Plan Review Details - Permit 16071059
Plan Review Stops For Permit 16071059
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 15:29 Rev Time 0.00
Received By shill Date 2017-08-10 Time 15:29 Sent To  
Notes
2017-08-10 15:30:27A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058
 WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE
 SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE
 PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED)
 DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED
 UNDER 16071058.
  
 K. REGARDING THE STRUCTURAL CALCULATIONS:
  
 PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY.
 PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC
 WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE
 APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I
 CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR
 WHY THEY WOULD BE DONE DIFFERENTLY.
 PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF
 LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS
 UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT.
 PLEASE PROVIDE THE WARNING NOTED.
  
 ***********************
 BUILDING DATA FOR CO / REPORTING
  
 16071059 BLDG 2
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 50957
  
 CONSTRUCTION TYPE: 14-II-A
 UNITS: 45
 FLOORS: 3
 BEDROOMS: 67
 ROOMS: 200
 SQ FT LIVABLE: 50957
 SQ FT FOOTPRINT: 20300
 SQ FT ROOF: 20300
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 289
 PROP USE: APT/AMN/OFS
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 67
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 09:56 Rev Time 0.00
Received By shill Date 2017-08-09 Time 09:56 Sent To  
Notes
2017-08-09 09:56:40SEE BUILDING REVIEW 16071058
  
 ***********************
 BUILDING DATA FOR CO / REPORTING
  
 16071059 BLDG 2
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 50957
  
 CONSTRUCTION TYPE: 14-II-A
 UNITS: 45
 FLOORS: 3
 BEDROOMS: 67
 ROOMS: 200
 SQ FT LIVABLE: 50957
 SQ FT FOOTPRINT: 20300
 SQ FT ROOF: 20300
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 289
 PROP USE: APT/AMN/OFS
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 67
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-07-28 Cont ID  
Sent By shill Date 2017-07-28 Time 10:45 Rev Time 0.00
Received By shill Date 2017-07-28 Time 10:45 Sent To  
Notes
2017-07-28 10:46:28SEE BUILDING REVIEW 16071058
  
 ***********************
 BUILDING DATA FOR CO / REPORTING
  
 16071059 BLDG 2
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 50957
  
 CONSTRUCTION TYPE: 14-II-A
 UNITS: 45
 FLOORS: 3
 BEDROOMS: 67
 ROOMS: 200
 SQ FT LIVABLE: 50957
 SQ FT FOOTPRINT: 20300
 SQ FT ROOF: 20300
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 289
 PROP USE: APT/AMN/OFS
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 67
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-12 Cont ID  
Sent By shill Date 2017-07-12 Time 13:17 Rev Time 0.00
Received By shill Date 2017-07-12 Time 13:17 Sent To  
Notes
2017-07-12 13:17:41SEE BUILDING REVIEW 16071058
  
 ***********************
 BUILDING DATA FOR CO / REPORTING
  
 16071059 BLDG 2
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 50957
  
 CONSTRUCTION TYPE: 14-II-A
 UNITS: 45
 FLOORS: 3
 BEDROOMS: 67
 ROOMS: 200
 SQ FT LIVABLE: 50957
 SQ FT FOOTPRINT: 20300
 SQ FT ROOF: 20300
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 289
 PROP USE: APT/AMN/OFS
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 67
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 11:18 Rev Time 0.00
Received By shill Date 2017-06-24 Time 11:18 Sent To  
Notes
2017-06-24 11:18:59SEE BUILDING REVIEW 16071058
  
 ***********************
 BUILDING DATA FOR CO / REPORTING
  
 16071059 BLDG 2
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 50957
  
 CONSTRUCTION TYPE: 14-II-A
 UNITS: 45
 FLOORS: 3
 BEDROOMS: 67
 ROOMS: 200
 SQ FT LIVABLE: 50957
 SQ FT FOOTPRINT: 20300
 SQ FT ROOF: 20300
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 289
 PROP USE: APT/AMN/OFS
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 67
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-29 Cont ID  
Sent By shill Date 2016-09-29 Time 06:35 Rev Time 0.00
Received By shill Date 2016-09-17 Time 14:08 Sent To  
Notes
2016-09-17 14:13:50SEE BUILDING REVIEW 16071058
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-08-10 Cont ID  
Sent By jpearson Date 2017-08-10 Time 13:28 Rev Time 0.00
Received By jpearson Date 2017-08-10 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By jpearson Date 2017-07-21 Time 07:52 Rev Time 0.00
Received By jpearson Date 2017-07-21 Time 07:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 13:43 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 08:30 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 08:30 Sent To  
Notes
2017-06-16 08:34:11APPROVED WITH EXCEPTION. NEED AIC CALCULATION FOR EACH
 SERVICE PRIOR TO ROUGH INSPECTION TO CONFIRM SIZING OF
 SERVICE EQUIPMENT. NEC 110.9, 110.10
 REVIEWED PER PREVIOUS COMMENTS ONLY WITH ASSISTANCE
 FROM JAKE LEAHY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By vperez Date 2016-08-29 Time 09:40 Rev Time 0.00
Received By vperez Date 2016-08-26 Time 14:06 Sent To  
Notes
2016-08-29 09:41:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS:
 PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED
 EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT
 LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL
 SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE
 PERMIT.
 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY
 STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA.
 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING
 REQUIREMENTS.
 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107.
 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM
 FOR A COMPLETE REVIEW. FBC 107.3.5
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2017-07-18 Cont ID  
Sent By SQ Date 2017-07-18 Time   Rev Time 8.00
Received By squinone Date 2017-07-18 Time   Sent To I
Notes
2017-07-18 14:44:22NO CIVIL SHEETS PROVIDED. PROJECT UNDER REVIEW THROUGH
 ENGINEERING SERVICES.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 11:19 Rev Time 0.00
Received By shill Date 2017-06-24 Time 11:19 Sent To  
Notes
2017-06-24 11:19:18SEE ENGINEERING REVIEW 16071058
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 08:28 Rev Time 0.00
Received By shill Date 2017-05-11 Time 08:28 Sent To  
Notes
2017-05-11 08:28:53ENGINEERING APPROVAL REQUIRED VIA A SEPARATE
 ENGINEERING SUBMITTAL TO THE ENGINEERING DEPARTMENT
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 13:30 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-05 Cont ID  
Sent By wjolin Date 2017-07-05 Time 12:49 Rev Time 0.00
Received By wjolin Date 2017-07-05 Time 12:49 Sent To  
Notes
2017-07-05 12:49:49PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND
 STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 11:55 Rev Time 0.00
Received By wjolin Date 2017-05-31 Time 11:55 Sent To  
Notes
2017-05-31 11:55:07PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND
 STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By wjolin Date 2016-08-18 Time 15:02 Rev Time 0.00
Received By wjolin Date 2016-08-18 Time 15:02 Sent To  
Notes
2016-08-18 15:02:47PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 SHEET WS-1 & WS-2: PROVIDE CHAIN WITH LOCK AND TAMPER
 SWITCHES FOR SUPERVISING THE BACKFLOW PREVENTER IN THE
 OPEN POSITION. PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTIONS.
  
 SHEET WS-2: NO FIRE MAINS OR FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 SHEET PD-2: THE SOUTH ENTRANCE OFF 15TH STREET IS ONLY
 12 FEET WIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE
 DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED
 TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36
 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF
 NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 SHEET LS1.05: THE CLUB ROOM IS AN ASSEMBLY ROOM WITH A
 POSSIBLE OCCUPANT LOAD OF 60 TO140 PERSONS DEPENDING
 UPON THE OCCUPANT LOAD FACTOR USED. DOOR C WILL NEED TO
 HAVE THE SWING REVERSED TO SWING WITH EGRESS. DOORS C
 AND D WILL NEED PANIC HARDWARE IF NOT ALREADY EQUIPPED.
  
 SHEET LS1.05: WHEN OCCUPANTS LEAVE THE EXERCISE ROOM,
 WHAT ROUTE IS BEING UTILIZED FOR THE SECONDARY MEANS OF
 EGRESS? THE PRIMARY MEANS OF EGRESS IS TO THE EAST.
  
 EXIT SIGNAGE: SOME OF THE CORRIDORS HAVE AN
 INSUFFICIENT AMOUNT OF EXIT SIGNS. PER NFPA 101 SECTION
 7.10.1.5.2 NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE
 RATED VIEWING DISTANCE OR 100 FEET, WHICHEVER IS LESS,
 FROM THE NEAREST SIGN.
  
 EMERGENCY LIGHTING: BUILDING 1 APPEARS TO ONLY HAVE
 EMERGENCY LIGHTING IN THE STAIRS AND ELEVATOR LOBBY
 AREAS. PER NFPA 101 SECTION 30.2.9 EMERGENCY LIGHTING
 SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR MORE STORIES
 IN HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS
 EVERY DWELLING UNIT HAS A DIRECT EXIT TO THE OUTSIDE OF
 THE BUILDING AT THE FINISHED GROUND LEVEL.
  
 SHEET FA-1.00A: ALL OF THE CODES AND STANDARDS
 REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 FIRE ALARM ADA: NO VISUAL DEVICES PROVIDED IN THE ADA
 UNITS.
  
 FIRE SPRINKLERS: BUILDINGS 3 AND 4 ARE NOT PROTECTED BY
 AN AUTOMATIC FIRE SPRINKLER SYSTEM. PER NFPA 101
 SECTION 30.3.5.1 ALL NEW APARTMENT BUILDINGS SHALL BE
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 15:40 Rev Time 0.00
Received By shill Date 2017-08-10 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-08-09 Cont ID  
Sent By cpuell Date 2017-08-09 Time 11:47 Rev Time 0.00
Received By cpuell Date 2017-08-04 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-08-04 Cont ID  
Sent By lmarchan Date 2017-08-04 Time 15:20 Rev Time 0.00
Received By lmarchan Date 2017-08-04 Time 14:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-31 Cont ID  
Sent By cpuell Date 2017-07-31 Time 11:45 Rev Time 0.00
Received By cpuell Date 2017-07-19 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-17 Cont ID  
Sent By cpuell Date 2017-07-17 Time 13:46 Rev Time 0.00
Received By cpuell Date 2017-07-03 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 11:19 Rev Time 0.00
Received By shill Date 2017-05-18 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-20 Cont ID  
Sent By cpuell Date 2016-10-20 Time 15:50 Rev Time 0.00
Received By cpuell Date 2016-08-15 Time 10:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By shill Date 2017-08-07 Time 16:50 Rev Time 0.00
Received By shill Date 2017-08-07 Time 16:50 Sent To  
Notes
2017-08-07 16:50:35MU-2017-021132
 125 UNITS
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-17 Cont ID  
Sent By shill Date 2016-09-17 Time 14:10 Rev Time 0.00
Received By shill Date 2016-09-17 Time 14:10 Sent To  
Notes
2016-09-17 14:10:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED
 PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE STAMPED
 AND THE RECEIPT SHOWING THAT THE FEES HAVE BEEN PAID IS
 TO BE PROVIDED.
  
 THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW
 PROCESS, AND MAY BE DONE AFTER ALL OTHER PLAN REVIEWS
 HAVE PASSED.
  
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-07-20 Cont ID  
Sent By ccole Date 2017-07-20 Time 12:49 Rev Time 0.00
Received By ccole Date 2017-07-20 Time 12:49 Sent To  
Notes
2017-07-20 13:03:29MECHANICAL PROVISOS
 PERMIT #16071059
 BUILDING #2
 7/20/2017
  
 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER
 SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING
 CALCULATIONS.
  
 2) THE TRASH ROOM EXHAUST FAN CAPACITY MUST INCREASE TO
 PROVIDE A MINIMUM EXHAUST RATE OF 1.00 CFMS PER SQ. FT
 PER ASHRAE 62.1. PLEASE REVISE THE FAN SCHEDULE AND
 EXHAUST CALCULATIONS ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 17:28 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 17:23 Sent To  
Notes
2017-07-14 17:29:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16071059
 BUILDING #2
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS
 HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I
 AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3
 REMOVED- PLEASE COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071059
 6/8/17
  
 RESULTS: DENIED.
  
 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS
 COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880)
 AND DID NOT ADDRESS COMMENTS #6-11.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN
 THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL
 FORM.
  
 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE
 WITH 1ST REVIEW COMMENTS #1, 6, 7, 8, 9, 10, 12, & 14
 REPRINTED BELOW:
  
 1ST REVIEW COMMENTS.
 8/29/16
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3,
 AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR
 VESTIBULE) SYSTEMS- PLEASE PROVIDE. A) THE CALCULATIONS
 ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B)
 REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1
 SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN
  
 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE
 CORRECT. C) REFER TO SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: A COOLING AND HEATING CALCULATION SHALL
 BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL
 SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER
 SHALL BEAR THE SIGNATURE AND SEAL OF THE EOR. D) THE
 HEATING CAPACITIES OF AHU-1 & 2 (8KW & 10KW IN
  
 THE EQUIPMENT SCHEDULE) ARE EXCEEDING THE CALCULATED
 LOADS AND ARE OVERSIZED- SEE SECTION C403.2.2 FBC-14
 ENERGY CONSERVATION.
  
 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE
 DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN.
  
 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD
 PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE
 A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS.
  
 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE
 THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR
 CALCULATIONS WILL BE REQUIRED.
  
 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST
 VENTILATION CALCULATIONS, AND HOISTWAY VENTING
 CALCULATIONS.
  
 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE
 PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE
 LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE
 AND THICKNESSES OF PIPE INSULATIONS.
  
 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED
 MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00
 IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE
 PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN,
 AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE
 DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP
 DRAWING APPROVAL STAMP AND SIGNATURE ON THE
  
 NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR
 MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE
 PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED
 DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER
 OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS.
  
 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY
 IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN
 INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE
 PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS
 SHOWN IN THE ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-08 Cont ID  
Sent By ccole Date 2017-06-08 Time 11:54 Rev Time 0.00
Received By ccole Date 2017-06-08 Time 11:32 Sent To  
Notes
2017-06-08 11:56:352ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071059
 6/8/17
  
 RESULTS: DENIED.
  
 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS
 COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880)
 AND DID NOT ADDRESS COMMENTS #6-11.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST
 REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY
 CODE.
  
 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN
 THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL
 FORM.
  
 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE
 WITH 1ST REVIEW COMMENTS #1, 6, 7, 8, 9, 10, 12, & 14
 REPRINTED BELOW:
  
 1ST REVIEW COMMENTS.
 8/29/16
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3,
 AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR
 VESTIBULE) SYSTEMS- PLEASE PROVIDE. A) THE CALCULATIONS
 ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B)
 REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1
 SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN
  
 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE
 CORRECT. C) REFER TO SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: A COOLING AND HEATING CALCULATION SHALL
 BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL
 SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER
 SHALL BEAR THE SIGNATURE AND SEAL OF THE EOR. D) THE
 HEATING CAPACITIES OF AHU-1 & 2 (8KW & 10KW IN
  
 THE EQUIPMENT SCHEDULE) ARE EXCEEDING THE CALCULATED
 LOADS AND ARE OVERSIZED- SEE SECTION C403.2.2 FBC-14
 ENERGY CONSERVATION.
  
 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE
 DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN.
  
 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD
 PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE
 A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS.
  
 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE
 THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR
 CALCULATIONS WILL BE REQUIRED.
  
 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST
 VENTILATION CALCULATIONS, AND HOISTWAY VENTING
 CALCULATIONS.
  
 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE
 PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE
 LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE
 AND THICKNESSES OF PIPE INSULATIONS.
  
 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED
 MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00
 IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE
 PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN,
 AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE
 DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP
 DRAWING APPROVAL STAMP AND SIGNATURE ON THE
  
 NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR
 MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE
 PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED
 DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER
 OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS.
  
 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY
 IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN
 INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE
 PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS
 SHOWN IN THE ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By ccole Date 2016-08-29 Time 13:45 Rev Time 0.00
Received By ccole Date 2016-08-29 Time 12:17 Sent To  
Notes
2016-08-29 14:20:311ST REVIEW FBC-2014 MECHANICAL
 ROYAL PALM PLACE- BUILDING- 2
 8/29/16
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3,
 AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR
 VESTIBULE) SYSTEMS- PLEASE PROVIDE. B) THE CALCULATIONS
 ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B)
 REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1
 SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN
  
 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE
 CORRECT. B) REFER TO SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: A COOLING AND HEATING CALCULATION SHALL
 BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL
 SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER
 SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE
 ALSO SECTION
  
 C407.5.2.3 IF SUBMITTING A TOTAL BUILDING PERFORMANCE
 ENERGY COMPLIANCE METHOD. C) THE HEATING CAPACITIES OF
 AHU-1 & 2 (8KW & 10KW IN THE EQUIPMENT SCHEDULE) ARE
 EXCEEDING THE CALCULATED LOADS AND ARE OVERSIZED- SEE
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 2) SHEETS M-2.00, M-2.01, & M-400: THE SPLIT AC
 SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, &
 AHU-B3 SYSTEMS.
  
 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION
 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS
 BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT
 INSTALLATION INSTRUCTIONS.
  
 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS
 C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE
 MATERIALS AND FORMS.
  
 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT
 OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE
 CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES-
 SECTION 401.4
  
 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE
 DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN.
  
 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD
 PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE
 A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS.
  
 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE
 MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE
 THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR
 CALCULATIONS WILL BE REQUIRED.
  
 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST
 VENTILATION CALCULATIONS, AND HOISTWAY VENTING
 CALCULATIONS.
  
 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE
 PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE
 LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE
 AND THICKNESSES OF PIPE INSULATIONS.
  
 11) PROVIDE UL FIRESTOPPING ASSEMBLIES FOR PIPE
 PENETRATIONS.
  
 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED
 MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00
 IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE
 PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN,
 AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE
 DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP
 DRAWING APPROVAL STAMP AND SIGNATURE ON THE
  
 NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR
 MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE
 PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED
 DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER
 OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS.
  
 13) REFER TO SECTION 306.5 AND PROVIDE DETAILS FOR THE
 LADDER THAT IS PROVIDING ACCESS TO THE ROOF HATCH.
  
 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY
 IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN
 INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE
 PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS
 SHOWN IN THE ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 09:49 Rev Time 0.00
Received By tklarge Date 2017-07-20 Time 09:49 Sent To  
Notes
2017-07-20 09:49:36APPROVED UNDER 3RD REVIEW WITH PROVISOS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-14 Cont ID  
Sent By tklarge Date 2017-07-14 Time 15:05 Rev Time 0.00
Received By tklarge Date 2017-07-14 Time 15:03 Sent To  
Notes
2017-07-14 15:03:501) SHT. A6.08 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE CENTERED ON THE FIXTURE PER THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES.IN ADDITION, PROVIDE THE CLEAR
 LENGTH X WIDTH DIMENSIONS OF ALL REQUIRED CLEAR FLOOR
 SPACE DIMENSIONS FOR THE FIXTURES PER THE FHAG.
 2) SHT. A6.10 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IN THE A1 UNIT MODEL. COMPLY
 WITH FHAG.
 3) SHT. A 6.10 - UNITS A1 & B1 ARE SHOWN AS A TYPE "A"
 & "B" DESIGN SPECIFICATION BATHROOM PER THE FHAG. IF
 THESE ARE "UFAS" UNITS, IDENTIFY THEM AS SUCH. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) THE LETTTER FROM THE ARCHITECT REGARDING THE TOILET
 FACILITIES FOR WORKERS IS VAGUE AND IS UNACCEPTABLE.
 REFERENCE IS MADE TO A MAINTENANCE RESTROOM BUT THERE
 IS NO MAINTENANCE RESTROOM IN BUILDING #1.SANITARY
 FACILITIES FOR WORKERS IN THE MAINTENANCE AND TRASH
 AREAS OF BUILDING #1 SHALL BE PROVIDED WITHIN 500 FEET
 OF THESE AREAS. 2014 FBC SEC. 403.3.3
 5) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET VENT
 THE RISER SHOWS THE URINAL IN THE MEN'S RESTROOM ACROSS
 FROM THE EXERCISE ROOM DISCHARGING INTO A VERTICAL WET
 VENT ABOVE THE LAVATORY. THE URINAL IS TO BE INSTALLED
 ON IT'S OWN STACK & VENTED. 2014 FBC SECS.912.1,
 912.1.1. 3RD REQUEST.
 6) SHT. P2.05B - THE MEN'S AND WOMEN'S RESTROOMS ACROSS
 FROM THE EXERCISE ROOM ARE STILL MISLABELED.PLEASE
 REVISE.
 7) THE LOCATION OF SANITARY RISERS S/24 & S/25 LOCATED
 ACROSS FROM THE LAUNDRY ROOM ON SHT. P2.05B ARE
 REVERSED AS TO THE LAYOUT ON SHT. P4.05, REFER TO
 BUILDING # II, UNIT B1.2ND REQUEST.
 8) THE DETAIL FOR THE "PLENUM RATED" WATER METERS ON
 SHEET P5.00 WILL REQUIRE ADDITIONAL DOCUMENTATION FROM
 THE MANUFACTURER CWE. INFORMATION ON THEIR WEBSITE
 INDICATES THEY DO NOT MANUFACTURE "PLENUM RATED WATER
 METERS". THE MATERIAL COMPOSITION OF THE WATER METERS
 SHALL MEET THE SMOKE- DEVELOPED INDEX AND FLAME SPREAD
 RATING REQUIREMENTS OF ASTM E84 OR UL 723. THE FLAME
 SPREAD INDEX SHALL BE NOT MORE THAN 25 AND THE
 SMOKE-DEVELOPED INDEX SHALL NOT BE MORE THAN 50. 2014
 FBC - MECHANICAL SEC. 602.2.1.2ND REQUEST.
 9) SHT. P1.00 - THE ORIENTATION OF BUILDING # II IN
 RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT
 CORRELATE WITH THE ORIENTATION OF BULDING II ON SHT.
 P2.05. CLARIFY. 2ND REQUEST.
  
 NOTE: THE ABOVE CONDITIONS ARE PROVISOS FOR APPROVAL OF
 THESE PLANS FOR PLUMBING PLAN REVIEW. REVISED PLANS
 SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE
 ISSUANCE OF THE PLUMBING PERMIT.
 T.LARGE, CHIEF PLUMBING INSPECTOR
 JULY 14TH, 2017.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By tklarge Date 2017-06-20 Time 06:45 Rev Time 0.00
Received By tklarge Date 2017-06-20 Time 06:14 Sent To  
Notes
2017-06-20 06:15:001) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND -
 THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF
 THE FIRST TOILET PAPER DISPENSER, NOT TO THE CENTERLINE
 OF THE UNIT AS SHOWN. 2014 FBC-ACCESS. SEC.604.7.
 2) SHT.A6.15 - USABLE BATHROOM FIGURES - IDENTIFY ON
 THE PLANS WHICH BATHROOMS ARE DESIGN SPECIFICATION "A"
 OR "B" OF THE FHA. THIS SHEET HAS NOT BEEN REVISED AS
 NOTED IN THE RESPONSE NARRATIVE. 2ND REQUEST.
 3) SUBMIT A SEPARATE LETTER FROM THE DESIGN
 PROFESSIONAL OF RECORD STATING THAT SANITARY FACILITIES
 FOR THE MAINTENANCE WORKERS ARE LOCATED WITHIN 500 FEET
 OF THE TRASH ROOMS, MAINTENANCE ROOMS, ETC., PER 2014
 FBC-PLUMBING SEC.403.3.3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR
 SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.
 5) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE
 SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.2014
 FBC-PLUMBING.2ND REQUEST.
 6) ACCESS SHALL BE PROVIDED TO THE WATER SUPPLY VALVES
 FOR THE STACKED WASHERS/DRYERS. I COULD NOT FIND THE
 REVISED NOTE ON THE PLANS. CLARIFY. 2014 FPC
 SEC.606.3.2ND REQUEST
 7) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET
 VENT. 2014 FBC-PLUMBING SEC.912.1, 912.1.1. THE ADDED
 STACK APPEARS TO HAVE A CLEANOUT ON IT BUT NO URINAL.
 CLARIFY.
 8) SHT.P2.05 - THE MEN'S AND WOMENS RESTROOMS ACROSS
 FROM THE EXERCISE ROOM ARE STILL MISLABELED.THE SAME
 ISSUE OCCURS ON SHT. P2.05B AND ON THE ENLARGED PLAN ON
 P2.05B AND ALSO THERE ARE NO PLUMBING FIXTURES SHOWN IN
 THE MEN'S RESTROOM ON SHT. P2.05B.
 9) THE LOCATION OF THE SANITARY RISERS S/24 & S/25 ON
 SHT. P2.05 B ARE REVERSED AS TO THE LAYOUT ON
 SHT.P4.05. BUILDING # II, SEE UNIT B1.
 10) THE LOCATION OF SANITARY RISERS S/24 & S/25 ON
 SHT.SHT. P2.05 A DOES NOT CORRELATE WITH THE LOCATION
 SHOWN ON SHT. P4.05.THE RISERS ARE REVERSED.
 11) SUBMIT A DETAIL FOR THE SUB-WATER METERS IF THEY
 ARE BEING INSTALLED IN THESE BUILDINGS. SHOW THE
 LOCATION OF THE SUB-METERS IF APPLICABLE. MATERIALS
 PLACED WITHIN RETURN AIR PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING
 A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E84 OR UL 723.2014
 FBC-MECHANICAL SEC. 602.2.1.
 12) SHT. P4.06 - A SHUTOFF VALVE IS REQUIRED ON THE 2
 INCH WATER MAIN SUPPLY TO THE AMENITIES/LEASING AREA
 PER 2014 FBC-PLUMBING SEC.606.2.
 13) SHT.P1.00 - THE ORIENTATION OF BUILDING II IN
 RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT
 CORRELATE WITH THE ORIENTATION OF BUILDING II ON SHT.
 P2.05. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-26 Cont ID  
Sent By tklarge Date 2016-09-26 Time 08:55 Rev Time 0.00
Received By tklarge Date 2016-09-26 Time 08:47 Sent To  
Notes
2016-09-26 08:55:15NOTE: NOT ALL OF THESE COMMENTS APPLY TO EACH BUILDING.
  
  
 1) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE
 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014)
 VERSION OF THE FBC. REVISE THE NOTE.
 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE -
 FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN
 ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING
 CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY
 VOLUME.
 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT
 (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE
 DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR
 B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS.
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND
 SEALED AS REQUIRED BY FL. ADMIN. CODE 61G15-23.001.
 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER
 AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF
 THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE
 PLAN/CIVIL DRAWINGS FOR THIS DRAIN.
 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL
 COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE
 OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF
 DRAINING INTO THE GUTTERS.
 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND -
 THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF
 THE DISPENSER. FAC SEC. 604.7.
 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE
 FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2,
 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE
 DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH
 THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14.
 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED
 CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS,
 AND APPLIANCES PER REQUIREMENT #7 OF THE FHA
 GUIDELINES.
 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY
 WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B.
 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS,
 ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS
 SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF
 THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3.
 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE
 LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG.
 #2) . CLARIFY.
 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC
 CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR
 THE CATCH BASINS. CLARIFY.
 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES
 NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS
 THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW
 "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1.
 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS
 ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR
 THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB
 AMEND. TO FBC SEC. 107.2.1.
 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN
 WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER
 LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT
 SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING
 /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES
 SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB
 AMEND. TO FBC SEC. 107.2.1.
 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR
 SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.
 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE
 EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4.
 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE
 SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2.
 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE
 LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO
 SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE
 NOTE TO REFER TO CORRECT SHEET.
 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH
 IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS
 INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED.
 CLARIFY.
 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC
 SEC. 107.2.1
 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR
 THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3.
 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 )
 BUT THIS RISER IS NOT ON THE COLLECTION SYSTEM ON
 SHT.P-4.01 - CLARIFY.
 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) -
 THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON
 THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE
 PLAN VIEW ON SHT. P-2.00. CLARIFY.
 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT
 SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY.
 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN
 SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED
 FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PER
 HOUR. 2014 FPC SEC.1106.1.
 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE
 STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2
 & 1106.3.
 32) SHT. P-4.05 - A URINAL IS NOT PERMITTED ON A WET
 VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN
 THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE
 WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP"
 IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC.
 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE
 MISLABELED.
 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT.
 P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05.
 SEE BUILDING #2 - UNIT B1 ( UNIT #115 ).
 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A
 MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2.
 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE
 NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON
 SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF
 THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE
 LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 (
 A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY
 COLLECTION ISOMETRIC ON SHT. P-4.05.
 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED
 S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A).
 SEE UNIT B1 (#100).
 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN
 VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON
 SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 )
 AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS
 THERE IS A RISER S/23 FURTHER UPSTREAM.
 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS
 IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE
 DETAIL PER THE 2014 FPC SEC.405.8.
 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER
 ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH
 DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A
 QUICK CLOSING VALVE. 2014 FPC SEC. 604.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 10:43 Rev Time 0.00
Received By shill Date 2017-08-09 Time 10:43 Sent To  
Notes
2017-08-09 10:43:41ROOF INFORMATION NOT PROVIDED
  
 THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED PRIOR TO INSTALLATION. THIS IS
 TYPICALLY SUBMITTED WITH THE ROOF SUB PERMIT
 APPLICATION.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 13:16 Rev Time 0.00
Received By shill Date 2017-08-10 Time 13:16 Sent To  
Notes
2017-08-10 13:16:57NEW SHEETS VERIFIED, ALL TRADES
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 10:01 Rev Time 0.00
Received By shill Date 2017-08-09 Time 10:01 Sent To  
Notes
2017-08-09 10:01:37PAPER PAGES 6.11, 6.12, 6.13
 NEW SHEETS VERIFIED
 ORIGINAL SOILS VERIFIED
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-07-19 Cont ID  
Sent By shill Date 2017-07-19 Time 07:46 Rev Time 0.00
Received By shill Date 2017-07-19 Time 07:46 Sent To  
Notes
2017-07-19 07:47:23SEE REVIEWS UNDER 16071058
 NEW SHEETS SUBMITTED REVIEW CYCLE #4 NEED TO BE
 VERIFIED
  
2017-07-17 09:35:45MECH DIG/SIGS VERIFIED- CCOLE
 7/17/17
2017-07-12 13:18:42SEE REVIEWS UNDER 16071058

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By jpearson Date 2017-06-16 Time 08:34 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 08:34 Sent To  
Notes
2017-06-16 08:34:40ELECTRICAL SHEETS APPROVED.
2017-05-11 08:31:53FOR SIGNATURE REVIEW FOR BUILDING SHEETS, SEE REVIEW
 UNDER 16071058
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status N Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 13:23 Rev Time 0.00
Received By shill Date 2017-08-10 Time 13:23 Sent To  
Notes
2017-08-10 13:24:10APPLICANT ELECTS TO USE CITY INSPECTORS AT THIS TIME
 PER KEN CONRAD, RESIDENT INSPECTOR IS VOLUNTARY FOR
 THIS BUILDING (NOT THRESHOLD)

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 10:29 Rev Time 0.00
Received By shill Date 2017-08-09 Time 10:29 Sent To  
Notes
2017-08-09 10:30:01SEE REVIEWS UNDER 16071058
  
 AS RESIDENT INSPECTOR IS NOW PROPOSED FOR THIS PROJECT,
 REVIEW #2 WAS CHANGED FROM "N" TO "F" TO PREVENT THIS
 PERMIT FROM PRINTING IN ERROR
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2017-08-09 Cont ID  
Sent By shill Date 2017-07-12 Time 13:19 Rev Time 0.00
Received By shill Date 2017-07-12 Time 13:18 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 08:06 Rev Time 0.00
Received By shill Date 2016-10-05 Time 08:06 Sent To  
Notes
2016-10-05 08:06:32SEE REVIEWS UNDER 16071058
  

Review Stop Z ZONING
Rev No 6 Status P Date 2017-08-10 Cont ID  
Sent By jroach Date 2017-08-10 Time 14:35 Rev Time 0.00
Received By jroach Date 2017-08-10 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2017-08-08 Cont ID  
Sent By jroach Date 2017-08-08 Time 13:01 Rev Time 0.00
Received By jroach Date 2017-08-08 Time 13:01 Sent To  
Notes
2017-08-08 13:01:19ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.08.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AT THE PROPOSED CROSSWALK BETWEEN BUILDINGS #2 AND
 #4, THE LANDSCAPE ISLANDS ON BOTH SIDES OF THE SIDEWALK
 SHALL BE EXPANDED TO A MINIMUM OF FIVE (5) FEET IN
 WIDTH. ADDITIONALLY, THE SOUTHERN-MOST PROPOSED GUMBO
 LIMBO SHALL BE PLACED IN THE ISLAND OPPOSITE THE
 PROPOSED TRAFFIC SIGN.
  
 2. PURSUANT TO RESOLUTION NO. 187-16, ALL IMPROVEMENTS
 (INCLUDING UTILITIES AND REQUIRED SCREENING) SHALL BE
 MODIFIED TO COMPLY WITH THE MAXIMUM HEIGHT PERMITTED
 WITHIN THE VISIBILITY TRIANGLE. THIS COMMENT WAS ISSUED
 PREVIOUSLY AND HAS NOT BEEN FULLY ADDRESSED. THE
 TRANSFORMER AND ASSOCIATED SCREENING LOCATED ON THE
 NORTHWEST CORNER OF DIVISION AVENUE AND 15TH STREET
 (L.A. KIRKSEY) SHALL BE RELOCATED TO COMPLY WITH SUCH
 PROVISION.
  
 3. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS
 AND OTHERS CONFLICT WITH LANDSCAPING. THIS COMMENT WAS
 ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED.
  
 4. THE LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A
 SEPARATE LANDSCAPE PERMIT APPLICATION. THIS COMMENT WAS
 ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. PLEASE
 NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THE
 BUILDING PERMIT PLANS DO NOT MATCH THE LATEST SUBMITTAL
 MADE FOR THE MINOR PD AMENDMENT. ALL PLANS NEED TO BE
 CONSISTENT.
  
 5. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
 THIS COMMENT WAS ISSUED PREVIOUSLY AND HAS NOT BEEN
 ADDRESSED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 4 Status F Date 2017-07-31 Cont ID  
Sent By jroach Date 2017-07-31 Time 11:34 Rev Time 0.00
Received By jroach Date 2017-07-31 Time 11:34 Sent To  
Notes
2017-07-31 11:34:18ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.31.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING THAT OCCURS BETWEEN THE HANDICAP
 SPACES (NORTH OF BUILDINGS III AND IV) SHOULD BE
 RECONFIGURED TO PROVIDE AN APPROPRIATE MID-BLOCK
 CROSSING WITH LANDSCAPE ISLANDS, ETC.
  
 6. CIVIL PLANS DO NOT REFLECT THE TWO (2) TREE GRATES
 PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE
 LEASING CENTER.
  
 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 8. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS
 AND OTHER CONFLICT WITH LANDSCAPING.
  
 9. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE
 ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE
 PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE
 SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2017-07-17 Cont ID  
Sent By jroach Date 2017-07-17 Time 13:05 Rev Time 0.00
Received By jroach Date 2017-07-17 Time 13:05 Sent To  
Notes
2017-07-17 13:13:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.17.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY
 ENTRANCE SHOULD BE REMOVED - PEDESTRIANS SHOULD USE THE
 CROSSING AT THE RIGHT-OF-WAY LINE. WHILE THE SIDEWALK
 HAS BEEN RELOCATED, A DIVIDER MEDIAN HAS BEEN REMOVED
 FROM THE ROW OF PARKING; PURSUANT TO THE CITY'S ZLDRS,
 NO MORE THAN 10 CONIGUOUS PARKING SPACES SHALL OCCUR
 WITH OUT THIS INSTALLATION OF A 5 FOOT WIDE LANDSCAPED
 DIVIDER MEDIAN WITH SHADE TREE.
  
 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE
 LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE
 INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO
 EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK.
  
 7. PAVING PLANS DO NOT REFLECT THE TWO (2) TREE GRATES
 PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE
 LEASING CENTER.
  
 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND
 LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM
 THE PROJECT.
  
 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE
 FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR
 EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT
 REFLECTED ON THE ELEVATION.
  
 11. ELEVATION D OF BUILDING II INDICATES THAT THE
 WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM,
 LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH
 ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO
 THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A
 DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE
 FIXED STOREFRONT WINDOWS.
  
 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE
 VARIOUS RETAINING WALLS?
  
 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF
 WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE
 CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE
 ADDRESSED.
  
 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A
 TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A
 LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL
 INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-14 Cont ID  
Sent By jroach Date 2017-06-14 Time 10:18 Rev Time 0.00
Received By jroach Date 2017-06-14 Time 10:18 Sent To  
Notes
2017-06-14 10:18:22ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.14.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY
 ENTRANCE SHOULD BE REMOVED?PEDESTRIANS SHOULD USE THE
 CROSSING AT THE RIGHT-OF-WAY LINE.
  
 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE
 LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE
 INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO
 EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK.
  
 7. SITE PLAN, PAVING PLANS, ETC. DO NOT REFLECT THE TWO
 (2) TREE GRATES PROPOSED ALONG THE ON-STREET PARKING,
 SOUTHWEST OF THE LEASING CENTER.
  
 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND
 LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM
 THE PROJECT.
  
 9. THERE?S A LABEL ON THE SITE PLAN THAT INCORRECTLY
 STATES THAT THERE ARE 143 OFF-STREET PARKING SPACES AND
 22 ON-STREET PARKING SPACES?.THE DATA TABLE INDICATES
 ONLY 156 PARKING SPACES.
  
 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE
 FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR
 EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT
 REFLECTED ON THE ELEVATION.
  
 11. ELEVATION D OF BUILDING II INDICATES THAT THE
 WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM,
 LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH
 ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO
 THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A
 DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE
 FIXED STOREFRONT WINDOWS.
  
 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE
 VARIOUS RETAINING WALLS?
  
 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF
 WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE
 CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE
 ADDRESSED.
  
 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A
 TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A
 LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL
 INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By jroach Date 2016-10-03 Time 14:24 Rev Time 0.00
Received By jroach Date 2016-10-03 Time 14:24 Sent To  
Notes
2016-10-03 14:24:33ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.03.2016
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL ISSUES REGARDING GRADING, BUILDING ELEVATION,
 ETC. THAT HAVE BEEN DISCUSSED IN RECENT MEETINGS SHALL
 BE SATISFACTORILY ADDRESSED.
  
 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 3. AS THE LANDSCAPE PLANS HAVE BEEN REVISED SINCE THE
 ADOPTION OF RESOLUTION NO. 187-16, A MINOR AMENDMENT TO
 THE DUNBAR VILLAGE RPD SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION.
  
 4. ON THE LANDSCAPE PLANS, THERE ARE NUMEROUS CONFLICTS
 BETWEEN PROPOSED LANDSCAPING AND PROPOSED SITE
 LIGHTING. ADDITIONALLY, SOME LIGHT POLES ARE SHOWN IN
 THE MIDDLE OF WALKWAYS, PARKING AREAS, ETC. ENSURE THAT
 ALL PLANS ARE CONSISTENT AND THAT CONFLICTS AND
 INCONSISTENCIES ARE ADDRESSED.
  
 5. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 6. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE
 ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE
 PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE
 SURVEY OF EXISTING TREES TO BE REMOVED.
  
 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 8. ALL PLANS SHALL ACCURATELY REFLECT VISIBILITY
 TRIANGLES IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 94-305(E). THE LOCATION OF ALL IMPROVEMENTS,
 INCLUDING BUT NOT LIMITED TO ABOVE-GROUND UTILITIES AND
 REQUIRED SCREENING, SHALL BE MODIFIED ACCORDINGLY TO
 COMPLY WITH MAXIMUM HEIGHT PERMITTED WITHIN THE
 VISIBILITY TRIANGLE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved