| 2016-08-03 16:35:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16071074/ 1 STORY/ R2VERSES I1 |
| | ADD: 1626 OKECHOBEE RD. |
| | CONT: POTTSWORK CONSTRUCTION |
| | TEL: 561-584-2563 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUG. 03/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S-1 LISTS UNDER THE SCOPE OF WORK THIS PROJECT |
| | AS A LEVEL III ALTERATION TO EXISTING 6 UNIT APARTMENTS |
| | (R2 OCCUPANCY GROUP). THE COVER SHEET INDICATES THE |
| | USAGE THE PROGRAM AS COMPREHENSIVE ALCOHOLISM |
| | REHABILITATION PROGRAMS, INC. PLEASE NOTE THIS IS A |
| | CHANGE OF USE WITHIN THE SAME OCCUPANCY GROUP OR |
| | POSSIBLY FROM A R2 TO AN R4 (ALCOHOL & DRUG CENTERS, |
| | ASSISTED LIVING FACILITIES AND OR RESIDENTIAL BOARD AND |
| | CUSTODIAL CARE FACILITIES). |
| | 2014 EXIST. BUILD. CODE 1001.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. PLEASE DECLARE THE END USAGE OF THE STRUCTURE, |
| | THE OCCUPANT LOAD ( BEDS FOR THE TENANTS. A R-4 |
| | CLASSIFICATION SHALL INCLUDE BUILDINGS, STRUCTURES OR |
| | PORTIONS THEREOF FOR MORE THAN FIVE BUT NOT MORE THAN |
| | 16 PERSONS, EXCLUDING STAFF, WHO RESIDE ON A 24-HOUR |
| | BASIS IN A SUPERVISED RESIDENTIAL ENVIRONMENT AND |
| | RECEIVE CUSTODIAL CARE. THE PERSONS RECEIVING CARE ARE |
| | CAPABLE OF SELF-PRESERVATION. PLEASE NOTE IF THE |
| | RECIPIENTS RECEIVING CUSTODIAL CARE ARE NO LONGER |
| | CAPABLE OF SELF- PRESERVATION THEN THE OCCUPANCY |
| | CHANGES TO AN I-2 OCCUPANCY. |
| | |
| | PLEASE NOTE THE BACK UNIT BEING UNDER A SEPARATE PERMIT |
| | DOES NOT MEAN THAT THE AMOUNT OF OCCUPANTS FOR THIS |
| | FACILITY ARE NOT COMBINED!!! SHEET S-11 DOES NOT SHOW |
| | THE USAGE OF THE ROOMS NOR THE AMOUNT OF OCCUPANTS THAT |
| | WILL BE SHARING SLEEPING QUARTERS. PLEASE NOTE THAT |
| | THIS MAY CREATE A CHANGE OF OCCUPANCY FROM THE R2 |
| | APARTMENTS TO A I-1 OCCUPANCY. SEE 2014 FBC-B 308.3 |
| | 308.3 INSTITUTIONAL GROUP I-1. UNDER THE 2012 IBC-B |
| | BASE CODE THE COMMENTARY ALSO USES THE TERMINOLOGY |
| | FACILITY. THE NUMBER OF PEOPLE RECEIVING CARE IN THE |
| | FACILITY. NOTE STATE LICENSING WILL BE FOR THE |
| | FACILITY, THE OCCUPATIONAL LICENSE/ BUSINESS TAX IS |
| | LICENSED FOR THE FACILITY. |
| | |
| | THIS OCCUPANCY SHALL INCLUDE BUILDINGS, STRUCTURES OR |
| | PORTIONS THEREOF FOR MORE THAN 16 PERSONS WHO RESIDE ON |
| | A 24 HOUR BASIS IN A SUPERVISED ENVIRONMENT AND RECEIVE |
| | CUSTODIAL CARE. THE PERSONS RECEIVING CARE ARE CAPABLE |
| | OF SELF PRESERVATION. THIS GROUP SHALL INCLUDE, BUT NOT |
| | BE LIMITED TO, THE FOLLOWING: |
| | ALCOHOL AND DRUG CENTERS, ASSISTED LIVING FACILITIES, |
| | CONGREGATE CARE FACILITIES, CONVALESCENT FACILITIES, |
| | GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL BOARD AND |
| | CUSTODIAL CARE FACILITIES AND OR SOCIAL REHABILITATION |
| | FACILITIES. |
| | |
| | 2) SHEET S-4 & S11 PLEASE SHOW RATED WALLS BETWEEN |
| | SLEEPING ROOMS. 2014 FBC-B 420.2 SEPARATION WALLS. |
| | WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING, |
| | WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING |
| | AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM |
| | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN |
| | ACCORDANCE WITH SECTION 708. |
| | PLEASE NOTE THAT WE ARE REVIEWING THE SLEEPING ROOMS AS |
| | DORMS AS DEFINED UNDER THE FBC-B DORMITORY. A SPACE IN |
| | A BUILDING WHERE GROUP SLEEPING ACCOMMODATIONS ARE |
| | PROVIDED IN ONE ROOM, OR IN A SERIES OF CLOSELY |
| | ASSOCIATED ROOMS, FOR PERSONS NOT MEMBERS OF THE SAME |
| | FAMILY GROUP, UNDER JOINT OCCUPANCY AND SINGLE |
| | MANAGEMENT, AS IN COLLEGE DORMITORIES OR FRATERNITY |
| | HOUSES. |
| | UNDER THE CITY MUNI-CODE ONLY TWO PEOPLE CAN USE A |
| | DWELLING UNIT WHO ARE NOT RELATED SEE THE TERM FAMILY |
| | 18-92. THE TERM FAMILY SHALL NOT INCLUDE THE OCCUPANTS |
| | OF GROUP HOMES, CONGREGATE LIVING FACILITIES OR OTHER |
| | SIMILAR USE WITH SHARED COOKING OR SANITARY FACILITIES. |
| | |
| | 3) PLEASE PROVIDE A LIFE SAFETY PLAN THAT SHOWS, SITE |
| | PLAN, THE FIRE RATING OF SLEEPING ROOMS, THE MEANS OF |
| | EGRESS FOR EACH SLEEPING ROOM TO THE PUBLIC WAY, AN |
| | ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY, |
| | ACCESSIBLE PARKING, COMMON PATH OF TRAVEL, THE SIZE OF |
| | THE EMERGENCY ACCESS WINDOWS (VENT) FOR EACH SLEEPING |
| | ROOM, FIRE RATING OF STAIRS, FIRE RATING OF SLEEPING |
| | ROOM DOORS, EXIT SIGNS, EMERGENCY LIGHTING OF |
| | CORRIDORS, STAIRS. 107.3.5.1.1 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. |
| | |
| | 4) PLANS WILL NEED TO SHOW COMPLIANCE WITH: 2014 FBC-B |
| | 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R OCCUPANCIES |
| | SHALL BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.8. |
| | GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.2.6. QUICK RESPONSE OR RESIDENTIAL |
| | AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE |
| | WITH SECTION 903.3.2. |
| | |
| | |
| | 5) PLANS WILL NEED TO SHOW COMPLIANCE WITH: 2014 FBC-B |
| | 420.5 SMOKE DETECTION AND FIRE ALARM SYSTEMS. |
| | FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE PROVIDED |
| | IN GROUP I-1, R-1 AND R-2 OCCUPANCIES IN ACCORDANCE |
| | WITH SECTIONS 907.2.6, 907.2.8 AND 907.2.9, |
| | RESPECTIVELY. SINGLE-OR MULTIPLE-STATION SMOKE ALARMS |
| | SHALL BE IN ACCORDANCE WITH SECTION 907.2.11. |
| | |
| | 6) 2014 FBC-EXISTING BUILDING CODE 1006.1 ACCESSIBILITY |
| | IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | PLEASE NOTE IF THIS FACILITY IS EITHER A R4 OR AN I1 |
| | OCCUPANCY, IN EITHER CASE THE COMMON AREAS WILL NEED TO |
| | COMPLY WITH THE FLORIDA ACCESSIBILITY CODE AND |
| | DEPENDING ON THE AMOUNT OF UNITS, COMPLY WITH THE |
| | REQUIREMENTS OF 224.2, TABLE 224.2, 224.4 , TABLE |
| | 224.4. |
| | |
| | 7) NONE OF THE PLANS SHOW THE WIND DESIGN CRITERIA NOR |
| | PRESSURES FOR COMPONENTS & CLADDING. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 7.2. RISK CATEGORY. |
| | |
| | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 8) / 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |