Plan Review Details - Permit 16071099
Plan Review Stops For Permit 16071099
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 08:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2016-10-22 Time 09:28 Sent To  
Notes
2016-10-22 10:54:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071099
 ADD: 501 FERN ST. SUITE #102
 CONT: JOHN ROSSI CONSTRUCTION
 TEL: 561-659-5505
 E-MAIL: ROSSI:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. OCT. 22/ 2016
 ACTION: DENIED
  
 1) SHEET A2, A3, LS1 AND LS2 ALL SHOW THE DOOR # 102 A
 SINGLE DOOR BEING WIDENED TO A DOUBLE DOOR. THERE IS NO
 INFORMATION HOW THE STRUCTURAL SUPPORT IN THIS WALL
 WILL BE DESIGNED, A NEW COLUMN TO THE WEST SIDE OF THE
 DOORWAY, AND EITHER NEW LINTEL OR BEAM. THIS WALL IS
 PART OF THE MAIN WIND FORCE RESISTING SYSTEM, (MWFRS).
 1901.3 CONSTRUCTION DOCUMENTS. THE CONSTRUCTION
 DOCUMENTS FOR STRUCTURAL CONCRETE CONSTRUCTION SHALL
 INCLUDE:
  
 1.1. THE SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE AT
 THE STATED AGES OR STAGES OF CONSTRUCTION FOR WHICH
 EACH CONCRETE ELEMENT IS DESIGNED.
  
 1.2. THE SPECIFIED STRENGTH OR GRADE OF REINFORCEMENT.
  
 1.3. THE SIZE AND LOCATION OF STRUCTURAL ELEMENTS,
 REINFORCEMENT
  
 1.4 1913.1 REINFORCED CONCRETE COMPONENTS.
  
 2) PLEASE PROVIDE THE PRESSURES ASCE 7-10 FOR THIS NEW
 OPENING. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (180
 MPH/ EXPOSURE C.
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-31 Cont ID  
Sent By jwitmer Date 2016-08-31 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2016-08-31 Time 07:02 Sent To  
Notes
2016-08-31 07:33:24BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071099
 ADD: 501 FERN ST. SUITE #102
 CONT: JOHN ROSSI CONSTRUCTION
 TEL: 561-659-5505
 E-MAIL: ROSSI:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 04/ 2016
 ACTION: DENIED
  
 1-6A) COMPLIED.
  
 6B) SHEET LS 1 AND A.3 SHOW A LOBBY BUT NO INFORMATION
 IS GIVEN ON THE STAIRS, RAMP HAND RAILS NOR THE
 GUARDRAILS. PLEASE NOTE THE CITY GAVE A ONE TIME USE ON
 A TEMPORARY EVENT PERMIT FOR THESE ITEMS, BUT IT WAS A
 ONE TIME EVENT. UNDER THAT ONE TIME EVENT THERE WERE NO
 LOADS GIVEN.
 2014 FBC-B 1009.7.2 RISER HEIGHT AND TREAD DEPTH.
 1009.3.1.1 MATERIALS
 1010.1 RAMPS SCOPE
 1010.3 SLOPE
 1010.5 VERTICAL RISE
 1010.7 LANDINGS.
 1010.7.4 CHANGE IN DIRECTION
 1010.8 RAMP CONSTRUCTION
 1010.9 HANDRAILS. & SECTION 1012
 1010.11 GUARDS. & SECTION 1013.
 TABLE 1607.1 LIVE LOADS STAIRS AND RAMPS
 1028.2 ASSEMBLY MAIN EXIT.
 1028.3 ASSEMBLY OTHER EXITS.
 2014 FBC-ACCESS. CODE SECTION 405. RAMPS / STAIRS 504.
 216.1. SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216
 AND SHALL COMPLY WITH 703.
 216.9.2 DIRECTIONAL SIGNS.
  
 6C) SHEET A.4 DETAIL A DOES NOT INDICATE WHAT THE
 MATERIALS THIS RAMP IS MADE FROM NOR THE LIVE LOADS FOR
 THE RAMP NOR THE HANDRAIL SYSTEM. 1607.8.1.1
 CONCENTRATED LOAD. HANDRAILS AND GUARDS SHALL ALSO BE
 DESIGNED TO RESIST A CONCENTRATED LOAD OF 200 POUNDS
 (0.89 KN) IN ACCORDANCE WITH SECTION 4.5.1 OF
 ASCE 7.
  
  
 7-9) COMPLIED.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 15:34 Rev Time  
Received By jwitmer Date 2016-08-04 Time   Sent To  
Notes
2016-08-04 15:34:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071099
 ADD: 501 FERN ST. SUITE #102
 CONT: JOHN ROSSI CONSTRUCTION
 TEL: 561-659-5505
 E-MAIL: ROSSI:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 04/ 2016
 ACTION: DENIED
  
 1) THE COVER-SHEET A.1 UNDER THE SCOPE OF WORK
 INDICATES THIS IS TO BE A CHANGE OF OCCUPANCY FROM A
 WAREHOUSE TO AN A-2 OCCUPANCY. PLEASE NOTE THE
 COVERSHEET ALSO STATES THIS IS A LEVEL III ALTERATION.
 PLEASE UPDATE THE DRAWING TO A CHANGE OF OCCUPANCY, TO
 BE DESIGNED AND REVIEWED UNDER CHAPTER 10 OF THE
 EXISTING BUILDING CODE. 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 2) THE LIFE SAFETY PLAN CALLS OUT THIS TENANT SPACE IS
 TO BE AN EVENT HALL, THE WORST CASE SCENARIO WILL NEED
 TO TAKE PRECEDENCE. PLEASE NOTE THE COVERSHEET & SHEET
 LS 1 BOTH INDICATE THE OCCUPANT LOAD TO BE REDUCED.
 MAXIMUM EVENT OCCUPANT LOAD OF 225 PERSONS PER SPECIAL
 PROVISIONS EXCEPTION FBC2014 SECTION 1004.1.2. PLEASE
 NOTE THE LIFE SAFETY PLAN DOES NOT SHOW ANY TABLES AND
 CHAIRS SUCH AS AN A2 OCCUPANCY (BANQUET HALL) WOULD
 HAVE. THE CODE REQUIRES THE STRICTER USE OF 7 SQ. FT./
 OCCUPANT WHEN NO TABLES AND CHAIRS ARE SHOWN IN THE
 LIFE SAFETY PLAN. TO DATE NEITHER THE BUILDING OFFICIAL
 NOR THE FIRE MARSHALL HAVE SEEN A LETTER ASKING BOTH
 DEPARTMENTS FOR THE REDUCED LOADING. 7,057/ 7 SQ. FT.
 PER OCC.= 1009 OCCUPANTS.
 7057 SQ. F./ 15 SQ. FT. PER OCC. =471 OCCUPANTS.
  
 PLEASE ALSO NOTE BECAUSE OF THE FLEXIBILITY OF THE
 TENANT SPACE AND THE ISSUES THAT MAY ARISE WITH EACH
 EVENT, THIS EVENT SPACE WILL NEED TO FILE A SPECIAL
 EVENT PERMIT WITH THE FIRE DEPARTMENT SHOWING THE
 USAGE, PROPOSED OCCUPANT LOAD, LAYOUT OF FURNITURE OR
 OTHER OBSTACLES, EGRESS AISLES, FINISHES HUNG ON WALLS
 AND OR FROM CEILINGS, ETC.
  
 3) PLEASE SEE THE NUMBER OF REQUIRED EXITS WOULD BE
 REQUIRED FOR 1009 OCCUPANTS. 1015.1.1 THREE OR MORE
 EXITS OR EXIT ACCESS DOORWAYS. THREE EXITS OR EXIT
 ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH
 AN OCCUPANT LOAD OF 501 TO 1,000. FOUR EXITS OR EXIT
 ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH
 AN OCCUPANT LOAD GREATER THAN 1,000. SHOW EGRESS FOR
 THE WORST CASE SCENARIO.
  
 4) PLEASE ALSO NOTE WHEN THE OCCUPANT LOAD WHEN THE
 PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY WITH AN OCCUPANT
 LOAD OF GREATER THAN 300. PLEASE NOTE THIS BUILDING HAS
 2 AREAS OF PUBLIC ASSEMBLY, AREAS A, & C.
 THE RISK CATEGORY FOR THE STRUCTURE INCREASES FROM A
 RISK FACTOR II TO A RISK FACTOR OF III. SEE TABLE
 1604.5 RISK CATEGORY OF BUILDINGS. PLEASE ALSO REVIEW
 FIGURE 1609B FOR RISK CATEGORY III BUILDINGS, 180 MPH
 VULT.
 THE BUILDING WILL NEED TO BE ANALYZED FOR THE HIGHER
 WIND SPEED. SECTION 1007.2. WIND LOADS.
  
  
  
  
 5) THE BUILDING SQUARE FOOT AREA IS OVER THE ALLOWABLE
 6,000 SQ. FT. AREA PER TABLE 503 FOR EITHER AN A2 OR A3
 OCCUPANCY. PLEASE PROVIDE THE AREA AND OR SPRINKLER
 INCREASES TAKEN TO COMPLY WITH THE CODE. 506.1 GENERAL.
 THE BUILDING AREAS LIMITED BY TABLE 503 SHALL BE
 PERMITTED TO BE INCREASED DUE TO FRONTAGE (IF) AND
 AUTOMATIC SPRINKLER SYSTEM PROTECTION (IS) IN
 ACCORDANCE WITH EQUATION 5-1.
  
 6) THE 2014 EXISTING BUILDING CODE SECTION 1013 ENERGY
 CONSERVATION. SEE THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION. PLEASE BE AWARE THE ENGINEER HAS
 SUBMITTED ENERGY GAUGE ASHRAE 90.1 THE ENERGY COST
 BUDGET METHOD OF COMPLIANCE. THE DOCUMENTS SUBMITTED
 HAVE LITTLE DATA IN REGARDS TO THE THERMAL ENVELOPE
 WHICH WILL NEED TO BE ADDRESSED UNDER 11.ENERGY COST
 BUDGET METHOD 11.1.3 ENVELOPE LIMITATIONS ALSO SEE 11.2
 COMPLIANCE REQUIREMENTS A-C. THE PLANS NEED TO SHOW THE
 COMPLIANCE WITH THE VALUES GIVEN IN THE REPORT.
 INSPECTIONS WILL VERIFY ASSUMPTION?S IN THE FIELD. NO
 INFORMATION PROVIDED FOR ROOFING NOR IS THERE
 ELEVATIONS SHOWING THE SIZES OF THE GLAZED OPENINGS.
  
 6) 2014 FBC-EXISTING BUILDING CODE SECTION 1012.1.3
 CHANGE OF OCCUPANCY CLASSIFICATION BASED ON HAZARD
 CATEGORY. THE RELATIVE DEGREE OF HAZARD BETWEEN
 DIFFERENT OCCUPANCY CLASSIFICATIONS SHALL BE DETERMINED
 IN ACCORDANCE WITH THE CATEGORIES SPECIFIED IN TABLES
 1012.4, 1012.5 AND 1012.6. SUCH A DETERMINATION SHALL
 BE THE BASIS FOR THE APPLICATION OF SECTIONS 1012.4
 THROUGH 1012.7.
  
 6A) THE LIFE SAFETY PLAN WILL NEED TO SHOW HOW THE
 AMOUNT OF OCCUPANTS THAT ARE GOING THROUGH DOORWAYS,
 GIVE THE CLEAR WIDTH, DOWN THE STAIR AND RAMPS AGAIN
 PROVIDE THE WIDTH OF THE RAMP OR STAIR AND AT WHAT
 FACTOR. 2014 FBC-B 1005.3.1 & 1005.3.2.
  
 6B) SHEET LS 1 AND A.3 SHOW A LOBBY BUT NO INFORMATION
 IS GIVEN ON THE STAIRS, RAMP HAND RAILS NOR THE
 GUARDRAILS. PLEASE NOTE THE CITY GAVE A ONE TIME USE ON
 A TEMPORARY EVENT PERMIT FOR THESE ITEMS, BUT IT WAS A
 ONE TIME EVENT. UNDER THAT ONE TIME EVENT THERE WERE NO
 LOADS GIVEN.
 2014 FBC-B 1009.7.2 RISER HEIGHT AND TREAD DEPTH.
 1009.3.1.1 MATERIALS
 1010.1 RAMPS SCOPE
 1010.3 SLOPE
 1010.5 VERTICAL RISE
 1010.7 LANDINGS.
 1010.7.4 CHANGE IN DIRECTION
 1010.8 RAMP CONSTRUCTION
 1010.9 HANDRAILS. & SECTION 1012
 1010.11 GUARDS. & SECTION 1013.
 TABLE 1607.1 LIVE LOADS STAIRS AND RAMPS
 1028.2 ASSEMBLY MAIN EXIT.
 1028.3 ASSEMBLY OTHER EXITS.
 2014 FBC-ACCESS. CODE SECTION 405. RAMPS / STAIRS 504.
 216.1. SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216
 AND SHALL COMPLY WITH 703.
 216.9.2 DIRECTIONAL SIGNS.
  
 6C) SHEET A.4 DETAIL A DOES NOT INDICATE WHAT THE
 MATERIALS THIS RAMP IS MADE FROM NOR THE LIVE LOADS FOR
 THE RAMP NOR THE HANDRAIL SYSTEM. 1607.8.1.1
 CONCENTRATED LOAD. HANDRAILS AND GUARDS SHALL ALSO BE
 DESIGNED TO RESIST A CONCENTRATED LOAD OF 200 POUNDS
 (0.89 KN) IN ACCORDANCE WITH SECTION 4.5.1 OF
 ASCE 7.
  
  
 7) SHEET A.5, M1.1 & M5.1 INDICATES 2 NEW ROOF TOP RTU
 UNITS. PLEASE PROVIDE THE STRUCTURAL REINFORCEMENT
 NECESSARY FOR THE NEW OPENINGS IN THE ROOF, POINT
 LOADING OF JOIST REINFORCEMENT, PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR THE ROOF TOP CURBS, AND THE
 ANCHORING SYSTEM FOR BOTH THE CURB TO THE ROOF FRAMING
 AS WELL AS THE RTU UNIT TO THE CURB. FOR ALL ROOF TOP
 EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO
 THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 8) SHEET A.5, M1.1 & M5.1. FBC-B 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE). PERMANENT
 LADDERS INSTALLED TO PROVIDE THE REQUIRED ACCESS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-11-29 Cont ID  
Sent By rlecky Date 2016-11-29 Time 12:45 Rev Time 0.00
Received By rlecky Date 2016-11-29 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-10-20 Cont ID  
Sent By albarran Date 2016-10-20 Time 19:25 Rev Time 0.00
Received By albarran Date 2016-10-20 Time 17:21 Sent To  
Notes
2016-10-20 21:48:022ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 501 FERN STREET 101
 JOB ADDRESS: 501 FERN STREET
 DESCRIPTION: GENERAL BUILDING ALTERATIONS TO EXISTING
 BLDG.
 MASTER PERMIT: 16071099
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE THAT PERMIT #13080450 IS NOW EXPIRED AND
 WITHOUT A FINAL ELECTRICAL INSPECTION. THEREFORE ALL OF
 THE ELECTRICAL WORK SHOWN ON THE DRAWINGS SHALL BE
 CONSIDERED NEW AND SHALL COMPLY WITH THE 2011 EDITION
 OF THE NEC. YOU SHALL REMOVE ALL REFERENCE TO ANY
 EXISTING WORK FROM THE DRAWINGS. FURTHERMORE, PERMIT
 13080450 WAS OBTAINED FOR TENANT AREA C AND NOT TENANT
 A.
 2. ACCORDING TO OUR RECORDS THERE HAVE ONLY BEEN
 SLAB/UNDERGROUND INSPECTIONS ON PERMIT 13080450 AND
 NEVER A FINAL THEREFORE THIS WORK IS CONSIDERED
 NONEXISTENT.
 3. REGARDLESS OF HAVING HAD PRIOR INSPECTIONS OR NOT,
 THE WIRING METHODS REQUIRED FOR THIS TYPE OF OCCUPANCY
 DIFFER GREATLY TO THOSE OF A WAREHOUSE OR STORAGE
 FACILITY OR EVEN AN EMPTY SHELL. BECAUSE THESE PREMISES
 WERE NOT DESIGNED AS ASSEMBLY AT THAT TIME, THOSE
 METHODS WERE NOT LOOKED FOR IN PLAN REVIEW.
  
 UNTIL WE ESTABLISH THE ABOVE, WE CAN?T PROCEED WITH
 THIS REVIEW, I WILL CONTINUE AND RESPONSE TO THE
 REMAINDER OF THE COMMENTS.
  
 4. NEC 518.4: A NOTE WILL BE PLACED ON THE RESUBMITTAL
 REMINDING THE INSPECTORS TO LOOK FOR ANY PVC CONDUIT
 WITHIN THE PREMISES.
 5. NEC 215.5: PROVIDE A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INDICATING THE TYPE OF RACEWAYS BEING USED FOR
 THE FEEDERS OF THE TWO ELECTRIC PANELS DESCRIBED. PER
 NEC 518.4, PVC IS PROHIBITED IN ANY ASSEMBLY OCCUPANCY
 UNLESS ENCASED IN 2? OF CONCRETE. YOU SHALL PROVIDE AS
 PART OF THIS RISER SITE SPECIFIC LOAD CALCS TO INCLUDE
 THE LOAD FOR THE 4 INSTANT WATER HEATERS. REVISE YOUR
 CALCS AS SHOWN THE DEMAND LOAD FROM YOUR PANEL SCHEDULE
 IS GREATER THAN MENTIONED AND THEREFORE THE FEEDER AND
 OCP FOR THE PANEL WILL NEED TO BE A 400 AMP BREAKER.
 6. NEC 408.4(A): PROVIDE A CIRCUIT DIRECTORY FOR EACH
 OF THE TWO PANELS. ACCORDING TO THE SUBMITTED DIRECTORY
 THERE IS A SINGLE CIRCUIT FOR THE AREA LIGHTING. THOUGH
 THE PLANS SHOW TWO PANELS AND YOU CLAIM TO ONLY HAVE
 ONE. THAT WOULD BE IRRELEVANT AS ALL WORK WILL BE
 CONSIDERED NEW. FROM OUR PERSPECTIVE YOU CAN?T RELOCATE
 WHAT IS NOT THERE.
 7. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY. IN YOUR RESPONSE YOU SAY THAT
 THE WINDOW IS NOT A SHOW WINDOW. THE OCCUPANCY ITSELF
 IS AN EXHIBIT HALL AND THIS IS NOT A SHOW WINDOW? SHOW
 WINDOW OUTLETS SHALL BE INSTALLED AND ADDED TO THE LOAD
 CALCS AS PER NEC 220.14(G).
 8. NEC 210.63: HVAC EQUIPMENT SERVICE OUTLETS. A 125
 VOLT, SINGLE?PHASE, 15 OR 20?AMPERE?RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. THIS
 INCLUDES THE RTU UNITS ON THE ROOF. I SEE YOU CORRECTED
 THIS ON THE PLANS.
 9. NEC 422.52: ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND?FAULT
 CIRCUIT INTERRUPTER PROTECTION (GFI). I SEE YOU
 CORRECTED THIS ON THE PLANS.
 10. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. NONE OF THE THREE DOORS COMPLY. THIS
 INCLUDES ALL FOUR DOORS TO THE OUTSIDE. THE ONE OUTLET
 PLACED ON THE PLANS IS NOT WHAT IS REQUIRED. YOU SHALL
 INSTALL A DEDICATED SIGN OUTLET AT EVERY DOOR. THIS HAS
 TO BE CLOSE TO THE DOOR.
 11. NEC 700.12 (F) (4) ? EMERGENCY LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT. AS CLEARLY STATED HEREIN, YOU MUST
 HAVE A MINIMUM OF THREE LIGHTING CIRCUITS FOR THE ONE
 AREA BEFORE YOU CAN USE A DEDICATED EMERGENCY LIGHTING
 CIRCUIT, OTHERWISE THEY SHALL BE CONNECTED TO THE
 LIGHTING CIRCUIT WITH THE AREA THEY OCCUPY. CORRECT
 THIS ACCORDINGLY.
 12. FBC?EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE.
 THE TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED
 ACCORDING TO THE APPLICABLE TABLES AS INDICATED IN THIS
 SECTION. WITHOUT A FIXTURE SCHEDULE THERE IS NO WAY TO
 VERIFY ALLOWANCE. THOUGH YOU MENTION HI-BAY FIXTURES,
 REMOVE ANY REFERENCE TO EXISTING AS MENTIONED
 PREVIOUSLY. PROVIDE A FIXTURE SCHEDULE AS REQUIRED.
 13. FBC?E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 FOR THE VARIOUS AREAS PER THIS CODE SECTION. THE NOTE
 ON THE PLANS INDICATES THAT WALL SWITCHES WILL HAVE
 OCCUPANCY SENSORS. I SEE YOU CORRECTED THIS ON THE
 PLANS.
 14. FBC?EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 FURTHER LOOKING AT THE PLANS THERE DOES NOT APPEAR TO
 BE A DAYLIGHT ZONE AFFECTED AREA.
 15. FBC?E 405.7.1: AT THE LEAST 50% OF ALL 125?VOLT,
 15? AND 20?AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1). THIS WOULD NOT APPLY TO YOUR SITUATION.
 16. FIRE ALARM IS REQUIRED UNDER SEPARATE PERMIT AND
 SUBMITTAL
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-06 Cont ID  
Sent By albarran Date 2016-09-06 Time 17:44 Rev Time 0.00
Received By albarran Date 2016-09-06 Time 15:15 Sent To  
Notes
2016-09-06 17:45:35ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 501 FERN STREET 101
 JOB ADDRESS: 501 FERN STREET
 DESCRIPTION: GENERAL BUILDING ALTERATIONS TO EXISTING
 BLDG.
 MASTER PERMIT: 16071099
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE THAT PERMIT #13080450 IS NOW EXPIRED AND
 WITHOUT A FINAL ELECTRICAL INSPECTION. THIS PERMIT WILL
 HAVE TO BE REOPENED FOR FINAL INSPECTIONS, OR THE
 ENTIRE SCOPE OF WORK IS INCLUDED IN THIS PERMIT. THAT
 DECISION WILL BE UP TO THE BUILDING OFFICIAL.
 2. ACCORDING TO OUR RECORDS THERE HAVE ONLY BEEN
 SLAB/UNDERGROUND INSPECTIONS FOR THIS PERMIT.
 3. THOUGH NO ROUGH ELECTRICAL INSPECTIONS WERE
 PERFORMED OR RECORDED, THE INITIAL OCCUPANCY WAS NOT
 INTENDED TO BE FOR ASSEMBLY; THEREFORE MINIMUM
 ELECTRICAL REQUIREMENTS FOR THIS TYPE OF OCCUPANCY WERE
 NOT LOOKED FOR IN PLAN REVIEWS.
 4. NEC 518.4: A NOTE WILL BE PLACED ON THE RESUBMITTAL
 REMINDING THE INSPECTORS TO LOOK FOR ANY PVC CONDUIT
 WITHIN THE PREMISES.
 5. NEC 215.5: PROVIDE A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INDICATING THE TYPE OF RACEWAYS BEING USED FOR
 THE FEEDERS OF THE TWO ELECTRIC PANELS DESCRIBED. PER
 NEC 518.4, PVC IS PROHIBITED IN ANY ASSEMBLY OCCUPANCY
 UNLESS ENCASED IN 2? OF CONCRETE. YOU SHALL PROVIDE AS
 PART OF THIS RISER SITE SPECIFIC LOAD CALCS TO INCLUDE
 THE LOAD FOR THE 4 INSTANT WATER HEATERS.
 6. NEC 408.4(A): PROVIDE A CIRCUIT DIRECTORY FOR EACH
 OF THE TWO PANELS. ACCORDING TO THE SUBMITTED DIRECTORY
 THERE IS A SINGLE CIRCUIT FOR THE AREA LIGHTING.
 7. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY.
 8. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLETS. A 125
 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. THIS
 INCLUDES THE RTU UNITS ON THE ROOF.
 9. NEC 422.52 ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT
 CIRCUIT ?INTERRUPTER PROTECTION (GFI).
 10. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. NONE OF THE THREE DOORS COMPLY. THIS
 INCLUDES ALL FOUR DOORS TO THE OUTSIDE.
 11. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
 12. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE.
 THE TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED
 ACCORDING TO THE APPLICABLE TABLES AS INDICATED IN THIS
 SECTION.
 13. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 FOR THE VARIOUS AREAS PER THIS CODE SECTION.
 14. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 15. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT,
 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1).
 16. FIRE ALARM IS REQUIRED UNDER SEPARATE PERMIT AND
 SUBMITTAL
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By albarran Date 2016-08-01 Time 13:25 Rev Time 0.00
Received By albarran Date 2016-08-01 Time 12:42 Sent To  
Notes
2016-08-01 13:39:27ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: CITY PLACE TENANT BUILD OUT
 JOB ADDRESS: 501 FERN ST., SUITE 102
 DESCRIPTION: REMODEL/INTERIOR BUILD OUT
 MAST. PERMIT: 16071099
 REVISION:
  
  
 1. PER A NOTE ON THE APPROVED PLANS, THE SCOPE OF THIS
 SUBMITTAL EXCLUDES ELECTRICAL WORK. PER THE NOTE ALL
 ELECTRICAL WORK IS/WAS PERFORMED UNDER A SEPARATE
 PERMIT. YOU SHALL INCLUDE THE PERMIT NUMBER YOU ARE
 REFERRING TO AS I LOOKED IN OUR SYSTEM AND WAS UNABLE
 TO LOCATE AN ELECTRICAL PERMIT FOR THE LOCATION IN
 QUESTION.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-10-21 Cont ID  
Sent By wjolin Date 2016-10-21 Time 10:28 Rev Time 0.00
Received By wjolin Date 2016-10-21 Time 09:25 Sent To  
Notes
2016-10-21 10:06:09501 FERN STREET #101
 PERMIT #16071099
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A TITLE ON EACH SHEET FOR THE SIX OWNER
 DESIGNED SEATING LAYOUTS. EXAMPLE: SEATING OPTION 1,
 SEATION OPTION 2, ETC. OR SIMILAR.
  
 THE ROWS OF CHAIRS WILL NEED TO BE FASTENED TOGETHER
 FOR THE LAST SEATING PLAN (20 CHAIRS PER ROW; 15 ROWS):
 PER NFPA 101 SECTION 12.7.9.1.1 SEATS IN ASSEMBLY
 OCCUPANCIES ACCOMMODATING MORE THAN 200 PERSONS SHALL
 BE SECURELY FASTENED TO THE FLOOR, EXCEPT WHERE
 FASTENED TOGETHER IN GROUPS OF NOT LESS THAN THREE.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE FIRE ALARM
 AND FIRE SPRINKLER DESIGN CHANGES NEEDED TO PROTECT THE
 SPACE.
  
 NOTE: FOR EACH EVENT, A SPECIAL EVENT PERMIT WILL BE
 NEEDED SHOWING THE EVENT TYPE, EVENT DATES, FURNITURE
 LAYOUT, # OF OCCUPANTS, INTERIOR FINISH MATERIALS,
 CROWD MANAGERS, ETC. A PLAN REVIEW AND FIRE INSPECTION
 WILL BE PERFORMED AT ADDITIONAL CHARGES FOR EACH EVENT
 ENSURING THE SAFETY OF THE EVENTS. PER NFPA 101 SECTION
 12.7.6.1 ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A
 MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER
 SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEEDS 250,
 ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER
 SUPERVISORS SHALL BE PROVIDED AT A RATIO OF ONE CROWD
 MANAGER OR CROWD MANAGER SUPERVISOR FOR EVERY 250
 OCCUPANTS. THE CROWD MANAGER SHALL RECEIVE APPROVED
 TRAINING IN CROWD MANAGEMENT TECHNIQUES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-08-31 Cont ID  
Sent By wjolin Date 2016-08-31 Time 13:16 Rev Time 0.00
Received By wjolin Date 2016-08-31 Time 13:00 Sent To  
Notes
2016-08-31 13:16:55501 FERN STREET #101
 PERMIT #16071099
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: SHEET A.1 INDICATES AN INCORRECT
 OCCUPANT LOAD FACTOR OF 30 SQUARE FEET PER PERSON.
 REFER TO NFPA 101 TABLE 7.3.1.2 FOR CORRECT LOAD
 FACTORS. THE CALCULATED OCCUPANT LOAD AFFECTS THE
 REMAININGL REVIEW COMMENTS.
 REPEAT COMMENT: THIS TENANT SPACE WILL NEED TO BE
 DESIGNED FOR THE GREATEST OCCUPANT LOAD POSSIBLE BASED
 UPON INTENDED USE. A REDUCTION IN OCCUPANT LOAD FOR THE
 SAKE OF DESIGNING THE LIFE SAFETY SYSTEMS (MEANS OF
 EGRESS, FIRE ALARM, FIRE SPRINKLER, ETC. ) IS GENERALLY
 NOT ACCEPTED. PER NFPA 101 SECTION 12.1.7.1. THE
 OCCUPANT LOAD, IN NUMBER OF PERSONS FOR WHOM MEANS OF
 EGRESS AND OTHER PROVISIONS ARE REQUIRED, SHALL BE
 DETERMINED ON THE BASIS OF THE OCCUPANT LOAD FACTORS OF
 TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE
 SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER. THE PLANS CURRENTLY DO NOT INDICATE ANY
 TABLES OR CHAIRS TO JUSTIFY AN OCCUPANT LOAD FACTOR OF
 15 SQ.FT. PER PERSON OR GREATER.
  
 REPEAT COMMENTS:
 THE MAIN ENTRANCE STAIR AND DOORS DO NOT APPEAR WIDE
 ENOUGH TO ACCOMODATE THE MAXIMUM POTENTIAL OCCUPANT
 LOAD AS CALCULATED IN THE PREVIOUS COMMENT. PER NFPA
 101 SECTION12.2.3.6.4 ACCESS TO THE MAIN ENTRANCE/EXIT
 SHALL BE AS FOLLOWS:
 (1) EACH LEVEL OF THE ASSEMBLY OCCUPANCY SHALL HAVE
 ACCESS TO THE MAIN ENTRANCE/EXIT, AND SUCH ACCESS SHALL
 HAVE THE CAPACITY TO ACCOMMODATE TWO-THIRDS OF THE
 OCCUPANT LOAD OF SUCH LEVELS IN THE FOLLOWING ASSEMBLY
 OCCUPANCIES:
 (A) BARS WITH LIVE ENTERTAINMENT
 (B) DANCE HALLS
 (C) DISCOTHEQUES
 (D) NIGHTCLUBS
 (E) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
 (2) IN ASSEMBLY OCCUPANCIES, OTHER THAN THOSE LISTED IN
 12.2.3.6.4(1), EACH LEVEL OF THE ASSEMBLY OCCUPANCY
 SHALL HAVE ACCESS TO THE MAIN ENTRANCE/EXIT, AND SUCH
 ACCESS SHALL HAVE THE CAPACITY TO ACCOMMODATE ONE-HALF
 OF THE OCCUPANT LOAD OF SUCH LEVELS.
  
 INSUFFICIENT SECONDARY EXITS PROVIDED TO ACCOMODATE
 MAXIMUM POTENTIAL OCCUPANT LOAD. PER NFPA 101 SECTION
 12.2.3.7 OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO THE MAIN ENTRANCE/EXIT
 AND SHALL BE PROVIDED WITH ADDITIONAL EXITS OF A WIDTH
 TO ACCOMMODATE NOT LESS THAN ONE-HALF OF THE TOTAL
 OCCUPANT LOAD SERVED BY THAT LEVEL.
  
 THE CURRENT FIRE ALARM SYSTEM FEATURES HORN-STROBE
 NOTIFICATION APPLIANCES AND THERE ARE AN INSUFFICIENT
 NUMBER OF DEVICES. ONCE THE ASSEMBLY OCCUPANCY EXCEEDS
 300 PERSONS, THE FIRE ALARM SYSTEM NEEDS TO BE UPGRADED
 TO INCLUDE VOICE EVACUATION CAPABILITIES WITH
 SPEAKER-STROBE NOTIFICATION DEVICES PER NFPA 101
 SECTION 12.3.4.3.3.
  
 INSUFFICIENT EMERGENCY LIGHTING EXISTS IN THIS TENANT
 SPACE. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR EACH EVENT, A SPECIAL EVENT PERMIT WILL BE NEEDED
 SHOWING THE EVENT TYPE, EVENT DATES, FURNITURE LAYOUT,
 # OF OCCUPANTS, INTERIOR FINISH MATERIALS, CROWD
 MANAGERS, ETC. A PLAN REVIEW AND FIRE INSPECTION WILL
 BE PERFORMED AT ADDITIONAL CHARGES FOR EACH EVENT
 ENSURING THE SAFETY OF THE EVENTS. PER NFPA 101 SECTION
 12.7.6.1 ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A
 MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER
 SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEEDS 250,
 ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER
 SUPERVISORS SHALL BE PROVIDED AT A RATIO OF ONE CROWD
 MANAGER OR CROWD MANAGER SUPERVISOR FOR EVERY 250
 OCCUPANTS. THE CROWD MANAGER SHALL RECEIVE APPROVED
 TRAINING IN CROWD MANAGEMENT TECHNIQUES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By wjolin Date 2016-08-05 Time 15:13 Rev Time 0.00
Received By wjolin Date 2016-08-05 Time 13:46 Sent To  
Notes
2016-08-05 14:18:17501 FERN STREET #101
 PERMIT #16071099
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS TENANT SPACE WILL NEED TO BE DESIGNED FOR THE
 GREATEST OCCUPANT LOAD POSSIBLE BASED UPON INTENDED
 USE. A REDUCTION IN OCCUPANT LOAD FOR THE SAKE OF
 DESIGNING THE LIFE SAFETY SYSTEMS (MEANS OF EGRESS,
 FIRE ALARM, FIRE SPRINKLER, ETC. ) IS GENERALLY NOT
 ACCEPTED. PER NFPA 101 SECTION 12.1.7.1. THE OCCUPANT
 LOAD, IN NUMBER OF PERSONS FOR WHOM MEANS OF EGRESS AND
 OTHER PROVISIONS ARE REQUIRED, SHALL BE DETERMINED ON
 THE BASIS OF THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2
 THAT ARE CHARACTERISTIC OF THE USE OF THE SPACE OR
 SHALL BE DETERMINED AS THE MAXIMUM PROBABLE POPULATION
 OF THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
 THE PLANS CURRENTLY DO NOT INDICATE ANY TABLES OR
 CHAIRS TO JUSTIFY AN OCCUPANT LOAD FACTOR OF 15 SQ.FT.
 PER PERSON OR GREATER.
  
 THE MAIN ENTRANCE STAIR AND DOORS DO NOT APPEAR WIDE
 ENOUGH TO ACCOMODATE THE MAXIMUM POTENTIAL OCCUPANT
 LOAD AS CALCULATED IN THE PREVIOUS COMMENT. PER NFPA
 101 SECTION12.2.3.6.4 ACCESS TO THE MAIN ENTRANCE/EXIT
 SHALL BE AS FOLLOWS:
 (1) EACH LEVEL OF THE ASSEMBLY OCCUPANCY SHALL HAVE
 ACCESS TO THE MAIN ENTRANCE/EXIT, AND SUCH ACCESS SHALL
 HAVE THE CAPACITY TO ACCOMMODATE TWO-THIRDS OF THE
 OCCUPANT LOAD OF SUCH LEVELS IN THE FOLLOWING ASSEMBLY
 OCCUPANCIES:
 (A) BARS WITH LIVE ENTERTAINMENT
 (B) DANCE HALLS
 (C) DISCOTHEQUES
 (D) NIGHTCLUBS
 (E) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
 (2) IN ASSEMBLY OCCUPANCIES, OTHER THAN THOSE LISTED IN
 12.2.3.6.4(1), EACH LEVEL OF THE ASSEMBLY OCCUPANCY
 SHALL HAVE ACCESS TO THE MAIN ENTRANCE/EXIT, AND SUCH
 ACCESS SHALL HAVE THE CAPACITY TO ACCOMMODATE ONE-HALF
 OF THE OCCUPANT LOAD OF SUCH LEVELS.
  
 INSUFFICIENT SECONDARY EXITS PROVIDED TO ACCOMODATE
 MAXIMUM POTENTIAL OCCUPANT LOAD. PER NFPA 101 SECTION
 12.2.3.7 OTHER EXITS. EACH LEVEL OF AN ASSEMBLY
 OCCUPANCY SHALL HAVE ACCESS TO THE MAIN ENTRANCE/EXIT
 AND SHALL BE PROVIDED WITH ADDITIONAL EXITS OF A WIDTH
 TO ACCOMMODATE NOT LESS THAN ONE-HALF OF THE TOTAL
 OCCUPANT LOAD SERVED BY THAT LEVEL.
  
 THE CURRENT FIRE ALARM SYSTEM FEATURES HORN-STROBE
 NOTIFICATION APPLIANCES AND THERE ARE AN INSUFFICIENT
 NUMBER OF DEVICES. ONCE THE ASSEMBLY OCCUPANCY EXCEEDS
 300 PERSONS, THE FIRE ALARM SYSTEM NEEDS TO BE UPGRADED
 TO INCLUDE VOICE EVACUATION CAPABILITIES WITH
 SPEAKER-STROBE NOTIFICATION DEVICES PER NFPA 101
 SECTION 12.3.4.3.3.
  
 PER NFPA 101 SECTION 12.3.3.3 INTERIOR WALL AND CEILING
 FINISH MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL
 ASSEMBLY AREAS HAVING OCCUPANT LOADS OF MORE THAN 300.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE STAIR, RAMP, HANDRAIL AND GUARDRAIL DETAILS.
  
 INSUFFICIENT EMERGENCY LIGHTING EXISTS IN THIS TENANT
 SPACE. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 PER NFPA 1 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 FOR EACH EVENT, A SPECIAL EVENT PERMIT WILL BE NEEDED
 SHOWING THE EVENT TYPE, EVENT DATES, FURNITURE LAYOUT,
 # OF OCCUPANTS, INTERIOR FINISH MATERIALS, CROWD
 MANAGERS, ETC. A PLAN REVIEW AND FIRE INSPECTION WILL
 BE PERFORMED AT ADDITIONAL CHARGES FOR EACH EVENT
 ENSURING THE SAFETY OF THE EVENTS. PER NFPA 101 SECTION
 12.7.6.1 ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A
 MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER
 SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEEDS 250,
 ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER
 SUPERVISORS SHALL BE PROVIDED AT A RATIO OF ONE CROWD
 MANAGER OR CROWD MANAGER SUPERVISOR FOR EVERY 250
 OCCUPANTS. THE CROWD MANAGER SHALL RECEIVE APPROVED
 TRAINING IN CROWD MANAGEMENT TECHNIQUES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-02 Cont ID  
Sent By gjohnson Date 2016-12-01 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2016-11-16 Time 11:27 Sent To  
Notes
2016-11-17 11:27:22B25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2016-10-22 Cont ID  
Sent By jwitmer Date 2016-10-22 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2016-09-28 Time 10:40 Sent To  
Notes
2016-09-30 10:40:36B25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-10 Cont ID  
Sent By tklarge Date 2016-09-10 Time 12:19 Rev Time 0.00
Received By tklarge Date 2016-08-29 Time 11:19 Sent To  
Notes
2016-08-30 11:20:03B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By gjohnson Date 2016-08-18 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2016-07-26 Time 11:28 Sent To  
Notes
2016-07-27 11:29:05B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By jwitmer Date 2016-08-31 Time 07:14 Rev Time 0.00
Received By jwitmer Date 2016-08-31 Time 07:02 Sent To  
Notes
2016-08-31 07:14:36P.B.C. IMPACT FEES
 MU-2016-21795
 A3 OCCUPANCY
 $24.82

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 15:35 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2016-08-04 15:34:44BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-11-21 Time 09:37 Rev Time 0.00
Received By ccole Date 2016-11-21 Time 09:38 Sent To FIRE
Notes
2016-11-21 09:49:47MECHANICAL PROVISO
 PERMIT #16071099
 11/21/16
  
 1) ACCESS TO ROOF MOUNTED EQUIPMENT TO BE IN COMPLIANCE
 WITH SECTION 306.5 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-12 Cont ID  
Sent By ccole Date 2016-10-12 Time 16:49 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 16:49 Sent To  
Notes
2016-10-12 17:10:523RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16071099
 10/12/16
  
 1) REFER TO SECTION 306.5 AND PROVIDE AN INTERIOR OR
 EXTERIOR ACCESS TO THE RTU'S THAT DOES NOT INVOLVE THE
 USE OF PORTABLE LADDERS. THE NOTES ON SHEET A.3
 INDICATE NON-COMPLIANCE: A) THERE IS NO WAY TO ACCESS
 THE ATTIC HATCH IN B-1 WITHOUT A PORTABLE LADDER. B)
 THE MEANS OF ACCESS VIA THE ADJOINING TENANT OCCUPANCY
 IS RESTRICTIVE BECAUSE THE BUSINESS MAY NOT BE OPEN
 WHEN ACCESS IS NEEDED.
  
 2) THE NEW CONDITIONED WAREHOUSE IS LABELED "EXHIBIT
 HALL" ON SHEET M1.1, BUT ON ALL THE ARCHITECTURAL
 SHEETS EXCEPT A1, IT IS LABELED "BANQUET HALL". AS
 PREVIOUSLY NOTED IN THE PREVIOUS REVIEW, THE
 VENTILATION RATE MUST BE INCREASED IF DINING HALL IS TO
 BE THE USE OF THE SPACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 11:43 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 11:43 Sent To  
Notes
2016-09-07 11:49:222ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071099
 9/7/16
  
 1) PLEASE PROVIDE THE SIZES OF THE RTU RETURN AIR DUCTS
 AND GRILLS.
  
 2) CORRIDOR 104 SHALL NOT BE USED TO CONVEY RETURN AIR
 TO THE RTU PER SECTION 601.2. PLEASE PROVIDE AN
 ALTERNATE METHOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By ccole Date 2016-08-02 Time 16:18 Rev Time 0.00
Received By ccole Date 2016-08-02 Time 16:17 Sent To  
Notes
2016-08-02 17:07:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16071099
 8/2/16
  
  
 1) ENERGYGAUGE/ASHRAE 90.1 COMPLIANCE SUBMITTAL: PLEASE
 COMPLETE THE CHECKLIST ON PAGE 1 AND SUBMIT THE
 MANDATORY COMPLIANCE CHECKLIST WITH ALL APPLICABLE
 BOXES CHECKED OFF. PLEASE NOTE THAT ALL CONSTRUCT DATA
 LISTED IN THE INPUT DATA REPORT SHALL BE SHOWN ON THE
 ARCHITECTURAL PLANS.
  
 2) SHEETS A.1, A.2, & M0.2: PLEASE REFER TO SECTION
 303.3 FBC-14 BUILDING AND SHEET A.1. THE ARCHITECT OF
 RECORD HAS CLASSIFIED THE OCCUPANCY AS AN A-2 WHICH IS
 ASSOCIATED WITH RESTAURANT AND DINING FACILITIES,
 BANQUET HALLS, CASINOS ETC. SEE TABLE 403.3 AND REVISE
 THE OUTDOOR AIR CALCULATIONS FOR THE EVENT SPACE (ROOM
 102) WITH THE RATES SPECIFIED FOR DINING ROOMS, AND FOR
 THE STAGING SPACE IN TABLE 403.3. WITH THE RATES
 SPECIFIED FOR KITCHENS. PLEASE NOTE THAT EXHAUST
 VENTILATION IS REQUIRED FOR THE KITCHENS AT A RATE OF
 0.70 CFM PER SQ. FT.
  
 3) M1.1: IDENTIFY THE ROOMS AND SPACES ON THE
 MECHANICAL PLAN.
  
 4) PROVIDE COMPLETE KITCHEN PLANS AND AN EQUIPMENT
 SCHEDULE. PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION
 SYSTEMS.
  
 5) DEMAND CONTROLLED VENTILATION IS REQUIRED FOR THE
 EVENT SPACE PER SECTION C403.2.5.1. INDICATE ON THE
 PLAN HOW COMPLIANCE WILL BE MET AND PROVIDE DETAILS.
  
 6) M5.1: THE THYBAR CURB NOA #12-0828.02 SPECIFIED ON
 THE PLAN EXPIRED ON 2/10/16. PLEASE CORRECT THE PLAN
 AND SUBMIT A VALID NOA WITH APPROVAL SIGNATURE BY THE
 EOR. PROVIDE COMPLETE ENGINEERING FOR INSTALLATION OF
 THE RTU'S INCLUDING ANCHORING DETAILS FOR MPOUNTING THE
 CURBS TO THE ROOF STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-11-30 Cont ID  
Sent By gjohnson Date 2016-11-28 Time 15:55 Rev Time 0.00
Received By gjohnson Date 2016-11-28 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-10-22 Cont ID  
Sent By tklarge Date 2016-10-22 Time 06:43 Rev Time 0.00
Received By tklarge Date 2016-10-22 Time 05:23 Sent To  
Notes
2016-10-22 06:36:511) SHT. A.2 - THE ROOM FINISH SCHEDULE IDENTIFIES THE
 WALL FINISH IN THE MEN'S & WOMEN'S RESTROOMS AND
 JANITOR'S ROOM AS "PAINT." COMPLY WITH 2014 FBC
 SEC.1210.2.1. 1210.2.2.
 2) SHT. A.2 REFERS TO PERMIT #12070659 FOR THE
 INSTALLATION OF THE ROUGH-IN PLUMBING AND SHT. A.1
 REFERS TO PERMIT #12070649. PERMIT #12070649 IS THE
 CORRECT MASTER NUMBER. PERMIT NUMBER 12070659 APPLIES
 TO 211 DYER ROAD AND IS OBVIOUSLY THE WRONG PERMIT
 NUMBER. THE PLUMBING PEMIT NUMBER IS #13080552 AND
 LIMITED PLUMBING INSPECTIONS WERE DONE UNDER THIS
 PERMIT NUMBER AND THIS PLUMBING PERRMIT HAS NEVER
 RECEIVED A FINAL PLUMBING INSPECTION. THE PERMIT SHALL
 BE RENEWED AND ALL REMAINING REQUIRED INSPECTIONS SHALL
 BE SCHEDULED AND COMPLETED. WPB AMENDMENTS TO FBC
 SEC.105.4.1.2. REVISE THE NOTES ON SHTS. A.1 & A.2.
 3) CLARIFY WHAT OPERATIONS/PROCESSES OCCUR IN THE
 "SUPPORT SPACE" SHOWN ON THE PLANS.
 4) SUPPLY A NARRATIVE RESPONSE TO THE PLUMBING COMENTS.
 ONE HAS NOT BEEN PROVIDED FOR THE PREVIOUS PLUMBING
 REVIEWS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-09-10 Cont ID  
Sent By tklarge Date 2016-09-10 Time 12:19 Rev Time 0.00
Received By tklarge Date 2016-09-10 Time 11:01 Sent To  
Notes
2016-09-10 12:12:181) THIS IS NOTED AS A CHANGE OF OCCUPANCY ON THE PLANS.
 INDICATE THE PREVIOUS OCCCUPANCY ON THE PLANS. WPB
 AMEND. TO FBC 107.2.1. COMPLIANCE WITH FPC SEC.403.1.3
 (POTTY PARITY) MAY BE APPLICABLE.
 2) SHT. A.2 - THE ROOM FINISH SCHEDULE IDENTIFIES THE
 WALL FINISH IN THE MEN'S & WOMEN'S RESTROOMS AS
 "PAINT." COMPLY WITH 2014 FBC SEC.1210.2.1. 1210.2.2.
 3) THE PLANS SHOW INSTANT WATER HEATERS UNDER THE
 LAVATORIES.TEMPERED WATER CONTROL SHALL BE IN
 ACCORDANCE WITH 2014 FPC SEC.607.1.2.
 4) THE GRAB BARS SHALL BE MEASURED FROM THE FINISH
 FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC SEC.
 609.4.
 5) WHERE ARE THE TOILET PAPER DISPENSERS FOR THE
 ACCESSIBLE COMPARTMENTS? THE DISPENSERS SHALL COMPLY
 WITH FAC SEC. 604.7.
 6) SUBMIT MANUF. SPECIFICATIONS FOR THE INSTANT WATER
 HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. A.2 REFERS TO PERMIT #16070659. THIS PERMIT
 NUMBER APPLIES TO 211 DYER ROAD AND IS OBVIOUSLY THE
 WRONG PERMIT NUMBER. SUPPLY THE CORRECT PERMIT NUMBER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By gjohnson Date 2016-08-18 Time 13:06 Rev Time 0.00
Received By gjohnson Date 2016-08-18 Time 13:06 Sent To  
Notes
2016-08-18 14:32:021ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAILED SCOPE OF PLUMBING WORK BEING DONE
 UNDER THIS PERMIT IF THERE IS NO PLUMBING WORK BEING
 DONE PUT A NOTE ON THE PLAN STATING THAT. WPB AMEND TO
 FBC 107.2.1
 2. THE CHANGE OF OCCUPANCY REQUIRES COMPLIANCE WITH FBC
 PL TABLE 403.1 IF THIS IS AN A2 WITH A OCCUPANT LOAD OF
 471 IT WILL REQUIRE 6 WATER CLOSETS FOR MEN AND 9 FOR
 WOMEN 4 LAVATORY'S FOR BOTH SEXES . IF THE OCCUPANT
 LOAD IS 225 IT WILL REQUIRE 3 WATER CLOSETS FOR MEN 6
 FOR WOMEN AND 2 LAVATORY'S FOR BOTH SEXES.
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.