Plan Review Details - Permit 16071058
Plan Review Stops For Permit 16071058
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 12:56 Rev Time 0.00
Received By shill Date 2017-08-10 Time 12:56 Sent To  
Notes
2017-08-10 12:57:06****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058
 WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE
 SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE
 PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED)
 DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED
 UNDER 16071058.
  
 K. REGARDING THE STRUCTURAL CALCULATIONS:
  
 PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY.
 PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC
 WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE
 APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I
 CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR
 WHY THEY WOULD BE DONE DIFFERENTLY.
 PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF
 LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS
 UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT.
 PLEASE PROVIDE THE WARNING NOTED.
  
  
 ******************************************
 BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY)
  
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 4964
  
 CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B
 UNITS: 6
 FLOORS: 1
 BEDROOMS: 8
 ROOMS: 22
 SQ FT LIVABLE: 4964
 SQ FT FOOTPRINT: 4964
 SQ FT ROOF: 4964
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 26
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 8
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 08:44 Rev Time 0.00
Received By shill Date 2017-08-08 Time 09:24 Sent To  
Notes
2017-08-09 08:55:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE INDEX PAGE, A0.01 INDEX, HAS BEEN REPLACED BY
 ANOTHER SHEET, A0.01 PROJECT DATA. THEREFORE, THE
 PROJECT DATA SHEET IS IN THE PLAN TWICE, AND THE 402
 PAGE PLAN NOW LACKS THE FIRST PAGE OF THE INDEX.
  
 RESTORE THE INDEX PAGE.
  
 PROVISO ITEMS - **DO NOT** ADDRESS AT THIS TIME.
 ADDRESS AFTER PERMIT ISSUANCE.
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058
 WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE
 SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE
 PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED)
 DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED
 UNDER 16071058.
  
 K. REGARDING THE STRUCTURAL CALCULATIONS:
  
 PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY.
 PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC
 WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE
 APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I
 CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR
 WHY THEY WOULD BE DONE DIFFERENTLY.
 PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF
 LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS
 UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT.
 PLEASE PROVIDE THE WARNING NOTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-07-28 Cont ID  
Sent By shill Date 2017-07-28 Time 10:32 Rev Time 0.00
Received By shill Date 2017-07-27 Time 17:51 Sent To  
Notes
2017-07-28 10:32:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS FILE STILL HAS DUPLICATE RECORDS; DOCUMENTS
 PREVIOUSLY DENIED AND RESUBMITTED DOCUMENTS WHICH
 SHOULD HAVE SUPERSEDED THE DENIED DOCUMENTS (BUT ARE
 NOW IN THE PERMIT RECORD TWICE - THE NON COMPLIANT ONE
 AND THE CURRENT ONE).
  
 FOR INSTANCE, SEE ENERGY CALCS - THERE IS ONE DATED
 "BLDG 2 ENERGY CALCS SIGNED" DATED 7/18/17. THERE IS
 ANOTHER ENERGY CALC FOR THE SAME BUILDING NAMED
 "BUILDING 2 ENERGY SIGNED" DATED 12/5/16. THIS IS ONE
 EXAMPLE; THERE ARE MORE DUPLICATES IN THE PERMIT
 RECORD.
  
 PLEASE COORDINATE WITH CAROLINE AND LAURA (DIGITAL
 LIBRARIANS) TO CLEAN UP THE FOUR PERMITS PRIOR TO
 ISSUANCE. ALL NEW FILES SHOULD BE NAMED IDENTICALLY TO
 THE OLD DENIED DIGITAL FILE, SO WHEN UPLOADED IT
 SUPERSEDES THE DENIED DOCUMENT.
  
 THIS IS ONLY ONE EXAMPLE. THE SOILS REPORT IS IN THE
 FILE THREE TIMES. PLEASE RETAIN ONLY THE MOST CURRENT
 VERSION; FOR PERMITTING PURPOSES, THE TWO OTHERS APPEAR
 UNNECESSARY. EITHER RENAME SO THEY CAN BE PROPERLY
 VERSIONED (SUBSEQUENT VERSIONS OVERWRITING PREVIOUS
 VERSIONS), OR HAVE THE DOCUMENTS NOT NEEDED REMOVED.
  
 THE LARGE NUMBER OF SUPPORTING DOCUMENTS, WHICH ARE NOT
 IN ANY PARTICULAR ORDER AND DO NOT HAVE A CONSISTENT
 NAMING CONVENTION, MAKES IT VERY DIFFICULT TO LOCATE
 INFORMATION.
  
 2. STRUCTURAL CALCS WERE MADE AVAILABLE TO ME VIA
 DROPBOX. I REQUESTED THAT THEY BE UPLOADED TO THE
 PERMIT RECORD. BUILDING OFFICIAL AND I REVIEWED A
 CALCULATION REPORT WHICH WAS 541 PAGES LONG (ALL
 BUILDINGS), COVER PAGE ETABS 2016, DATED 11/27/16.
 ENGINEER LATER SENT ADDITIONAL REPORTS WHICH INCLUDED
 THE SLAB, GENERATED FROM OTHER SOFTWARE PROGRAMS. THIS
 IS NOT WHAT IS NOW IN PROJECTDOX - THERE IS ONLY ONE
 CALC REPORT IN THE FILE, 62 PAGES, ETABS 2013, BUILDING
 3 ONLY, NAMED 8/10/16 BUT WITH A DATE ON THE COVER PAGE
 OF 7/14/2017.
  
 THE ISSUE IS NOT THAT THE REPORT HAS ONLY ONE BUILDING,
 BUT THAT THE BUILDING OFFICIAL AND I SPENT CONSIDERABLE
 TIME REVIEWING A REPORT SENT BY THE ENGINEER. THE
 ENGINEER STATED THAT THE REPORT I FAILED PREVIOUSLY WAS
 "THE WRONG REPORT". PLEASE COORDINATE WITH HIM TO
 ENSURE THAT THE REPORTS UPLOADED ARE THE CORRECT
 STRUCTURAL CALCULATIONS.
  
 ALSO, IT IS MY UNDERSTANDING THAT THE PLANS IN EACH
 PERMIT ARE IDENTICAL AND HAS BEEN REVIEWED THIS WAY
 (REVIEW DONE ON 16071058 ONLY, AS OTHER PERMITS SHOULD
 HAVE THE SAME DOCUMENTS). IS THIS NO LONGER THE CASE?
 PRIOR TO ISSUANCE, A CHECK WILL BE DONE TO VERIFY THAT
 ALL FOUR PERMITS HAVE THE SAME DOCUMENTS. PLEASE ENSURE
 THAT THIS IS THE CASE PRIOR TO NEXT REVIEW.
  
 IF THE OTHER PERMITS DO NOT HAVE THE SAME DOCUMENTS AS
 THIS ONE, PLEASE ADVISE SO ADDITIONAL REVIEW CAN BE
 DONE.
  
 3. PROVISO, A DUMPSTER ENCLOSURE DETAIL WAS ADDED ON
 SHEET A1.01A. THIS IS SUBJECT TO ENGINEERING
 DEPARTMENT'S APPROVAL.
  
 4. SEE PREVIOUS LIST, ITEM 13. A6.11, OTHER LOCATIONS,
 PLANS STILL REFER TO JOHNSONITE PROFILE SLT-XX-C 2MM
 QT-SCU UNDERLAYMENT. PREVIOUS LIST STATED TO EITHER
 REMOVE THE REFERENCE TO SPECIFIC PRODUCTS OR PROVIDE
 THE 3 TEST REPORTS (STC, IIC, FLAME SPREAD) AT THIS
 TIME. TO MY KNOWLEDGE ONLY ONE PRODUCT HAS ALL THREE
 TEST REPORTS, ANOTHER MANUFACTURER MAY BE HAVING THEIR
 PRODUCT TESTED. SPECIFIC UNDERLAYMENT AND TEST REPORTS
 CAN BE A PROVISO ITEM, BUT THE PERMIT WILL NOT BE
 ISSUED WITH A SPECIFICATION FOR A PRODUCT FOR WHICH
 CODE COMPLIANCE HAS NOT BEEN DEMONSTRATED. PLEASE
 REMOVE REFERENCE TO SPECIFIC PRODUCT SO THAT THIS CAN
 BE A PROVISO ITEM.
  
 5. PLEASE EXPLAIN WHY SHEET S-B1-2.3 AND OTHER S SHEETS
 WERE REVISED. DOES THE STRUCTURAL CHANGE REQUIRE NEW
 CALCULATIONS? IT IS SUGGESTED THAT ANY ADDITIONAL VE BE
 DONE AFTER PERMIT ISSUANCE, AS A REVISION, TO AVOID NEW
 COMMENTS.
  
 PENDING ADDITIONAL INFORMATION (NARRATIVE FOR
 STRUCTURAL CHANGES, COMPLETE CALCULATIONS)
  
 6. APPLICANT MAY CONSIDER APPLYING FOR A FOUNDATION
 PERMIT TO MAINTAIN CONSTRUCTION SCHEDULE, IF DESIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-07-12 Cont ID  
Sent By shill Date 2017-07-12 Time 12:47 Rev Time 0.00
Received By shill Date 2017-07-12 Time 12:47 Sent To  
Notes
2017-07-12 12:49:48****CORRECTIONS****
 IF ALL OTHER TRADES PASS REVIEW, PLEASE CONTACT ME
 REGARDING A POSSIBLE PROVISO
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1) THRESHOLD BUILDING
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED:
  
 1-10. OK
  
 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT
 APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO,
 THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS
 (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO
 SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM
 ALLOWED").
  
 PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL
 DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE
 REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR
 MESSAGES ARE NOT RELEVANT.
  
 3RD REVIEW, THE SAME REPORT WAS PROVIDED (WITH A VALID
 SIGNATURE & SEAL). THEREFORE, THE SAME ERRORS ARE IN
 THE REPORT. THE STRUCTURAL DESIGN CHANGED AFTER THIS
 REPORT WAS PREPARED; IT APPEARS THAT A NEW REPORT IS
 REQUIRED. REPORT SHOWS AN 8" SLAB (SEE TABLE 2.2 SHELL
 SECTIONS SUMMARY), PLAN WAS REVISED TO 6". COLUMN AND
 FOOTING LOCATIONS AND SIZES WERE REVISED.
  
 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED
 SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16.
  
 3RD REVIEW, THIS REPORT HAS BEEN UPLOADED TWICE BUT IS
 NOT DIGITALLY OR ELECTRONICALLY SIGNED AND SEALED. A
 PAPER ORIGINAL MAY BE SUBMITTED, OR A DIGITALLY OR
 ELECTRONICALLY SIGNED AND SEALED REPORT CAN BE UPLOADED
 TO PROJECTDOX.
  
 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS
 REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12
 (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU
 UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE
 THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT
 THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR
 THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED
 PRIOR TO INSTALLATION.
  
 3RD REVIEW, NOT ADDRESSED.
  
 14-17. OK
  
 18. SEE IMPACT FEE REVIEW.
  
 19-21. OK
  
 22-30. OK
  
 WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR
 BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC B 603.
  
 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT
 ADDRESS AT THIS TIME):
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 ******************************************
 BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY)
  
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 4964
  
 CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B
 UNITS: 6
 FLOORS: 1
 BEDROOMS: 8
 ROOMS: 22
 SQ FT LIVABLE: 4964
 SQ FT FOOTPRINT: 4964
 SQ FT ROOF: 4964
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 26
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 8
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-23 Cont ID  
Sent By shill Date 2017-06-23 Time 09:51 Rev Time 0.00
Received By shill Date 2017-06-21 Time 16:48 Sent To  
Notes
2017-06-23 09:54:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1) THRESHOLD BUILDING
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 1. FA1.00A (AND POSSIBLY OTHER PLACES) GOVERNING CODE
 IS INCORRECT, REVISE AND CHECK ALL SHEETS.
  
 2-9. OK
  
 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY
 COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW,
 FBC 5TH EDITION ACCESSIBILITY.
  
 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT
 APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO,
 THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS
 (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO
 SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM
 ALLOWED").
  
 PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL
 DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE
 REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR
 MESSAGES ARE NOT RELEVANT.
  
 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED
 SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16.
  
 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS
 REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12
 (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU
 UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE
 THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT
 THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR
 THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED
 PRIOR TO INSTALLATION.
  
 14. OK
  
 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING,
 FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 2ND REVIEW, ENGINEER'S RESPONSE IS THAT THIS IS ON
 SHEET S0, UNABLE TO LOCATE. PLEASE CLOUD ALL CHANGES
 FBC 107. THIS STATEMENT IS REQUIRED BY THE ARCHITECT
 AND BY THE ENGINEER FOR BUILDING 1.
  
 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79.
  
 RESPONSE STATES THIS IS ATTACHED, UNABLE TO LOCATE.
  
 18. SEE IMPACT FEE REVIEW.
  
 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109.
 WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB VIA EMAIL OR AT TIME OF RESUBMITTAL.
  
 20. OK
  
 21. A8.00, CLUB ROOM DOORS TO HAVE PANIC OR FIRE EXIT
 HARDWARE, 1008.1.10. THE HARDWARE REQUIREMENT IS
 APPLICABLE FOR ALL DOORS IN THE MEANS OF EGRESS.
  
 2ND REVIEW, I WAS UNABLE TO LOCATE DOOR LABELS. SEE
 A8.00, ONLY ONE DOOR (6A) HAS PANIC HARDWARE NOTE 19,
 BUT CLUB ROOM IS ASSEMBLY OCCUPANCY AND HAS TWO EXITS
 (ONE DOUBLE DOOR, ONE SINGLE DOOR). REVISE AND CLARIFY.
  
 22-30. OK
  
 NEW COMMENTS:
  
 PROJECT DATA A0.01, TRAVEL DISTANCE FOR RESIDENTIAL
 SHOULD BE 250' MAX PER FBC B TABLE 1016.2; PLAN APPEARS
 TO COMPLY BUT PLEASE CORRECT THE TABLE (325' STATED AS
 MAX).
  
 WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR
 BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC B 603.
  
 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT
 ADDRESS AT THIS TIME):
  
 A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  
 B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A
 902.1 ADVISORY, ABA) PER ARCHITECT
  
 C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
 (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
 (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION.
  
 D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY
 WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT
 APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING
 WILL BE REVIEWED UNDER A SEPARATE PERMIT.
  
 G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE:
 1 BED 75 UNITS WITH TYPE B BATH
 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA
  
 H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY
 CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED,
 REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING
 DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO
 COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON
 SITE, REVIEWED AND ISSUED BY BUILDING DIVISION.
  
 I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A
 DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS
 REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE
 CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY
 BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
  
  
  
 ******************************
 INFORMATION FOR C.O.:
  
 16071058 BLDG 3
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 4964
  
 CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B
 UNITS: 6
 FLOORS: 1
 BEDROOMS: 8
 ROOMS: 22
 SQ FT LIVABLE: 4964
 SQ FT FOOTPRINT: 4964
 SQ FT ROOF: 4964
  
 OCC LOAD: 26
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 8
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 08:01 Rev Time 0.00
Received By shill Date 2016-10-03 Time 09:43 Sent To  
Notes
2016-10-05 08:02:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT
 NUMBER.
  
 1. A0.01, FA1.00A (AND OTHER PLACES) GOVERNING CODE IS
 INCORRECT, REVISE AND CHECK ALL SHEETS.
  
 2. A0.01 INCLUDES ONLY R2 OCCUPANCY WHEN SHOWING
 COMPLIANCE WITH BUILDING HEIGHT AND AREA. REVISE PLAN
 TO INCLUDE THE BUSINESS AND ASSEMBLY OCCUPANCIES.
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503.
  
 3. A0.01 FBC 508 BUILDING 2 IS A MIXED OCCUPANCY
 BUILDING. INDICATE WHETHER THIS IS SEPARATED OR NON
 SEPARATED MIXED USE.
  
 4. A0.01 TRAVEL DISTANCE DOES NOT INCLUDE ASSEMBLY
 OCCUPANCIES IN THE TABLE, REVISE, FBC 1016.
  
 5. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR
 HOUSING IS NOT CLEAR. IF USING THE FAIR HOUSING DESIGN
 MANUAL, REVISE PLAN TO SHOW COMPLIANCE WITH
 SPECIFICATION A, SPECIFICATION B, NUMBER OF EACH.
  
 6. A1.00, COMPLIANCE WITH REQUIREMENTS FOR ACCESSIBLE
 PARKING SPACES IS NOT CLEAR. PLANS STATE COMPLIANCE
 WITH ADA, BUT DOES NOT COMPLY WITH THE PARKING REQUIRED
 BY FBC ACCESSIBILITY 208.2.
  
 REVISE PLAN TO CLEARLY INDICATE WHICH SPACES SERVE THE
 AMENITY, RESIDENTIAL, LEASING, AMENITY, EMPLOYEES.
 PROVIDE THE NUMBER FOR EACH AS WELL AS NUMBER OF
 ACCESSIBLE SPACES FOR THE SEPARATE USES. LEASING OFFICE
 TO COMPLY WITH ADA, RESIDENTIAL TO COMPLY WITH FHA
 UNLESS DESIGNER IS OPTING FOR ADA AS AN ALTERNATE
 DESIGN METHOD (IN WHICH CASE, NOT ENOUGH ACCESSIBLE
 PARKING IS PROVIDED). AT THIS POINT IT IS DIFFICULT TO
 DETERMINE REQUIREMENTS DUE TO LACK OF FAIR HOUSING
 INFORMATION.
  
 7. GENERAL COMMENT RE WORK AREAS, FBC ACCESSIBILITY
 902.1 ADVISORY, ABA ALSO APPLIES TO FACILITIES
 DESIGNED, BUILT, ALTERED, OR LEASED WITH FEDERAL FUNDS.
 EITHER CONFIRM COMPLIANCE OR CONFIRM NO FEDERAL FUNDS
 WERE USED. THIS MAY BE ADDRESSED IN THE RESPONSE
 LETTER.
  
 8. S0 HAS TEXT WHICH IS ILLEGIBLE (DESIGN CRITERIA),
 REVISE.
  
 9. SB3 2.1 IS NAMED CORRECTLY (ROOF) BUT THE DETAIL IS
 LABLED GROUND FLOOR FRAMING PLAN, REVISE, FBC 107.
  
 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY
 COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW,
 FBC 5TH EDITION ACCESSIBILITY.
  
 11. FS471, FBC 1609, THE STRUCTURAL REPORT DATED
 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, UPLOAD A
 CORRECTLY SIGNED AND SEALED REPORT.
  
 12. FBC 1803, PROVIDE THE SIGNED AND SEALED SOILS
 REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. IT IS
 INCLUDED IN THE STRUCTURAL REPORT BUT THE SOILS REPORT
 NEEDS TO BE SIGNED AND SEALED BY THE ENGINEER ON THE
 SOILS REPORT TITLE BLOCK, FS 471.
  
 13. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207
 IS TO COMPLY WITH THE FOLLOWING:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED
 GYPSUM CEILING ASSEMBLY).
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT
 A DROPPED GYPSUM CEILING ASSEMBLY).
  
 C. FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25
 AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450
 REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 THIS MAY BE A DEFERRED SUBMITTAL UPON REQUEST. TEST
 REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE
 SUBMITTED AS A REVISION PRIOR TO INSTALLATION.
  
 14. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS
 AND CLADDING, FBC 1609. THIS MAY BE A DEFERRED
 SUBMITTAL UPON REQUEST. PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, ARE TO BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION. COMPONENTS AND CLADDING ARE TO
 COMPLY WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE
 OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 15. A SEPARATE ROOF PERMIT IS REQUIRED. IF THIS
 SUBMITTAL IS DEFERRED, THE PRODUCT APPROVAL REVIEWED BY
 DOR IS TO BE SUBMITTED AS A REVISION PRIOR TO
 INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE
 INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED.
  
 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING,
 FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633.
  
 CONFIRM ALL APPLICABLE PAGES INCLUDE THE REQUIRED
 STATEMENT.
  
 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79.
  
 18. SEE IMPACT FEE REVIEW.
  
 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109.
 WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB VIA EMAIL OR AT TIME OF RESUBMITTAL.
  
 20. FBC 107, FOR INFORMATION REQUIRED FOR C.O., PROVIDE
 A TOTAL PER BUILDING:
  
 ROOMS
 BATHROOMS
 BEDROOMS
  
 21. A8.00, CLUB ROOM DOORS TO SWING IN THE DIRECTION OF
 EGRESS TRAVEL AND TO HAVE PANIC OR FIRE EXIT HARDWARE,
 1008.1.10. THE HARDWARE REQUIREMENT IS APPLICABLE FOR
 ALL DOORS IN THE MEANS OF EGRESS. REVISE DOOR SCHEDULE
 TO CLARIFY.
  
 22. FBC 603, BUILDINGS 1 AND 2, IT IS NOT CLEAR UNDER
 WHAT EXEMPTION THE COMBUSTBLE OUTLOOKERS ARE PROPOSED,
 A3.00 AND OTHER SHEETS. SEE ALSO FBC 1406.
  
 23. FBC 603, SHEETS A3.00, 3.01, BUILDINGS 1 AND 2, FBC
 603.1(3), NOTE COMPLIANCE WITH REQUIREMENTS FOR FOAM
 PLASTICS FOR THE FOAM COLUMNS (OR REVISE PLAN TO SHOW
 APPLICABLE EXEMPTION).
  
 24. A2.05, THE WALL BETWEEN UNIT AND AMENITIES LACK THE
 WALL TAG, FBC 107.
  
 A0.01 INDICATES THAT BUILDINGS 3 AND 4 WILL BE
 SPRINKLERED, BUT I WAS UNABLE TO LOCATE FIRE SPRINKLER
 PLANS FOR THESE BUILDINGS, FBC 107, 903.2.8.
  
 25. S 0, WIND DESIGN CRITERIA INCLUDES HVHZ. THIS
 PROJECT IS NOT LOCATED IN HIGH VELOCITY, REMOVE NOTE.
 PLEASE NOTE THAT HIGH VELOCITY IS NOT MORE STRINGENT
 THAN NON HVHZ IN ALL CASES. THE MINIMUM REQUIREMENTS OF
 THE FBC NON HVHZ ARE TO BE MET OR EXCEEDED.
  
 26. ENERGY CALCS REQUIRED FBC 5TH EDITION ENERGY
 CONSERVATION C103 (BUILDING 1), R103 (BUILDINGS 2, 3,
 4).
  
 27. A1.00, LEGEND 10 REFERS TO THE WRONG BUILDING CODE
 AND ALSO REFERS TO ASCE 7 10. CLARIFY; IS THE POOL
 FENCE TO RESIST WIND LOADS? IF SO, WHAT WIND LOADS?
  
 28. A1.00, FBC 107, FBC 1004, OCCUPANT LOAD NOT SHOWN
 FOR THE POOL DECK AREA. FBC TABLE 1004, POOL DECK IS TO
 BE CALCULATED AT 15 SF PER PERSON, POOL SURFACE AT 50
 SF. IT APPEARS THAT THE OCCUPANT LOAD WILL EXCEED 50.
  
 29. A1.00, POOL GATES ARE TO COMPLY WITH THE
 REQUIREMENTS FOR DOORS, FBC 1008.2. THE FOLLOWING IS
 REQUIRED:
 SWING IN THE DIRECTION OF EGRESS TRAVEL
 INCLUDE PANIC OR FIRE EXIT HARDWARE
 SWING AWAY FROM THE POOL AND COMPLY WITH ALL
 REQUIREMENTS OF FBC 454.2.17.1.8
 THE TWO PAIRS OF GATES ARE NOT REMOTELY LOCATED AS
 REQUIRED BY
  
 30. CLARIFY DOOR AND GATE OBSTRUCTION INTO THE EGRESS
 PATH BETWEEN THE FOOD PREP ROOM AND POOL DECK, FBC 107.
  
 31. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL,
 POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE
 SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING,
 TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS.
 SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-08-10 Cont ID  
Sent By jpearson Date 2017-08-10 Time 13:28 Rev Time 0.00
Received By jpearson Date 2017-08-10 Time 13:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By jpearson Date 2017-07-21 Time 07:51 Rev Time 0.00
Received By jpearson Date 2017-07-21 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By jpearson Date 2017-07-12 Time 13:42 Rev Time 0.00
Received By jpearson Date 2017-07-12 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 08:23 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 08:23 Sent To  
Notes
2017-06-16 08:24:40APPROVED WITH EXCEPTION. NEED AIC CALCULATIONS FOR EACH
 SERVICE PRIOR TO ROUGH INSPECTION TO CONFIRM SIZING OF
 SERVICE EQUIPMENT. NEC 110.9, 110.10
 REVIEWED PER PREVIOUS COMMENTS ONLY, WITH ASSISTANCE
 FROM JAKE LEAHY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By vperez Date 2016-08-29 Time 09:33 Rev Time 0.00
Received By vperez Date 2016-08-26 Time 14:05 Sent To  
Notes
2016-08-29 09:37:25INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS:
 PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED
 EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT
 LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL
 SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE
 PERMIT.
 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY
 STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA.
 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING
 REQUIREMENTS.
 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107.
 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM
 FOR A COMPLETE REVIEW. FBC 107.3.5
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2017-07-18 Cont ID  
Sent By SQ Date 2017-07-17 Time 09:02 Rev Time 0.00
Received By squinone Date 2017-07-18 Time 09:02 Sent To I
Notes
2017-07-18 14:59:52NO CIVIL SHEETS PROVIDED. PROJECT UNDER REVIEW THROUGH
 ENGINEERING SERVICES.
2017-07-18 09:03:07PROVIDE STATUS OF E16120006
 ENGINEERING DEPARTMENT APPROVAL REQUIRED PRIOR TO
 PERMIT ISSUANCE
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2017-06-23 Cont ID  
Sent By shill Date 2017-06-23 Time 11:41 Rev Time 0.00
Received By shill Date 2017-06-23 Time 11:41 Sent To  
Notes
2017-06-23 11:42:23ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
 ADVISE AS TO STATUS OF ENGINEERING PERMIT APPLICATION
 E16120006
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 08:28 Rev Time 0.00
Received By shill Date 2017-05-11 Time 08:28 Sent To  
Notes
2017-05-11 08:28:19ENGINEERING APPROVAL REQUIRED VIA A SEPARATE
 ENGINEERING SUBMITTAL TO THE ENGINEERING DEPARTMENT
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-07-21 Cont ID  
Sent By wjolin Date 2017-07-21 Time 13:31 Rev Time 0.00
Received By wjolin Date 2017-07-21 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-05 Cont ID  
Sent By wjolin Date 2017-07-05 Time 12:48 Rev Time 0.00
Received By wjolin Date 2017-07-05 Time 12:48 Sent To  
Notes
2017-07-05 12:48:48PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND
 STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By wjolin Date 2017-05-31 Time 11:55 Rev Time 0.00
Received By wjolin Date 2017-05-31 Time 11:55 Sent To  
Notes
2017-05-31 11:55:40PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND
 STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-18 Cont ID  
Sent By wjolin Date 2016-08-18 Time 15:02 Rev Time 0.00
Received By wjolin Date 2016-08-18 Time 15:02 Sent To  
Notes
2016-08-18 15:02:25PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING
 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING
 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4)
  
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION
 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND
 IN SERVICE PRIOR TO CONSTRUCTION WORK.
  
 GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION
 TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241
 SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 SHEET WS-1 & WS-2: PROVIDE CHAIN WITH LOCK AND TAMPER
 SWITCHES FOR SUPERVISING THE BACKFLOW PREVENTER IN THE
 OPEN POSITION. PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTIONS.
  
 SHEET WS-2: NO FIRE MAINS OR FIRE DEPARTMENT
 CONNECTIONS PROVIDED FOR BUILDING #3 OR #4.
  
 SHEET PD-2: THE SOUTH ENTRANCE OFF 15TH STREET IS ONLY
 12 FEET WIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE
 DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED
 TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36
 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF
 NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 SHEET LS1.05: THE CLUB ROOM IS AN ASSEMBLY ROOM WITH A
 POSSIBLE OCCUPANT LOAD OF 60 TO140 PERSONS DEPENDING
 UPON THE OCCUPANT LOAD FACTOR USED. DOOR C WILL NEED TO
 HAVE THE SWING REVERSED TO SWING WITH EGRESS. DOORS C
 AND D WILL NEED PANIC HARDWARE IF NOT ALREADY EQUIPPED.
  
 SHEET LS1.05: WHEN OCCUPANTS LEAVE THE EXERCISE ROOM,
 WHAT ROUTE IS BEING UTILIZED FOR THE SECONDARY MEANS OF
 EGRESS? THE PRIMARY MEANS OF EGRESS IS TO THE EAST.
  
 EXIT SIGNAGE: SOME OF THE CORRIDORS HAVE AN
 INSUFFICIENT AMOUNT OF EXIT SIGNS. PER NFPA 101 SECTION
 7.10.1.5.2 NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE
 RATED VIEWING DISTANCE OR 100 FEET, WHICHEVER IS LESS,
 FROM THE NEAREST SIGN.
  
 EMERGENCY LIGHTING: BUILDING 1 APPEARS TO ONLY HAVE
 EMERGENCY LIGHTING IN THE STAIRS AND ELEVATOR LOBBY
 AREAS. PER NFPA 101 SECTION 30.2.9 EMERGENCY LIGHTING
 SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR MORE STORIES
 IN HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS
 EVERY DWELLING UNIT HAS A DIRECT EXIT TO THE OUTSIDE OF
 THE BUILDING AT THE FINISHED GROUND LEVEL.
  
 SHEET FA-1.00A: ALL OF THE CODES AND STANDARDS
 REFERENCED IN NOTE #34 ARE OUT OF DATE.
  
 FIRE ALARM ADA: NO VISUAL DEVICES PROVIDED IN THE ADA
 UNITS.
  
 FIRE SPRINKLERS: BUILDINGS 3 AND 4 ARE NOT PROTECTED BY
 AN AUTOMATIC FIRE SPRINKLER SYSTEM. PER NFPA 101
 SECTION 30.3.5.1 ALL NEW APARTMENT BUILDINGS SHALL BE
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ
 SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4).
  
 NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT.
 ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND
 PRIVATE UNDERGROUND FIRE MAINS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 15:38 Rev Time 0.00
Received By shill Date 2017-08-10 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-08-09 Cont ID  
Sent By shill Date 2017-08-09 Time 09:27 Rev Time 0.00
Received By shill Date 2017-08-04 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-08-04 Cont ID  
Sent By lmarchan Date 2017-08-04 Time 15:20 Rev Time 0.00
Received By lmarchan Date 2017-08-04 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-07-31 Cont ID  
Sent By cpuell Date 2017-07-31 Time 11:42 Rev Time 0.00
Received By cpuell Date 2017-07-19 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-17 Cont ID  
Sent By cpuell Date 2017-07-17 Time 13:44 Rev Time 0.00
Received By cpuell Date 2017-07-03 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-24 Cont ID  
Sent By shill Date 2017-06-24 Time 10:58 Rev Time 0.00
Received By shill Date 2017-05-18 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-20 Cont ID  
Sent By cpuell Date 2016-10-20 Time 15:53 Rev Time 0.00
Received By cpuell Date 2016-08-15 Time 10:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By shill Date 2017-08-07 Time 16:51 Rev Time 0.00
Received By shill Date 2017-08-07 Time 16:51 Sent To  
Notes
2017-08-07 16:51:12MU-2017-021132
 125 UNITS
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-17 Cont ID  
Sent By shill Date 2016-09-17 Time 12:58 Rev Time 0.00
Received By shill Date 2016-09-17 Time 12:58 Sent To  
Notes
2016-09-17 13:05:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED
 PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE STAMPED
 AND THE RECEIPT SHOWING THAT THE FEES HAVE BEEN PAID IS
 TO BE PROVIDED.
  
 THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW
 PROCESS, AND MAY BE DONE AFTER ALL OTHER PLAN REVIEWS
 HAVE PASSED.
  
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-07-20 Cont ID  
Sent By ccole Date 2017-07-20 Time 12:49 Rev Time 0.00
Received By ccole Date 2017-07-20 Time 12:49 Sent To  
Notes
2017-07-20 12:54:17MECHANICAL PROVISOS
 PERMIT #16071058
 BUILDING #3
 7/20/2017
  
 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER
 SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING
 CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-14 Cont ID  
Sent By ccole Date 2017-07-14 Time 15:39 Rev Time 0.00
Received By ccole Date 2017-07-14 Time 15:08 Sent To  
Notes
2017-07-14 15:45:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 BUILDING #3
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS
 HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I
 AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3
 REMOVED- PLEASE COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 6/8/17
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- MISSING
 DOCUMENTS: THE SUBMITTED AC CALCULATION PACKET DOES NOT
 INCLUDE THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2,
 SYSTEMS, AND ARE LISTING MIAMI AS THE LOCATION. A)
 REVIEW THE AC SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM
 AHU-1 SYSTEM DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON
 SHEET M-2.00 IN TERMS OF CAPACITY. B)
  
 REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A
 COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR
 EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY
 CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 4) MISSING DOCUMENTS: PROVIDE ENERGY COMPLIANCE FORM
 R405-2014 FOR UNIT A1, AND FOR ENTIRE BUILDING #3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-08 Cont ID  
Sent By ccole Date 2017-06-08 Time 07:26 Rev Time 0.00
Received By ccole Date 2017-06-08 Time 07:01 Sent To  
Notes
2017-06-08 07:27:272ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 6/8/17
  
 RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- THE
 SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE THE
 AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS, AND
 ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC
 SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM
 DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00
 IN TERMS OF CAPACITY. B)
  
 REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A
 COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR
 EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY
 CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL
 BEAR THE SIGNATURE AND SEAL OF THE ENGINEER.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST
 REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY
 CODE.
  
 4) PROVIDE ENERGY COMPLIANCE FORM R405-2014 FOR UNIT
 A1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By ccole Date 2016-08-29 Time 12:04 Rev Time 0.00
Received By ccole Date 2016-08-29 Time 11:22 Sent To  
Notes
2016-08-29 12:05:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16071058
 ROYAL PALM PLACE, BUILDING-3.
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS,
 AND ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC
 SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM
 DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00
 IN TERMS OF CAPACITY. B) REFER TO SECTION C403.2.1
 FBC-14 ENERGY
  
 CONSERVATION: A COOLING AND HEATING CALCULATION SHALL
 BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL
 SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER
 SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE
 ALSO SECTION C407.5.2.3 IF SUBMITTING A TOTAL BUILDING
 PERFORMANCE ENERGY COMPLIANCE METHOD.
  
 2) SHEETS M-1.09, M-2.00, & M-400: THE SPLIT AC
 SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, &
 AHU-B3 SYSTEMS.
  
 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION
 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS
 BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT
 INSTALLATION INSTRUCTIONS.
  
 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS
 C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE
 MATERIALS AND FORMS.
  
 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT
 OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE
 CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES-
 SECTION 401.4
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2017-07-20 Cont ID  
Sent By tklarge Date 2017-07-20 Time 09:39 Rev Time 0.00
Received By tklarge Date 2017-07-20 Time 09:39 Sent To  
Notes
2017-07-20 09:40:23APPROVED UNDER 3RD REVIEW WITH PROVISOS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-14 Cont ID  
Sent By tklarge Date 2017-07-14 Time 14:58 Rev Time 0.00
Received By tklarge Date 2017-07-14 Time 14:58 Sent To  
Notes
2017-07-14 14:58:541) SHT. A6.08 - THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE CENTERED ON THE FIXTURE PER THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES.IN ADDITION, PROVIDE THE CLEAR
 LENGTH X WIDTH DIMENSIONS OF ALL REQUIRED CLEAR FLOOR
 SPACE DIMENSIONS FOR THE FIXTURES PER THE FHAG.
 2) SHT. A6.10 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IN THE A1 UNIT MODEL. COMPLY
 WITH FHAG.
 3) SHT. A 6.10 - UNITS A1 & B1 ARE SHOWN AS A TYPE "A"
 & "B" DESIGN SPECIFICATION BATHROOM PER THE FHAG. IF
 THESE ARE "UFAS" UNITS, IDENTIFY THEM AS SUCH. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) THE LETTTER FROM THE ARCHITECT REGARDING THE TOILET
 FACILITIES FOR WORKERS IS VAGUE AND IS UNACCEPTABLE.
 REFERENCE IS MADE TO A MAINTENANCE RESTROOM BUT THERE
 IS NO MAINTENANCE RESTROOM IN BUILDING #1.SANITARY
 FACILITIES FOR WORKERS IN THE MAINTENANCE AND TRASH
 AREAS OF BUILDING #1 SHALL BE PROVIDED WITHIN 500 FEET
 OF THESE AREAS. 2014 FBC SEC. 403.3.3
 5) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET VENT
 THE RISER SHOWS THE URINAL IN THE MEN'S RESTROOM ACROSS
 FROM THE EXERCISE ROOM DISCHARGING INTO A VERTICAL WET
 VENT ABOVE THE LAVATORY. THE URINAL IS TO BE INSTALLED
 ON IT'S OWN STACK & VENTED. 2014 FBC SECS.912.1,
 912.1.1. 3RD REQUEST.
 6) SHT. P2.05B - THE MEN'S AND WOMEN'S RESTROOMS ACROSS
 FROM THE EXERCISE ROOM ARE STILL MISLABELED.PLEASE
 REVISE.
 7) THE LOCATION OF SANITARY RISERS S/24 & S/25 LOCATED
 ACROSS FROM THE LAUNDRY ROOM ON SHT. P2.05B ARE
 REVERSED AS TO THE LAYOUT ON SHT. P4.05, REFER TO
 BUILDING # II, UNIT B1.2ND REQUEST.
 8) THE DETAIL FOR THE "PLENUM RATED" WATER METERS ON
 SHEET P5.00 WILL REQUIRE ADDITIONAL DOCUMENTATION FROM
 THE MANUFACTURER CWE. INFORMATION ON THEIR WEBSITE
 INDICATES THEY DO NOT MANUFACTURE "PLENUM RATED WATER
 METERS". THE MATERIAL COMPOSITION OF THE WATER METERS
 SHALL MEET THE SMOKE- DEVELOPED INDEX AND FLAME SPREAD
 RATING REQUIREMENTS OF ASTM E84 OR UL 723. THE FLAME
 SPREAD INDEX SHALL BE NOT MORE THAN 25 AND THE
 SMOKE-DEVELOPED INDEX SHALL NOT BE MORE THAN 50. 2014
 FBC - MECHANICAL SEC. 602.2.1.2ND REQUEST.
 9) SHT. P1.00 - THE ORIENTATION OF BUILDING # II IN
 RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT
 CORRELATE WITH THE ORIENTATION OF BULDING II ON SHT.
 P2.05. CLARIFY. 2ND REQUEST.
  
