Plan Review Details - Permit 16071059
| Plan Review Stops For Permit 16071059 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2017-08-10 15:30:27 | A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | | | | B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A | | | 902.1 ADVISORY, ABA) PER ARCHITECT | | | | | | C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED PRIOR TO INSTALLATION. | | | | | | D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT | | | APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING | | | WILL BE REVIEWED UNDER A SEPARATE PERMIT. | | | | | | G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: | | | 1 BED 75 UNITS WITH TYPE B BATH | | | 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA | | | | | | H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY | | | CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, | | | REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING | | | DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO | | | COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON | | | SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. | | | | | | I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A | | | DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS | | | REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE | | | CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY | | | BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. | | | | | | J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058 | | | WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE | | | SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE | | | PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED) | | | DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED | | | UNDER 16071058. | | | | | | K. REGARDING THE STRUCTURAL CALCULATIONS: | | | | | | PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY. | | | PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC | | | WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE | | | APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I | | | CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR | | | WHY THEY WOULD BE DONE DIFFERENTLY. | | | PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF | | | LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS | | | UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT. | | | PLEASE PROVIDE THE WARNING NOTED. | | | | | | *********************** | | | BUILDING DATA FOR CO / REPORTING | | | | | | 16071059 BLDG 2 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 50957 | | | | | | CONSTRUCTION TYPE: 14-II-A | | | UNITS: 45 | | | FLOORS: 3 | | | BEDROOMS: 67 | | | ROOMS: 200 | | | SQ FT LIVABLE: 50957 | | | SQ FT FOOTPRINT: 20300 | | | SQ FT ROOF: 20300 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 289 | | | PROP USE: APT/AMN/OFS | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 67 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-09 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2017-08-09 09:56:40 | SEE BUILDING REVIEW 16071058 | | | | | | *********************** | | | BUILDING DATA FOR CO / REPORTING | | | | | | 16071059 BLDG 2 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 50957 | | | | | | CONSTRUCTION TYPE: 14-II-A | | | UNITS: 45 | | | FLOORS: 3 | | | BEDROOMS: 67 | | | ROOMS: 200 | | | SQ FT LIVABLE: 50957 | | | SQ FT FOOTPRINT: 20300 | | | SQ FT ROOF: 20300 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 289 | | | PROP USE: APT/AMN/OFS | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 67 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-28 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-28 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2017-07-28 10:46:28 | SEE BUILDING REVIEW 16071058 | | | | | | *********************** | | | BUILDING DATA FOR CO / REPORTING | | | | | | 16071059 BLDG 2 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 50957 | | | | | | CONSTRUCTION TYPE: 14-II-A | | | UNITS: 45 | | | FLOORS: 3 | | | BEDROOMS: 67 | | | ROOMS: 200 | | | SQ FT LIVABLE: 50957 | | | SQ FT FOOTPRINT: 20300 | | | SQ FT ROOF: 20300 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 289 | | | PROP USE: APT/AMN/OFS | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 67 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-12 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-12 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2017-07-12 13:17:41 | SEE BUILDING REVIEW 16071058 | | | | | | *********************** | | | BUILDING DATA FOR CO / REPORTING | | | | | | 16071059 BLDG 2 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 50957 | | | | | | CONSTRUCTION TYPE: 14-II-A | | | UNITS: 45 | | | FLOORS: 3 | | | BEDROOMS: 67 | | | ROOMS: 200 | | | SQ FT LIVABLE: 50957 | | | SQ FT FOOTPRINT: 20300 | | | SQ FT ROOF: 20300 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 289 | | | PROP USE: APT/AMN/OFS | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 67 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-24 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2017-06-24 11:18:59 | SEE BUILDING REVIEW 16071058 | | | | | | *********************** | | | BUILDING DATA FOR CO / REPORTING | | | | | | 16071059 BLDG 2 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 50957 | | | | | | CONSTRUCTION TYPE: 14-II-A | | | UNITS: 45 | | | FLOORS: 3 | | | BEDROOMS: 67 | | | ROOMS: 200 | | | SQ FT LIVABLE: 50957 | | | SQ FT FOOTPRINT: 20300 | | | SQ FT ROOF: 20300 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 289 | | | PROP USE: APT/AMN/OFS | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 67 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-09-29 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-17 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2016-09-17 14:13:50 | SEE BUILDING REVIEW 16071058 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-10 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-10 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-21 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-21 |
Time |
07:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-12 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-12 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-06-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-16 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-16 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2017-06-16 08:34:11 | APPROVED WITH EXCEPTION. NEED AIC CALCULATION FOR EACH | | | SERVICE PRIOR TO ROUGH INSPECTION TO CONFIRM SIZING OF | | | SERVICE EQUIPMENT. NEC 110.9, 110.10 | | | REVIEWED PER PREVIOUS COMMENTS ONLY WITH ASSISTANCE | | | FROM JAKE LEAHY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-08-29 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-08-26 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2016-08-29 09:41:37 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS: | | | PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED | | | EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT | | | LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV, | | | PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL | | | SUFFICE. | | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP | | | AND COMPLETIONS DOCUMENTS. | | | 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE | | | PERMIT. | | | 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY | | | STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA. | | | 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING | | | REQUIREMENTS. | | | 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION | | | PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC | | | 107. | | | 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM | | | FOR A COMPLETE REVIEW. FBC 107.3.5 | | | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2017-07-18 |
|
|
Cont ID |
|
| Sent By |
SQ |
Date |
2017-07-18 |
Time |
|
Rev Time |
8.00 |
| Received By |
squinone |
Date |
2017-07-18 |
Time |
|
Sent To |
I |
|
| Notes |
| 2017-07-18 14:44:22 | NO CIVIL SHEETS PROVIDED. PROJECT UNDER REVIEW THROUGH | | | ENGINEERING SERVICES. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-24 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2017-06-24 11:19:18 | SEE ENGINEERING REVIEW 16071058 | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-05-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-11 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-11 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2017-05-11 08:28:53 | ENGINEERING APPROVAL REQUIRED VIA A SEPARATE | | | ENGINEERING SUBMITTAL TO THE ENGINEERING DEPARTMENT | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-07-21 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-07-21 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-07-05 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-07-05 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2017-07-05 12:49:49 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND | | | STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-05-31 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-05-31 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2017-05-31 11:55:07 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND | | | STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-08-18 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-08-18 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-08-18 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2016-08-18 15:02:47 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | SHEET WS-1 & WS-2: PROVIDE CHAIN WITH LOCK AND TAMPER | | | SWITCHES FOR SUPERVISING THE BACKFLOW PREVENTER IN THE | | | OPEN POSITION. PROVIDE LOCKING KNOX CAPS ON FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | SHEET WS-2: NO FIRE MAINS OR FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | SHEET PD-2: THE SOUTH ENTRANCE OFF 15TH STREET IS ONLY | | | 12 FEET WIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE | | | DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED | | | TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 | | | TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF | | | NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL | | | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. | | | | | | SHEET LS1.05: THE CLUB ROOM IS AN ASSEMBLY ROOM WITH A | | | POSSIBLE OCCUPANT LOAD OF 60 TO140 PERSONS DEPENDING | | | UPON THE OCCUPANT LOAD FACTOR USED. DOOR C WILL NEED TO | | | HAVE THE SWING REVERSED TO SWING WITH EGRESS. DOORS C | | | AND D WILL NEED PANIC HARDWARE IF NOT ALREADY EQUIPPED. | | | | | | SHEET LS1.05: WHEN OCCUPANTS LEAVE THE EXERCISE ROOM, | | | WHAT ROUTE IS BEING UTILIZED FOR THE SECONDARY MEANS OF | | | EGRESS? THE PRIMARY MEANS OF EGRESS IS TO THE EAST. | | | | | | EXIT SIGNAGE: SOME OF THE CORRIDORS HAVE AN | | | INSUFFICIENT AMOUNT OF EXIT SIGNS. PER NFPA 101 SECTION | | | 7.10.1.5.2 NEW SIGN PLACEMENT SHALL BE SUCH THAT NO | | | POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE | | | RATED VIEWING DISTANCE OR 100 FEET, WHICHEVER IS LESS, | | | FROM THE NEAREST SIGN. | | | | | | EMERGENCY LIGHTING: BUILDING 1 APPEARS TO ONLY HAVE | | | EMERGENCY LIGHTING IN THE STAIRS AND ELEVATOR LOBBY | | | AREAS. PER NFPA 101 SECTION 30.2.9 EMERGENCY LIGHTING | | | SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR MORE STORIES | | | IN HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS | | | EVERY DWELLING UNIT HAS A DIRECT EXIT TO THE OUTSIDE OF | | | THE BUILDING AT THE FINISHED GROUND LEVEL. | | | | | | SHEET FA-1.00A: ALL OF THE CODES AND STANDARDS | | | REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | FIRE ALARM ADA: NO VISUAL DEVICES PROVIDED IN THE ADA | | | UNITS. | | | | | | FIRE SPRINKLERS: BUILDINGS 3 AND 4 ARE NOT PROTECTED BY | | | AN AUTOMATIC FIRE SPRINKLER SYSTEM. PER NFPA 101 | | | SECTION 30.3.5.1 ALL NEW APARTMENT BUILDINGS SHALL BE | | | PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED | | | AUTOMATIC SPRINKLER SYSTEM. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-08-09 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-08-04 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2017-08-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-08-04 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-08-04 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-07-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-31 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-19 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-17 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-03 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-18 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-10-20 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-08-15 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-08-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-07 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-07 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2017-08-07 16:50:35 | MU-2017-021132 | | | 125 UNITS | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-09-17 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-17 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2016-09-17 14:10:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED | | | PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE STAMPED | | | AND THE RECEIPT SHOWING THAT THE FEES HAVE BEEN PAID IS | | | TO BE PROVIDED. | | | | | | THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW | | | PROCESS, AND MAY BE DONE AFTER ALL OTHER PLAN REVIEWS | | | HAVE PASSED. | | | | | | CONTACT 561-233-5025 FOR MORE INFORMATION. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-07-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-20 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-20 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2017-07-20 13:03:29 | MECHANICAL PROVISOS | | | PERMIT #16071059 | | | BUILDING #2 | | | 7/20/2017 | | | | | | 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER | | | SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING | | | CALCULATIONS. | | | | | | 2) THE TRASH ROOM EXHAUST FAN CAPACITY MUST INCREASE TO | | | PROVIDE A MINIMUM EXHAUST RATE OF 1.00 CFMS PER SQ. FT | | | PER ASHRAE 62.1. PLEASE REVISE THE FAN SCHEDULE AND | | | EXHAUST CALCULATIONS ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-14 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-14 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2017-07-14 17:29:03 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071059 | | | BUILDING #2 | | | 7/14/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS | | | HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I | | | AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3 | | | REMOVED- PLEASE COMPLY. | | | | | | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071059 | | | 6/8/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS | | | COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880) | | | AND DID NOT ADDRESS COMMENTS #6-11. | | | | | | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, | | | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH | | | THE MECHANICAL CLOSETS PER SECTION 504.4. | | | | | | 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN | | | THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL | | | FORM. | | | | | | 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE | | | WITH 1ST REVIEW COMMENTS #1, 6, 7, 8, 9, 10, 12, & 14 | | | REPRINTED BELOW: | | | | | | 1ST REVIEW COMMENTS. | | | 8/29/16 | | | | | | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE | | | THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3, | | | AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR | | | VESTIBULE) SYSTEMS- PLEASE PROVIDE. A) THE CALCULATIONS | | | ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B) | | | REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1 | | | SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN | | | | | | 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE | | | CORRECT. C) REFER TO SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL | | | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL | | | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER | | | SHALL BEAR THE SIGNATURE AND SEAL OF THE EOR. D) THE | | | HEATING CAPACITIES OF AHU-1 & 2 (8KW & 10KW IN | | | | | | THE EQUIPMENT SCHEDULE) ARE EXCEEDING THE CALCULATED | | | LOADS AND ARE OVERSIZED- SEE SECTION C403.2.2 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE | | | DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN. | | | | | | 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD | | | PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE | | | A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. | | | | | | 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE | | | THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR | | | CALCULATIONS WILL BE REQUIRED. | | | | | | 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST | | | VENTILATION CALCULATIONS, AND HOISTWAY VENTING | | | CALCULATIONS. | | | | | | 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE | | | PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE | | | LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE | | | AND THICKNESSES OF PIPE INSULATIONS. | | | | | | 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED | | | MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00 | | | IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE | | | PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN, | | | AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE | | | DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP | | | DRAWING APPROVAL STAMP AND SIGNATURE ON THE | | | | | | NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR | | | MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE | | | PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED | | | DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER | | | OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS. | | | | | | 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY | | | IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN | | | INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE | | | PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS | | | SHOWN IN THE ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-08 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-08 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2017-06-08 11:56:35 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071059 | | | 6/8/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS | | | COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880) | | | AND DID NOT ADDRESS COMMENTS #6-11. | | | | | | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, | | | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH | | | THE MECHANICAL CLOSETS PER SECTION 504.4. | | | | | | 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST | | | REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY | | | CODE. | | | | | | 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN | | | THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL | | | FORM. | | | | | | 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE | | | WITH 1ST REVIEW COMMENTS #1, 6, 7, 8, 9, 10, 12, & 14 | | | REPRINTED BELOW: | | | | | | 1ST REVIEW COMMENTS. | | | 8/29/16 | | | | | | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE | | | THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3, | | | AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR | | | VESTIBULE) SYSTEMS- PLEASE PROVIDE. A) THE CALCULATIONS | | | ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B) | | | REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1 | | | SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN | | | | | | 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE | | | CORRECT. C) REFER TO SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL | | | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL | | | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER | | | SHALL BEAR THE SIGNATURE AND SEAL OF THE EOR. D) THE | | | HEATING CAPACITIES OF AHU-1 & 2 (8KW & 10KW IN | | | | | | THE EQUIPMENT SCHEDULE) ARE EXCEEDING THE CALCULATED | | | LOADS AND ARE OVERSIZED- SEE SECTION C403.2.2 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE | | | DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN. | | | | | | 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD | | | PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE | | | A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. | | | | | | 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE | | | THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR | | | CALCULATIONS WILL BE REQUIRED. | | | | | | 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST | | | VENTILATION CALCULATIONS, AND HOISTWAY VENTING | | | CALCULATIONS. | | | | | | 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE | | | PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE | | | LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE | | | AND THICKNESSES OF PIPE INSULATIONS. | | | | | | 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED | | | MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00 | | | IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE | | | PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN, | | | AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE | | | DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP | | | DRAWING APPROVAL STAMP AND SIGNATURE ON THE | | | | | | NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR | | | MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE | | | PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED | | | DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER | | | OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS. | | | | | | 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY | | | IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN | | | INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE | | | PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS | | | SHOWN IN THE ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-29 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-29 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2016-08-29 14:20:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | ROYAL PALM PLACE- BUILDING- 2 | | | 8/29/16 | | | | | | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE | | | THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3, | | | AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR | | | VESTIBULE) SYSTEMS- PLEASE PROVIDE. B) THE CALCULATIONS | | | ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B) | | | REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1 | | | SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN | | | | | | 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE | | | CORRECT. B) REFER TO SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL | | | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL | | | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER | | | SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE | | | ALSO SECTION | | | | | | C407.5.2.3 IF SUBMITTING A TOTAL BUILDING PERFORMANCE | | | ENERGY COMPLIANCE METHOD. C) THE HEATING CAPACITIES OF | | | AHU-1 & 2 (8KW & 10KW IN THE EQUIPMENT SCHEDULE) ARE | | | EXCEEDING THE CALCULATED LOADS AND ARE OVERSIZED- SEE | | | SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | | | 2) SHEETS M-2.00, M-2.01, & M-400: THE SPLIT AC | | | SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, & | | | AHU-B3 SYSTEMS. | | | | | | 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION | | | 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS | | | BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE | | | SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT | | | INSTALLATION INSTRUCTIONS. | | | | | | 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH | | | THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS | | | C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE | | | MATERIALS AND FORMS. | | | | | | 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT | | | OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE | | | CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES- | | | SECTION 401.4 | | | | | | 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE | | | DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN. | | | | | | 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD | | | PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE | | | A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. | | | | | | 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE | | | MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE | | | THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR | | | CALCULATIONS WILL BE REQUIRED. | | | | | | 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST | | | VENTILATION CALCULATIONS, AND HOISTWAY VENTING | | | CALCULATIONS. | | | | | | 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE | | | PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE | | | LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE | | | AND THICKNESSES OF PIPE INSULATIONS. | | | | | | 11) PROVIDE UL FIRESTOPPING ASSEMBLIES FOR PIPE | | | PENETRATIONS. | | | | | | 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED | | | MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00 | | | IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE | | | PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN, | | | AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE | | | DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP | | | DRAWING APPROVAL STAMP AND SIGNATURE ON THE | | | | | | NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR | | | MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE | | | PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED | | | DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER | | | OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS. | | | | | | 13) REFER TO SECTION 306.5 AND PROVIDE DETAILS FOR THE | | | LADDER THAT IS PROVIDING ACCESS TO THE ROOF HATCH. | | | | | | 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY | | | IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN | | | INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE | | | PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS | | | SHOWN IN THE ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2017-07-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-07-20 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-07-20 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2017-07-20 09:49:36 | APPROVED UNDER 3RD REVIEW WITH PROVISOS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-07-14 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-07-14 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2017-07-14 15:03:50 | 1) SHT. A6.08 - THE CLEAR FLOOR SPACE FOR THE LAVATORY | | | SHALL BE CENTERED ON THE FIXTURE PER THE FAIR HOUSING | | | ACCESSIBILITY GUIDELINES.IN ADDITION, PROVIDE THE CLEAR | | | LENGTH X WIDTH DIMENSIONS OF ALL REQUIRED CLEAR FLOOR | | | SPACE DIMENSIONS FOR THE FIXTURES PER THE FHAG. | | | 2) SHT. A6.10 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR | | | SPACE FOR THE WATER CLOSET IN THE A1 UNIT MODEL. COMPLY | | | WITH FHAG. | | | 3) SHT. A 6.10 - UNITS A1 & B1 ARE SHOWN AS A TYPE "A" | | | & "B" DESIGN SPECIFICATION BATHROOM PER THE FHAG. IF | | | THESE ARE "UFAS" UNITS, IDENTIFY THEM AS SUCH. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) THE LETTTER FROM THE ARCHITECT REGARDING THE TOILET | | | FACILITIES FOR WORKERS IS VAGUE AND IS UNACCEPTABLE. | | | REFERENCE IS MADE TO A MAINTENANCE RESTROOM BUT THERE | | | IS NO MAINTENANCE RESTROOM IN BUILDING #1.SANITARY | | | FACILITIES FOR WORKERS IN THE MAINTENANCE AND TRASH | | | AREAS OF BUILDING #1 SHALL BE PROVIDED WITHIN 500 FEET | | | OF THESE AREAS. 2014 FBC SEC. 403.3.3 | | | 5) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET VENT | | | THE RISER SHOWS THE URINAL IN THE MEN'S RESTROOM ACROSS | | | FROM THE EXERCISE ROOM DISCHARGING INTO A VERTICAL WET | | | VENT ABOVE THE LAVATORY. THE URINAL IS TO BE INSTALLED | | | ON IT'S OWN STACK & VENTED. 2014 FBC SECS.912.1, | | | 912.1.1. 3RD REQUEST. | | | 6) SHT. P2.05B - THE MEN'S AND WOMEN'S RESTROOMS ACROSS | | | FROM THE EXERCISE ROOM ARE STILL MISLABELED.PLEASE | | | REVISE. | | | 7) THE LOCATION OF SANITARY RISERS S/24 & S/25 LOCATED | | | ACROSS FROM THE LAUNDRY ROOM ON SHT. P2.05B ARE | | | REVERSED AS TO THE LAYOUT ON SHT. P4.05, REFER TO | | | BUILDING # II, UNIT B1.2ND REQUEST. | | | 8) THE DETAIL FOR THE "PLENUM RATED" WATER METERS ON | | | SHEET P5.00 WILL REQUIRE ADDITIONAL DOCUMENTATION FROM | | | THE MANUFACTURER CWE. INFORMATION ON THEIR WEBSITE | | | INDICATES THEY DO NOT MANUFACTURE "PLENUM RATED WATER | | | METERS". THE MATERIAL COMPOSITION OF THE WATER METERS | | | SHALL MEET THE SMOKE- DEVELOPED INDEX AND FLAME SPREAD | | | RATING REQUIREMENTS OF ASTM E84 OR UL 723. THE FLAME | | | SPREAD INDEX SHALL BE NOT MORE THAN 25 AND THE | | | SMOKE-DEVELOPED INDEX SHALL NOT BE MORE THAN 50. 2014 | | | FBC - MECHANICAL SEC. 602.2.1.2ND REQUEST. | | | 9) SHT. P1.00 - THE ORIENTATION OF BUILDING # II IN | | | RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT | | | CORRELATE WITH THE ORIENTATION OF BULDING II ON SHT. | | | P2.05. CLARIFY. 2ND REQUEST. | | | | | | NOTE: THE ABOVE CONDITIONS ARE PROVISOS FOR APPROVAL OF | | | THESE PLANS FOR PLUMBING PLAN REVIEW. REVISED PLANS | | | SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE | | | ISSUANCE OF THE PLUMBING PERMIT. | | | T.LARGE, CHIEF PLUMBING INSPECTOR | | | JULY 14TH, 2017. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-06-20 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-06-20 |
Time |
06:14 |
Sent To |
|
|
| Notes |
| 2017-06-20 06:15:00 | 1) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND - | | | THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES | | | FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF | | | THE FIRST TOILET PAPER DISPENSER, NOT TO THE CENTERLINE | | | OF THE UNIT AS SHOWN. 2014 FBC-ACCESS. SEC.604.7. | | | 2) SHT.A6.15 - USABLE BATHROOM FIGURES - IDENTIFY ON | | | THE PLANS WHICH BATHROOMS ARE DESIGN SPECIFICATION "A" | | | OR "B" OF THE FHA. THIS SHEET HAS NOT BEEN REVISED AS | | | NOTED IN THE RESPONSE NARRATIVE. 2ND REQUEST. | | | 3) SUBMIT A SEPARATE LETTER FROM THE DESIGN | | | PROFESSIONAL OF RECORD STATING THAT SANITARY FACILITIES | | | FOR THE MAINTENANCE WORKERS ARE LOCATED WITHIN 500 FEET | | | OF THE TRASH ROOMS, MAINTENANCE ROOMS, ETC., PER 2014 | | | FBC-PLUMBING SEC.403.3.3. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR | | | SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST. | | | 5) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE | | | SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.2014 | | | FBC-PLUMBING.2ND REQUEST. | | | 6) ACCESS SHALL BE PROVIDED TO THE WATER SUPPLY VALVES | | | FOR THE STACKED WASHERS/DRYERS. I COULD NOT FIND THE | | | REVISED NOTE ON THE PLANS. CLARIFY. 2014 FPC | | | SEC.606.3.2ND REQUEST | | | 7) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET | | | VENT. 2014 FBC-PLUMBING SEC.912.1, 912.1.1. THE ADDED | | | STACK APPEARS TO HAVE A CLEANOUT ON IT BUT NO URINAL. | | | CLARIFY. | | | 8) SHT.P2.05 - THE MEN'S AND WOMENS RESTROOMS ACROSS | | | FROM THE EXERCISE ROOM ARE STILL MISLABELED.THE SAME | | | ISSUE OCCURS ON SHT. P2.05B AND ON THE ENLARGED PLAN ON | | | P2.05B AND ALSO THERE ARE NO PLUMBING FIXTURES SHOWN IN | | | THE MEN'S RESTROOM ON SHT. P2.05B. | | | 9) THE LOCATION OF THE SANITARY RISERS S/24 & S/25 ON | | | SHT. P2.05 B ARE REVERSED AS TO THE LAYOUT ON | | | SHT.P4.05. BUILDING # II, SEE UNIT B1. | | | 10) THE LOCATION OF SANITARY RISERS S/24 & S/25 ON | | | SHT.SHT. P2.05 A DOES NOT CORRELATE WITH THE LOCATION | | | SHOWN ON SHT. P4.05.THE RISERS ARE REVERSED. | | | 11) SUBMIT A DETAIL FOR THE SUB-WATER METERS IF THEY | | | ARE BEING INSTALLED IN THESE BUILDINGS. SHOW THE | | | LOCATION OF THE SUB-METERS IF APPLICABLE. MATERIALS | | | PLACED WITHIN RETURN AIR PLENUMS SHALL BE | | | NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING | | | A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED | | | IN ACCORDANCE WITH ASTM E84 OR UL 723.2014 | | | FBC-MECHANICAL SEC. 602.2.1. | | | 12) SHT. P4.06 - A SHUTOFF VALVE IS REQUIRED ON THE 2 | | | INCH WATER MAIN SUPPLY TO THE AMENITIES/LEASING AREA | | | PER 2014 FBC-PLUMBING SEC.606.2. | | | 13) SHT.P1.00 - THE ORIENTATION OF BUILDING II IN | | | RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT | | | CORRELATE WITH THE ORIENTATION OF BUILDING II ON SHT. | | | P2.05. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-09-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-09-26 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-09-26 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2016-09-26 08:55:15 | NOTE: NOT ALL OF THESE COMMENTS APPLY TO EACH BUILDING. | | | | | | | | | 1) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE | | | 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014) | | | VERSION OF THE FBC. REVISE THE NOTE. | | | 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE - | | | FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN | | | ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING | | | CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY | | | VOLUME. | | | 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT | | | (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE | | | DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR | | | B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS. | | | WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND | | | SEALED AS REQUIRED BY FL. ADMIN. CODE 61G15-23.001. | | | 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER | | | AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF | | | THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE | | | PLAN/CIVIL DRAWINGS FOR THIS DRAIN. | | | 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL | | | COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE | | | OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF | | | DRAINING INTO THE GUTTERS. | | | 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND - | | | THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES | | | FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF | | | THE DISPENSER. FAC SEC. 604.7. | | | 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE | | | REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE | | | FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2, | | | 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE | | | DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH | | | THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14. | | | 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED | | | CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS, | | | AND APPLIANCES PER REQUIREMENT #7 OF THE FHA | | | GUIDELINES. | | | 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY | | | WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B. | | | 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS, | | | ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS | | | SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF | | | THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3. | | | 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE | | | LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG. | | | #2) . CLARIFY. | | | 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE | | | CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC | | | CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR | | | THE CATCH BASINS. CLARIFY. | | | 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES | | | NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS | | | THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW | | | "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1. | | | 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS | | | ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1. | | | 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR | | | THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN | | | WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER | | | LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT | | | SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING | | | /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES | | | SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR | | | SHAFT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE | | | EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4. | | | 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE | | | SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2. | | | 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE | | | LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO | | | SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE | | | NOTE TO REFER TO CORRECT SHEET. | | | 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH | | | IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS | | | INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED. | | | CLARIFY. | | | 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC | | | SEC. 107.2.1 | | | 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR | | | THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3. | | | 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 ) | | | BUT THIS RISER IS NOT ON THE COLLECTION SYSTEM ON | | | SHT.P-4.01 - CLARIFY. | | | 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) - | | | THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON | | | THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE | | | PLAN VIEW ON SHT. P-2.00. CLARIFY. | | | 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT | | | SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY. | | | 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN | | | SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED | | | FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PER | | | HOUR. 2014 FPC SEC.1106.1. | | | 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE | | | STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2 | | | & 1106.3. | | | 32) SHT. P-4.05 - A URINAL IS NOT PERMITTED ON A WET | | | VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN | | | THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE | | | WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP" | | | IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC. | | | 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE | | | MISLABELED. | | | 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT. | | | P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05. | | | SEE BUILDING #2 - UNIT B1 ( UNIT #115 ). | | | 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A | | | MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2. | | | 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE | | | NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE | | | SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON | | | SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF | | | THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE | | | LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 ( | | | A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY | | | COLLECTION ISOMETRIC ON SHT. P-4.05. | | | 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED | | | S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A). | | | SEE UNIT B1 (#100). | | | 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN | | | VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON | | | SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 ) | | | AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS | | | THERE IS A RISER S/23 FURTHER UPSTREAM. | | | 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS | | | IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE | | | DETAIL PER THE 2014 FPC SEC.405.8. | | | 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER | | | ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH | | | DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A | | | QUICK CLOSING VALVE. 2014 FPC SEC. 604.9. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-09 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2017-08-09 10:43:41 | ROOF INFORMATION NOT PROVIDED | | | | | | THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD AND SUBMITTED PRIOR TO INSTALLATION. THIS IS | | | TYPICALLY SUBMITTED WITH THE ROOF SUB PERMIT | | | APPLICATION. | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2017-08-10 13:16:57 | NEW SHEETS VERIFIED, ALL TRADES | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-09 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2017-08-09 10:01:37 | PAPER PAGES 6.11, 6.12, 6.13 | | | NEW SHEETS VERIFIED | | | ORIGINAL SOILS VERIFIED | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2017-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-19 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-19 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2017-07-19 07:47:23 | SEE REVIEWS UNDER 16071058 | | | NEW SHEETS SUBMITTED REVIEW CYCLE #4 NEED TO BE | | | VERIFIED | | | | | 2017-07-17 09:35:45 | MECH DIG/SIGS VERIFIED- CCOLE | | | 7/17/17 | | 2017-07-12 13:18:42 | SEE REVIEWS UNDER 16071058 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-16 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-16 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2017-06-16 08:34:40 | ELECTRICAL SHEETS APPROVED. | | 2017-05-11 08:31:53 | FOR SIGNATURE REVIEW FOR BUILDING SHEETS, SEE REVIEW | | | UNDER 16071058 | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2017-08-10 13:24:10 | APPLICANT ELECTS TO USE CITY INSPECTORS AT THIS TIME | | | PER KEN CONRAD, RESIDENT INSPECTOR IS VOLUNTARY FOR | | | THIS BUILDING (NOT THRESHOLD) |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-09 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2017-08-09 10:30:01 | SEE REVIEWS UNDER 16071058 | | | | | | AS RESIDENT INSPECTOR IS NOW PROPOSED FOR THIS PROJECT, | | | REVIEW #2 WAS CHANGED FROM "N" TO "F" TO PREVENT THIS | | | PERMIT FROM PRINTING IN ERROR | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-12 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-12 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2016-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-05 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-05 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2016-10-05 08:06:32 | SEE REVIEWS UNDER 16071058 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-08-10 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-08-10 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-08-08 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-08-08 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2017-08-08 13:01:19 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.08.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. AT THE PROPOSED CROSSWALK BETWEEN BUILDINGS #2 AND | | | #4, THE LANDSCAPE ISLANDS ON BOTH SIDES OF THE SIDEWALK | | | SHALL BE EXPANDED TO A MINIMUM OF FIVE (5) FEET IN | | | WIDTH. ADDITIONALLY, THE SOUTHERN-MOST PROPOSED GUMBO | | | LIMBO SHALL BE PLACED IN THE ISLAND OPPOSITE THE | | | PROPOSED TRAFFIC SIGN. | | | | | | 2. PURSUANT TO RESOLUTION NO. 187-16, ALL IMPROVEMENTS | | | (INCLUDING UTILITIES AND REQUIRED SCREENING) SHALL BE | | | MODIFIED TO COMPLY WITH THE MAXIMUM HEIGHT PERMITTED | | | WITHIN THE VISIBILITY TRIANGLE. THIS COMMENT WAS ISSUED | | | PREVIOUSLY AND HAS NOT BEEN FULLY ADDRESSED. THE | | | TRANSFORMER AND ASSOCIATED SCREENING LOCATED ON THE | | | NORTHWEST CORNER OF DIVISION AVENUE AND 15TH STREET | | | (L.A. KIRKSEY) SHALL BE RELOCATED TO COMPLY WITH SUCH | | | PROVISION. | | | | | | 3. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS | | | AND OTHERS CONFLICT WITH LANDSCAPING. THIS COMMENT WAS | | | ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. | | | | | | 4. THE LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A | | | SEPARATE LANDSCAPE PERMIT APPLICATION. THIS COMMENT WAS | | | ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. PLEASE | | | NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THE | | | BUILDING PERMIT PLANS DO NOT MATCH THE LATEST SUBMITTAL | | | MADE FOR THE MINOR PD AMENDMENT. ALL PLANS NEED TO BE | | | CONSISTENT. | | | | | | 5. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | THIS COMMENT WAS ISSUED PREVIOUSLY AND HAS NOT BEEN | | | ADDRESSED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2017-07-31 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-07-31 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-07-31 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2017-07-31 11:34:18 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.31.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING THAT OCCURS BETWEEN THE HANDICAP | | | SPACES (NORTH OF BUILDINGS III AND IV) SHOULD BE | | | RECONFIGURED TO PROVIDE AN APPROPRIATE MID-BLOCK | | | CROSSING WITH LANDSCAPE ISLANDS, ETC. | | | | | | 6. CIVIL PLANS DO NOT REFLECT THE TWO (2) TREE GRATES | | | PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE | | | LEASING CENTER. | | | | | | 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 8. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS | | | AND OTHER CONFLICT WITH LANDSCAPING. | | | | | | 9. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE | | | ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE | | | PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE | | | SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-07-17 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-07-17 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2017-07-17 13:13:09 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.17.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY | | | ENTRANCE SHOULD BE REMOVED - PEDESTRIANS SHOULD USE THE | | | CROSSING AT THE RIGHT-OF-WAY LINE. WHILE THE SIDEWALK | | | HAS BEEN RELOCATED, A DIVIDER MEDIAN HAS BEEN REMOVED | | | FROM THE ROW OF PARKING; PURSUANT TO THE CITY'S ZLDRS, | | | NO MORE THAN 10 CONIGUOUS PARKING SPACES SHALL OCCUR | | | WITH OUT THIS INSTALLATION OF A 5 FOOT WIDE LANDSCAPED | | | DIVIDER MEDIAN WITH SHADE TREE. | | | | | | 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE | | | LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE | | | INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO | | | EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK. | | | | | | 7. PAVING PLANS DO NOT REFLECT THE TWO (2) TREE GRATES | | | PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE | | | LEASING CENTER. | | | | | | 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND | | | LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM | | | THE PROJECT. | | | | | | 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE | | | FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR | | | EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT | | | REFLECTED ON THE ELEVATION. | | | | | | 11. ELEVATION D OF BUILDING II INDICATES THAT THE | | | WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM, | | | LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH | | | ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO | | | THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A | | | DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE | | | FIXED STOREFRONT WINDOWS. | | | | | | 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE | | | VARIOUS RETAINING WALLS? | | | | | | 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF | | | WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE | | | CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE | | | ADDRESSED. | | | | | | 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A | | | TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A | | | LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL | | | INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-06-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-06-14 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-06-14 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2017-06-14 10:18:22 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 06.14.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY | | | ENTRANCE SHOULD BE REMOVED?PEDESTRIANS SHOULD USE THE | | | CROSSING AT THE RIGHT-OF-WAY LINE. | | | | | | 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE | | | LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE | | | INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO | | | EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK. | | | | | | 7. SITE PLAN, PAVING PLANS, ETC. DO NOT REFLECT THE TWO | | | (2) TREE GRATES PROPOSED ALONG THE ON-STREET PARKING, | | | SOUTHWEST OF THE LEASING CENTER. | | | | | | 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND | | | LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM | | | THE PROJECT. | | | | | | 9. THERE?S A LABEL ON THE SITE PLAN THAT INCORRECTLY | | | STATES THAT THERE ARE 143 OFF-STREET PARKING SPACES AND | | | 22 ON-STREET PARKING SPACES?.THE DATA TABLE INDICATES | | | ONLY 156 PARKING SPACES. | | | | | | 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE | | | FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR | | | EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT | | | REFLECTED ON THE ELEVATION. | | | | | | 11. ELEVATION D OF BUILDING II INDICATES THAT THE | | | WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM, | | | LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH | | | ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO | | | THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A | | | DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE | | | FIXED STOREFRONT WINDOWS. | | | | | | 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE | | | VARIOUS RETAINING WALLS? | | | | | | 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF | | | WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE | | | CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE | | | ADDRESSED. | | | | | | 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A | | | TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A | | | LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL | | | INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-10-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-10-03 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2016-10-03 14:24:33 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.03.2016 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL ISSUES REGARDING GRADING, BUILDING ELEVATION, | | | ETC. THAT HAVE BEEN DISCUSSED IN RECENT MEETINGS SHALL | | | BE SATISFACTORILY ADDRESSED. | | | | | | 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 3. AS THE LANDSCAPE PLANS HAVE BEEN REVISED SINCE THE | | | ADOPTION OF RESOLUTION NO. 187-16, A MINOR AMENDMENT TO | | | THE DUNBAR VILLAGE RPD SHALL BE SUBMITTED TO AND | | | APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ? | | | PLANNING DIVISION. | | | | | | 4. ON THE LANDSCAPE PLANS, THERE ARE NUMEROUS CONFLICTS | | | BETWEEN PROPOSED LANDSCAPING AND PROPOSED SITE | | | LIGHTING. ADDITIONALLY, SOME LIGHT POLES ARE SHOWN IN | | | THE MIDDLE OF WALKWAYS, PARKING AREAS, ETC. ENSURE THAT | | | ALL PLANS ARE CONSISTENT AND THAT CONFLICTS AND | | | INCONSISTENCIES ARE ADDRESSED. | | | | | | 5. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 6. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE | | | ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE | | | PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE | | | SURVEY OF EXISTING TREES TO BE REMOVED. | | | | | | 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 8. ALL PLANS SHALL ACCURATELY REFLECT VISIBILITY | | | TRIANGLES IN ACCORDANCE WITH THE REQUIREMENTS OF | | | SECTION 94-305(E). THE LOCATION OF ALL IMPROVEMENTS, | | | INCLUDING BUT NOT LIMITED TO ABOVE-GROUND UTILITIES AND | | | REQUIRED SCREENING, SHALL BE MODIFIED ACCORDINGLY TO | | | COMPLY WITH MAXIMUM HEIGHT PERMITTED WITHIN THE | | | VISIBILITY TRIANGLE. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy