Plan Review Details - Permit 16071233
Plan Review Stops For Permit 16071233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-16 Cont ID  
Sent By cthroop Date 2016-09-16 Time 14:20 Rev Time 0.00
Received By cthroop Date 2016-09-16 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By cthroop Date 2016-09-02 Time 08:39 Rev Time 0.00
Received By cthroop Date 2016-09-01 Time 15:03 Sent To  
Notes
2016-09-02 08:44:06BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. STRUCTURE IDENTIFCATION ON PLAN PAGE C-1 SHOULD READ
 "PROPOSED 2 STORY RESIDENCE".
 2. PROVIDE DESIGN WIND LOADS FOR DOOR AND WINDOW
 OPENINGS.
 3. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 SUBMITTALS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-01 Cont ID  
Sent By albarran Date 2016-08-01 Time 17:28 Rev Time 0.00
Received By albarran Date 2016-08-01 Time 15:57 Sent To  
Notes
2016-08-01 17:36:58ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 EVEN THOUGH THE ELECTRICAL PLAN REVIEW WAS APPROVED,
 THERE ARE TWO NOTES BEING ADDED TO THE APPROVED
 DRAWINGS:
 1. THE GENERATOR IS ADDRESSED ON THIS SET OF PLANS BUT
 IF AND WHEN IT IS TO BE INSTALLED, IT SHALL BE UNDER A
 SEPARATE PERMIT AND SUBMITTAL. THE GENERATOR PERMIT
 MUST BE ACCOMPANIED BY GENERATOR SPECS AND A REVISED
 ELECTRICAL RISER DIAGRAM.
 2. CORRECTION TO THE FBC-R ENERGY CONSERVATION NOTE TO
 BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
 FBC-RE404.1 TO WHICH 75% OF ALL PERMANENTLY INSTALLED
 LAMPS SHALL OF THE HIGH EFFICIENCY TYPE.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-21 Time 12:53 Rev Time 0.00
Received By tklarge Date 2016-09-09 Time 14:09 Sent To  
Notes
2016-09-09 14:09:42RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-06 Cont ID  
Sent By hmoser Date 2016-09-06 Time 10:13 Rev Time 0.00
Received By hmoser Date 2016-07-29 Time 15:47 Sent To  
Notes
2016-07-29 15:47:09R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2016-09-01 Cont ID  
Sent By cthroop Date 2016-09-01 Time 15:31 Rev Time 0.00
Received By cthroop Date 2016-09-01 Time 15:31 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2016-08-02 Cont ID  
Sent By rcaranci Date 2016-08-02 Time 16:55 Rev Time 0.00
Received By rcaranci Date 2016-08-02 Time 16:55 Sent To M
Notes
2016-08-02 16:57:57SEPARATE LANDSCAPE PERMIT REQUIRED, MUST SUBMIT PRIOR
 TO ISSUANCE OF THIS PERMIT. LANDSCAPE PLANS ARE IN THIS
 PERMIT, NEED TO BE REMOVED AND SUBMITTED WITH LANDSCAPE
 PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-09-06 Cont ID  
Sent By hmoser Date 2016-09-06 Time 10:13 Rev Time 0.00
Received By hmoser Date 2016-09-06 Time 10:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-21 Cont ID  
Sent By tklarge Date 2016-09-20 Time 12:53 Rev Time 0.00
Received By tklarge Date 2016-09-20 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By tklarge Date 2016-08-24 Time 07:12 Rev Time 0.00
Received By tklarge Date 2016-08-24 Time 06:22 Sent To  
Notes
2016-08-24 07:00:161) SHTS. C1 & EC 1 DESIGNATE THE BUILDING AS A PROPOSED
 ONE STORY STRUCTURE YET THE ARCHITECTURAL/PLUMBING ETC.
 PLANS SHOW A TWO STORY BUILDING. CLARIFY.
 2) THE WATER CLOSET AND SHOWER IN THE MASTER BATH ISS
 NOT VENTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-09-01 Cont ID  
Sent By cthroop Date 2016-09-01 Time 15:52 Rev Time 0.00
Received By cthroop Date 2016-09-01 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-15 Cont ID  
Sent By njwira Date 2016-09-15 Time 15:50 Rev Time 0.00
Received By njwira Date 2016-09-12 Time 14:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-02 Cont ID  
Sent By nwair Date 2016-08-02 Time 16:17 Rev Time 0.00
Received By njwira Date 2016-08-02 Time 16:17 Sent To L
Notes
2016-08-02 16:26:528/2/16- PASSED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 1. 100FT. WIDE MEETS THE 60FT. LOT WIDTH REQUIREMENT.
 2. LOT SIZE IS 19,022SQFT. MEETS THE 6,000 SQFT. LOT
 REQUIREMENT.
 3. FRONT SETBACK IS 49.8 MEETING THE 25FT. FRONT
 SETBACK REQUIREMENT.
 4. REAR SETBACK IS 83.5FT. MEETING THE 15FT. REAR
 SETBACK REQUIREMENT.
 5. SIDE SETBACK IS 5.1FT. MINIMUM AND 16.7FT. TOTAL
 MEETING THE 5FT. MINIMUM AND 15FT. TOTAL SIDE SETBACK
 REQUIREMENT.
 6. A/C UNIT IS NOT LOCATED WITHIN A REQUIRED SETBACK.
 7. POOL IS EXISTING AND ON A SEPORATE PERMIT.
 8. ONE KITCHEN SO ONE UNIT ON THE PROPERTY.
 9. BUILDING HEIGHT IS 25FT. 10IN. MEETING THE 30FT.
 HEIGHT LIMIT IN THE DISTRICT.
 10. ROOF OVERHANG IS 1FT. 6IN. MEETING THE 3FT. LIMIT
 INTO A REQUIRED SETBACK.
 11. 11,670 OF IMPERVIOUS SURFACE MEETS THE 1,000FT. OF
 REQUIRED IMPERVIOUS SURFACE.
 12. ACCESSORY STRUCTURES MEET THE SIZE AND SETBACK
 REQUIREMENTS.
 13. NO TREES BEING REMOVED
 14. GAZEBO IS NOT LOCATED WITHIN A REQUIRED SETBACK
 ALONG WITH THE DECK.
 15. DRIVEWAY IS 18FT. MEETING THE 20FT. LIMIT AND NOT
 WITHIN THE 20FT. SIDE SETBACK.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  