Plan Review Details - Permit 16071104
Plan Review Stops For Permit 16071104
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 19:14 Rev Time 0.00
Received By mvaldes Date 2016-08-17 Time 18:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 18:25 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 18:25 Sent To  
Notes
2016-08-04 18:27:56REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
  
  
  
 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) COMPLETE ELECTRICAL COMPLIANCE IS DEPENDENT ON FIRE
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-17 Cont ID  
Sent By pleduc Date 2016-08-17 Time   Rev Time 0.00
Received By pleduc Date 2016-08-16 Time 16:17 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By pleduc Date 2016-08-04 Time   Rev Time 0.00
Received By pleduc Date 2016-08-04 Time 15:10 Sent To E
Notes
2016-08-04 15:40:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN SHEETS ARE NOT BOUND OR
 ORGANIZED.
  
 1.7.11 PLANS AND SPECIFICATIONS.
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 EACH SET OF PLAN SHEETS SHALL BE BOUND AND ORGANIZED TO
 AVOID CONFUSION AND/OR LOST SHEETS.
  
  
 2) THERE IS NO REFERNCE TO ANY INDICATED NFPA CODE
 COMPLIANCE.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE THE APPLICABLE NFPA CODE.
  
  
  
 3) THE SUBMITTED PALNS DO NOT INDICATE A SYMBOL/PRODUC
 TABLE.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE PROVICE THE APPLICABLE TABLE AND PRODUCT
 IDENTIFICATION.
  
  
  
 4) A WIRING DIAGRAM OR WIRE DETAIL IS NOT INDICATED.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE ALL APPLICABLE WIRING INFORMATION
 INCLUDING THE FA SYSTEM SCHEMATIC DRAWING.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 19:14 Rev Time 0.00
Received By mvaldes Date 2016-08-15 Time 09:59 Sent To  
Notes
2016-08-16 09:59:45RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 18:28 Rev Time 0.00
Received By mvaldes Date 2016-07-28 Time 09:25 Sent To  
Notes
2016-07-29 09:25:38ROUTED TO FIRE INBOX