| 2016-08-16 14:41:23 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 2010 & NFPA 70 2008 (NEC) |
| | |
| | PROJECT: |
| | JOB ADDRESS: 1220 ORTEGA RD. |
| | DESCRIPTION: MECHANICAL & ELECTRICAL CHANGES |
| | MAST. PERMIT: 15060911 |
| | REVISION: 16080035 |
| | |
| | BELOW IS A COPY OF MY PREVIOUS COMMENTS ALONG WITH |
| | NOTES OF THE CORRECTIONS REQUIRED. THE BLANK LINE ITEMS |
| | HAVE BEEN SATISFACTORILY COMPLIED WITH. |
| | |
| | THE LACK OF A NARRATIVE PROMPTED ME TO REVIEW THE |
| | COMPLETE SUBMITTAL TO FIND THAT THERE WERE ELECTRICAL |
| | CHANGES BEYOND THE CORRECTIONS REQUIRED FROM PREVIOUS |
| | REVIEW. BELOW ARE THE CORRECTIONS REQUIRED FOR A |
| | SUCCESSFUL ELECTRICAL REVIEW. |
| | |
| | 1. YOU WERE PREVIOUSLY INFORMED OF THE SIGN OUTLET |
| | REQUIREMENT OF NEC 600.5 WHICH WAS NOT COMPLIED WITH ON |
| | THE RESUBMITTAL. |
| | |
| | A) NEC 600.5 REQUIRES THAT THERE BE A SIGN OUTLET AT |
| | EACH ENTRY DOOR WITH ONLY ONE EXCEPTION, THE DOOR TO A |
| | SERVICE CORRIDOR. YOU ADDED THE SIGN OUTLET AT ONLY ONE |
| | DOOR. THERE IS A DOORWAY ADJACENT TO PANEL F; THERE IS |
| | ANOTHER DOOR ON THE N.E. END AS WELL AS ONE ON THE WEST |
| | SIDE OF THE BLDG. ALL OF WHICH REQUIRE SIGN OUTLETS. |
| | |
| | 2. THERE IS AN EXIT OUT OF THE MAIN WAREHOUSE AREA |
| | LEADING INTO AN EXISTING OFFICE. THERE IS NO INDICATION |
| | OF EXISTING EXIT OR EMERGENCY LIGHTING IN THAT AREA. |
| | PLEASE INDICATE IF THERE IS AN EMERGENCY AND EXIT |
| | LIGHTING IN THAT SPACE AND IF THERE IS NOT, PLEASE |
| | CORRECT TO INCLUDE. SEE FBC 2010 SECTIONS 1006 & 1011. |
| | (W/O A COMPASS POINT ON THE PLANS IT IS DIFFICULT TO |
| | IDENTIFY THE LOCATION. IN THE FUTURE PLEASE INCLUDE A |
| | COMPASS POINT ON ALL PLANS). |
| | |
| | A) YOU ADDED THE REQUIRED EXIT LIGHTS BUT ACCORDING TO |
| | THE NOTE ON THE CIRCUIT DIRECTORY FOR PANEL F, THEY ARE |
| | RUN THRU THE TIMER. EMERGENCY OR EXIT LIGHTS SHALL NOT |
| | BE RUN THRU THE TIMER. |
| | |
| | 3. COMPLIED |
| | |
| | 4. COMPLIED |
| | |
| | 5. CORRECT THE CIRCUIT DIRECTORY OF PANEL A TO MATCH |
| | CIRCUIT DESIGNATION ON THE FLOOR PLANS FOR THE NEW |
| | EVAP. UNITS. |
| | |
| | A) EVAP UNITS FORMERLY ASSIGNED TO PANEL A HAVE BEEN |
| | REASSIGNED TO PANEL F, BUT THE CIRCUIT DESIGNATIONS AND |
| | THE FLOOR PLAN DO NOT MATCH. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE?SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |