5 WHICH WAS NOT COMPLIED WITH ON
 THE RESUBMITTAL.
 2. THERE IS AN EXIT OUT OF THE MAIN WAREHOUSE AREA
 LEADING INTO AN EXISTING OFFICE. THERE IS NO INDICATION
 OF EXISTING EXIT OR EMERGENCY LIGHTING IN THAT AREA.
 PLEASE INDICATE IF THERE IS EMERGENCY AND EXIT LIGHTING
 IN THAT SPACE AND IF THERE IS NOT, PLEASE CORRECT TO
 INCLUDE. SEE FBC 2010 SECTIONS 1006 & 1011. (W/O A
 COMPASS POINT ON THE PLANS IT IS DIFFICULT TO IDENTIFY
 THE LOCATION. IN THE FUTURE PLEASE INCLUDE A COMPASS
 POINT ON ALL PLANS).
 3. IDENTIFY ALL PANELS ON THE FLOORPLAN TO MATCH THE
 RISER DIAGRAM. THERE ARE THREE(3) PANELS REFLECTED ON
 THE FLOOR PLAN, 2 EXISTING AND 1 NEW. THE RISER DIAGRAM
 SHOWS 5 PANELS, FOUR (4) EXISTING AND A NEW. WHICH IS
 CORRECT AND HAVE THEM MATCH?
 4. PROVIDE LOAD CALCS FOR THE SERVICE NOT JUST THE NEW
 PANEL.
 5. CORRECT THE CIRCUIT DIRECTORY OF PANEL A TO MATCH
 CIRCUIT DESIGNATION ON THE FLOOR PLANS FOR THE NEW
 EVAP. UNITS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 12:06 Rev Time 0.00
Received By albarran Date 2016-08-17 Time 16:41 Sent To  
Notes
2016-08-25 12:06:488/25/16 ALL TRADE REVIEWS HAVE BEEN APPROVED.
 CONTRACTOR NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY
 BIN "H". MA
2016-08-17 16:43:03ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 16:43 Rev Time 0.00
Received By ccole Date 2016-08-11 Time 10:11 Sent To  
Notes
2016-08-12 10:11:53RESUB OF REVISION ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By ccole Date 2016-08-03 Time 06:53 Rev Time 0.00
Received By ccole Date 2016-08-01 Time 11:00 Sent To  
Notes
2016-08-02 11:00:50REVISION ROUTED TO MALBARRAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 16:43 Rev Time 0.00
Received By ccole Date 2016-08-16 Time 16:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-08-03 Cont ID  
Sent By ccole Date 2016-08-03 Time 07:17 Rev Time 0.00
Received By ccole Date 2016-08-03 Time 06:54 Sent To  
Notes
2016-08-03 07:23:58MECHANICAL PROVISOS
 PERMIT #16080035
 8/3/16
  
 1) THE REVISED PLANS SHOULD HAVE BEEN TAKEN IN AS A
 RESUB TO REVISION #16070440, AND NOT AS REVISION
 #16080035.
  
 2) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE CONDENSER PADS AND MOUNTING OF THE CONDENSERS
 SHALL BE ONSITE AT TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  