 NOTE: THE ABOVE CONDITIONS ARE PROVISOS FOR APPROVAL OF
 THESE PLANS FOR PLUMBING PLAN REVIEW. REVISED PLANS
 SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE
 ISSUANCE OF THE PLUMBING PERMIT.
 T.LARGE, CHIEF PLUMBING INSPECTOR
 JULY 14TH, 2017.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By tklarge Date 2017-06-20 Time 6:15 Rev Time 0.00
Received By tklarge Date 2017-06-20 Time 05:44 Sent To  
Notes
2017-06-19 14:26:191) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND -
 THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF
 THE FIRST TOILET PAPER DISPENSER, NOT TO THE CENTERLINE
 OF THE UNIT AS SHOWN. 2014 FBC-ACCESS. SEC.604.7.
 2) SHT.A6.15 - USABLE BATHROOM FIGURES - IDENTIFY ON
 THE PLANS WHICH BATHROOMS ARE DESIGN SPECIFICATION "A"
 OR "B" OF THE FHA. THIS SHEET HAS NOT BEEN REVISED AS
 NOTED IN THE RESPONSE NARRATIVE. 2ND REQUEST.
 3) SUBMIT A SEPARATE LETTER FROM THE DESIGN
 PROFESSIONAL OF RECORD STATING THAT SANITARY FACILITIES
 FOR THE MAINTENANCE WORKERS ARE LOCATED WITHIN 500 FEET
 OF THE TRASH ROOMS, MAINTENANCE ROOMS, ETC., PER 2014
 FBC-PLUMBING SEC.403.3.3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR
 SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.
 5) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE
 SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.2014
 FBC-PLUMBING.2ND REQUEST.
 6) ACCESS SHALL BE PROVIDED TO THE WATER SUPPLY VALVES
 FOR THE STACKED WASHERS/DRYERS. I COULD NOT FIND THE
 REVISED NOTE ON THE PLANS. CLARIFY. 2014 FPC
 SEC.606.3.2ND REQUEST
 7) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET
 VENT. 2014 FBC-PLUMBING SEC.912.1, 912.1.1. THE ADDED
 STACK APPEARS TO HAVE A CLEANOUT ON IT BUT NO URINAL.
 CLARIFY.
 8) SHT.P2.05 - THE MEN'S AND WOMENS RESTROOMS ACROSS
 FROM THE EXERCISE ROOM ARE STILL MISLABELED.THE SAME
 ISSUE OCCURS ON SHT. P2.05B AND ON THE ENLARGED PLAN ON
 P2.05B AND ALSO THERE ARE NO PLUMBING FIXTURES SHOWN IN
 THE MEN'S RESTROOM ON SHT. P2.05B.
 9) THE LOCATION OF THE SANITARY RISERS S/24 & S/25 ON
 SHT. P2.05 B ARE REVERSED AS TO THE LAYOUT ON
 SHT.P4.05. BUILDING # II, SEE UNIT B1.
 10) THE LOCATION OF SANITARY RISERS S/24 & S/25 ON
 SHT.SHT. P2.05 A DOES NOT CORRELATE WITH THE LOCATION
 SHOWN ON SHT. P4.05.THE RISERS ARE REVERSED.
 11) SUBMIT A DETAIL FOR THE SUB-WATER METERS IF THEY
 ARE BEING INSTALLED IN THESE BUILDINGS. SHOW THE
 LOCATION OF THE SUB-METERS IF APPLICABLE. MATERIALS
 PLACED WITHIN RETURN AIR PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING
 A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E84 OR UL 723.2014
 FBC-MECHANICAL SEC. 602.2.1.
 12) SHT. P4.06 - A SHUTOFF VALVE IS REQUIRED ON THE 2
 INCH WATER MAIN SUPPLY TO THE AMENITIES/LEASING AREA
 PER 2014 FBC-PLUMBING SEC.606.2.
 13) SHT.P1.00 - THE ORIENTATION OF BUILDING II IN
 RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT
 CORRELATE WITH THE ORIENTATION OF BUILDING II ON SHT.
 P2.05. CLARIFY.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-09-26 Cont ID  
Sent By tklarge Date 2016-09-26 Time 08:31 Rev Time 0.00
Received By tklarge Date 2016-09-24 Time 04:32 Sent To  
Notes
2016-09-24 09:18:231) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE
 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014)
 VERSION OF THE FBC. REVISE THE NOTE.
 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE -
 FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN
 ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING
 CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY
 VOLUME.
 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT
 (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE
 DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR
 B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS.
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND
 SEALED AS REQUIRED BY FL. ADDMIN. CODE 61G15-23.001.
 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER
 AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF
 THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE
 PLAN/CIVIL DRAWINGS FOR THIS DRAIN.
 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL
 COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE
 OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF
 DRAINING INTO THE GUTTERS.
 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND -
 THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF
 THE DISPENSER. FAC SEC. 604.7.
 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE
 FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2,
 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE
 DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH
 THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14.
 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED
 CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS,
 AND APPLIANCES PER REQUIREMENT #7 OF THE FHA
 GUIDELINES.
 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY
 WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B.
 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS,
 ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS
 SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF
 THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3.
 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE
 LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG.
 #2) ? CLARIFY.
 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC
 CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR
 THE CATCH BASINS. CLARIFY.
 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES
 NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS
 THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW
 "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1.
 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS
 ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR
 THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB
 AMEND. TO FBC SEC. 107.2.1.
 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN
 WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER
 LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT
 SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING
 /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES
 SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB
 AMEND. TO FBC SEC. 107.2.1.
 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR
 SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.
 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE
 EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4.
 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE
 SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2.
 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE
 LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO
 SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE
 NOTE TO REFER TO CORRECT SHEET.
 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH
 IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS
 INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED.
 CLARIFY.
 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC
 SEC. 107.2.1
 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR
 THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3.
 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 )
 BUT THIS RISER IS NOT ON THE COOLECTION SYSTEM ON
 SHT.P-4.01 - CLARIFY.
 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) -
 THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON
 THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE
 PLAN VIEW ON SHT. P-2.00. CLARIFY.
 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT
 SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY.
 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN
 SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED
 FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PERR
 HOUR. 2014 FPC SEC.1106.1.
 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE
 STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2
 & 1106.3.
 32) SHT. P-4.05 - A URINAL IS NOT PERNITTED ON A WET
 VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN
 THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE
 WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP"
 IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC.
 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE
 MISLABELED.
 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT.
 P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05.
 SEE BUILDING #2 - UNIT B1 ( UNIT #115 ).
 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A
 MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2.
 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE
 NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON
 SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF
 THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE
 LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 (
 A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY
 COLLECTION ISOMETRIC ON SHT. P-4.05.
 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED
 S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A).
 SEE UNIT B1 (#100).
 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN
 VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON
 SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 )
 AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS
 THERE IS A RISER S/23 FURTHER UPSTREAM.
 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS
 IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE
 DETAIL PER THE 2014 FPC SEC.405.8.
 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER
 ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH
 DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A
 QUICK CLOSING VALVE. 2014 FPC SEC. 604.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-10-05 Cont ID  
Sent By shill Date 2016-10-05 Time 06:52 Rev Time 0.00
Received By shill Date 2016-10-05 Time 06:52 Sent To  
Notes
2016-10-05 06:53:01ROOF INFORMATION NOT PROVIDED
  
 THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED PRIOR TO INSTALLATION. THIS IS
 TYPICALLY SUBMITTED WITH THE ROOF SUB PERMIT
 APPLICATION.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 13:01 Rev Time 0.00
Received By shill Date 2017-08-10 Time 13:01 Sent To  
Notes
2017-08-10 13:01:56NEW SHEETS VERIFIED, ALL TRADES
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2017-08-08 Cont ID  
Sent By shill Date 2017-08-08 Time 08:43 Rev Time 0.00
Received By shill Date 2017-08-08 Time 08:43 Sent To  
Notes
2017-08-08 09:23:35PAPER PAGES 6.11, 6.12, 6.13
 NEW SHEETS VERIFIED
 ORIGINAL SOILS VERIFIED
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2017-07-28 Cont ID  
Sent By shill Date 2017-07-28 Time 10:33 Rev Time 0.00
Received By shill Date 2017-07-28 Time 10:33 Sent To  
Notes
2017-07-28 07:33:09SOILS REPORT DATED 1/6/17 IS DIGITALLY SIGNED AND
 SEALED; REQUESTED THAT THE OTHERS BE REMOVED (OR
 VERSIONED).
  
 SIGNATURE REVIEW REQUIRED FOR REVIEW CYCLE #5
  
  
  
  
2017-07-20 12:56:22MECHANICAL DIG/SIGS VERIFIED. CCOLE- 7/20/2017

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-07-19 Cont ID  
Sent By shill Date 2017-07-19 Time 07:43 Rev Time 0.00
Received By shill Date 2017-07-19 Time 07:43 Sent To  
Notes
2017-07-17 09:34:49MECH DIG/SIGS VERIFIED- CCOLE
 7/17/17
2017-07-12 13:05:00SIGNATURE REVIEW REVISED 7/12/17, S.HILL
  
 NEW SHEETS SUBMITTED FOR 4TH REVIEW CYCLE NEED REVIEW,
 IF APPLICABLE
  
 THE SOILS IS NOT DIGITALLY SIGNED AND SEALED. EITHER
 UPLOAD A DIGITALLY SIGNED AND SEALED SOILS REPORT OR
 THE ORIGINAL PAPER SIGNED AND SEALED SOILS REPORT WILL
 BE REQUIRED TO BE SUBMITTED PRIOR TO PERMIT ISSUANCE.
  
 CIVIL PAGES OK
 STRUCTUAL PLAN PAGES OK
 ARCHITECTURAL PLAN PAGES OK
 FIRE ALARM, FIRE PROTECTION PAGES OK
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-06-16 Cont ID  
Sent By shill Date 2017-06-16 Time 08:25 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 08:25 Sent To  
Notes
2017-06-16 08:25:27ELECTRICAL SHEETS APPROVED.
2016-08-17 15:14:09SIGNATURE REVIEW REVISED 6/23/17, S.HILL
  
 NEW SHEETS SUBMITTED FOR 3RD REVIEW CYCLE NEED REVIEW
  
 STRUCTURAL REPORT (SUPPORTING DOCUMENTS FOLDER)
 PREPARED BY ALISINA MALEK, PE HAS A DIGITAL SIGNATURE
 WITH AN ERROR. CORRECT AND RESUBMIT.
  
 THE SOILS IS NOT DIGITALLY SIGNED AND SEALED. EITHER
 UPLOAD A DIGITALLY SIGNED AND SEALED SOILS REPORT OR
 THE ORIGINAL PAPER SIGNED AND SEALED SOILS REPORT WILL
 BE REQUIRED TO BE SUBMITTED PRIOR TO PERMIT ISSUANCE.
  
 CIVIL PAGES OK
 STRUCTUAL PLAN PAGES OK
 ARCHITECTURAL PLAN PAGES OK
 FIRE ALARM, FIRE PROTECTION PAGES OK
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status N Date 2017-08-10 Cont ID  
Sent By shill Date 2017-08-10 Time 13:06 Rev Time 0.00
Received By shill Date 2017-08-10 Time 13:06 Sent To  
Notes
2017-08-10 13:07:25APPLICANT ELECTS TO USE CITY INSPECTORS AT THIS TIME
 PER KEN CONRAD, RESIDENT INSPECTOR IS VOLUNTARY FOR
 THIS BUILDING (NOT THRESHOLD)

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2017-08-07 Cont ID  
Sent By shill Date 2017-08-07 Time 14:20 Rev Time 0.00
Received By shill Date 2017-08-07 Time 14:20 Sent To  
Notes
2017-08-07 14:37:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 WASEEN QUADRI, PE HAS BEEN APPROVED BY K.CONRAD
 GISELLE BARRERA, BN7157 HAS BEEN PRELIMINARILY APPROVED
 BY K.CONRAD PENDING RECEIPT OF RESUME
  
 AS RESIDENT INSPECTOR IS VOLUNTARY, IT IS POSSIBLE THAT
 THIS PERMIT CAN BE ISSUED WITH THE UNDERSTANDING THAT
 ALL INSPECTIONS WILL BE PERFORMED BY CITY STAFF UNTIL
 APPLICANT PROVIDES ALL REQUIRED RESIDENT INSPECTOR
 DOCUMENTS.
  
 GENERAL COMMENT: NOTARIAL CERTIFICATES AND NOTARY
 PRACTICE TO BE IN ACCORDANCE WITH LAW, WHETHER
 SPECIFICALLY MENTIONED IN THIS LIST OR NOT. NEARLY
 EVERY PAGE HAS AN ERROR. THIS INFORMATION (ACCEPTABLE
 METHODS FOR NOTARIAL CERTIFICATE, OTHER REQUIREMENTS)
 IS READILY AVAILABLE ONLINE. TO EXPEDITE REVIEW, PRIOR
 TO SUBMITTING THE AGREEMENTS TO ME FOR REVIEW,
 APPLICANT IS TO CONFIRM THAT THIS BASIC INFORMATION IS
 CORRECT.
  
 PLEASE RESOLVE THE FOLLOWING ISSUES WITH DOCUMENT "B.1
 SPECIAL INSPECTOR AGREEMENT.PDF" (SI AGREEMENT FOR
 PERMIT #16070916):
  
 1. AS DISCUSSED WITH CHARLES DURING A PRELIMINARY
 REVIEW OF THE SPECIAL INSPECTOR AGREEMENT, THE
 INSPECTOR'S SIGNATURE IS REQUIRED TO BE NOTARIZED.
 GISELLE BARRERA HAS SIGNED THE AGREEMENT, BUT HER
 SIGNATURE IS NOT NOTARIZED.
  
 THE PAGE WITH WASEEM QUADRI, PE'S SIGNATURE MAY REMAIN
 IN THE PACKAGE. ADD ANOTHER PAGE WITH GISELLE BARRERA'S
 NOTARIZED SIGNATURE. ENGINEER SIGNS AT THE TOP OF EACH
 INSPECTOR PAGE.
  
 2. THE NOTARIAL CERTIFICATE FOR CONTRACTOR STATES THAT
 "LEN RICARDO SAEZ" SIGNED, BUT MR. SAEZ APPEARS TO BE
 THE NOTARY, NOT THE CONTRACTOR. PROVIDE A PERMIT
 APPLICATION, NOTARIZED BY THE CONTRACTOR (THIS
 APPLICATION IS STILL "TBD" IN OUR SYSTEM), AND PROVIDE
 THE CONTRACTOR'S NOTARIZED SIGNATURE ON THE SPECIAL
 INSPECTOR AGREEMENT.
  
 3. PLEASE REMOVE THE FORM "AFFIDAVIT CERTIFICATE OF
 CODE COMPLIANCE". THIS IS REQUIRED TO BE SUBMITTED
 AFTER CONSTRUCTION, BEFORE C.O.
  
 4. I AM UNABLE TO LOCATE A RESUME FOR THE PROPOSED
 INSPECTOR, GISELLE BARRERA.
  
 5. I AM UNABLE TO LOCATE A RESUME OF EXPERIENCE FOR THE
 PROPOSED CONTRACTOR, CHRISTOPHER MORAN, LYNX
 CONSTRUCTION MANAGEMENT.
  
 6. ONLY ONE INSPECTOR HAS SIGNED THE AGREEMENT. IN OUR
 EXPERIENCE, A BACKUP INSPECTOR IS RECOMMEDED AS NO
 OTHER INSPECTOR WILL BE PERMITTED ON THE JOB WITHOUT
 PRIOR APPROVAL. AS DISCUSSED WITH CHARLES, SOME
 COMPANIES HAVE ALL OF THEIR (LICENSED) EMPLOYEES SIGN
 THE AGREEMENT. WHETHER THIS WILL BE A RECOMMENDATION OR
 A REQUIREMENT WILL BE AT KEN CONRAD'S DISCRETION. NOTE
 THAT ADDITIONAL INSPECTORS MAY SIGN ON AT ANY TIME, BUT
 PRIOR TO PERFORMING INSPECTIONS ON THIS PROJECT.
  
 7. AS DISCUSSED, A COMPLETE THRESHOLD PACKAGE IS
 REQUIRED. AFTER A COMPLETE PACKAGE IS PROVIDED, THE
 PACKAGE WILL BE FORWARDED TO KEN CONRAD FOR APPROVAL.
  
 IF INFORMATION IS SENT VIA EMAIL RATHER THAN VIA
 RESUBMITTAL, PLEASE SEND A COMPLETE PACKAGE - SIGNED
 AGREEMENTS, RESUMES FOR ALL PARTIES. THE COMPLETE
 PACKAGE WILL BE FORWARDED TO KEN CONRAD. HE DOES NOT
 HAVE ACCESS TO PROJECTDOX.
  
 (NOTE - THRESHOLD INSPECTION PLAN OK, LOCATED IN
 SUPPORTING DOCUMENTS "THRESHOLD INSPECTION GUID LINE")
  
 ***************************************************
 REVIEW FOR DOCUMENTS "B.2 RESIDENT INSPECTOR
 AGREEMENT.PDF", "B.3 RESIDENT INSPECTOR AGREEMENT",
 "B.4 RESIDENT INSPECTOR AGREEMENT".
  
 1. CLARIFY RELATIONSHIP OF YASMIN K QUADRI (NOTARY) TO
 WASEEM QUADRI, PE. THIS MAY BE DONE WITH A LETTER WHICH
 DOES NOT NEED TO BE NOTARIZED, BUT PLEASE INCLUDE IN
 THE AGREEMENT, FLORIDA STATUTE 117.107(11).
  
 2. NOTARIAL CERTIFICATE FOR THE ENGINEER IS INCORRECT;
 THIS LACKS A NAME ON THE LINE WHICH STATES WHO SIGNED
 THE DOCUMENT.
  
 3. NOTARIAL CERTIFICATE FOR THE CONTRACTOR IS
 INCORRECT; NOTARY'S NAME IS INCLUDED RATHER THAN
 CONTRACTOR'S NAME. CONTRACTOR'S NOTARIZED SIGNATURE IS
 REQUIRED FOR THE AGREEMENT.
  
 4. OWNER SIGNATURE OK.
  
 5. ONLY THE ENGINEER, WASEEM QUADRI, PE HAS SIGNED THE
 RESIDENT INSPECTOR AGREEMENT. CONFIRM THAT NO OTHER
 INDIVIDUALS WITH BE PERFORMING INSPECTIONS FOR THIS
 PERMIT, OR ADD ANY PROPOSED INSPECTORS TO THE
 AGREEMENT. USE PAGE 1 FOR EACH INSPECTOR. A RESUME IS
 REQUIRED FOR EACH.
  
 6. A RESIDENT INSPECTOR INSPECTION PLAN IS REQUIRED. IT
 IS POSSIBLE THAT THIS MAY BE A PROVISO ITEM.
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2017-07-28 Cont ID  
Sent By shill Date 2017-07-28 Time 10:34 Rev Time 0.00
Received By shill Date 2017-07-28 Time 10:34 Sent To  
Notes
2017-07-28 10:38:20IF AVAILABLE, PLEASE UPLOAD THE THRESHOLD PACKAGE TO
 PROJECTDOX WHEN RESUBMITTING.
  
 SI AGREEMENT SIGNED BY ALL PARTIES
 RESUMES FOR SI, INSPECTORS, CONTRACTOR
 COPIES OF LICENSES (OR PRINT PAGE FROM
 WWW.MYFLORIDALICENSE.COM)
  
 THIS MAY ALSO BE SENT VIA EMAIL ([email protected]). AFTER
 RECEIPT OF THE COMPLETE PACKAGE, IT WILL BE FORWARDED
 TO KEN CONRAD FOR FINAL APPROVAL. PRIOR TO
 CONSTRUCTION, SCHEDULE A PRE-CONSTRUCTION MEETING WITH
 CONTRACTOR, KEN CONRAD, AND SI.
  
 PLEASE ADVISE, IS APPLICANT USING A RESIDENT INSPECTOR
 FOR THE NON-THRESHOLD BUILDINGS? IF YES, PLEASE PROVIDE
 THAT AGREEMENT AS WELL.
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2017-07-12 Cont ID  
Sent By shill Date 2017-07-12 Time 13:02 Rev Time 0.00
Received By shill Date 2017-07-12 Time 13:02 Sent To  
Notes
2017-07-12 13:03:17****CORRECTIONS****
 THRESHOLD INSPECTOR REQUIRED FOR PERMIT 16070916
 (BUILDING 1; 4 STORIES) ONLY
 RESIDENT INSPECTOR FOR OTHER BUILDINGS RECOMMENDED BUT
 OPTIONAL
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected] ON 9/29/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. CONFIRM
 ALL APPLICABLE PAGES INCLUDE THE REQUIRED STATEMENT.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD AND
 THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SPECIAL INSPECTOR REQUIRED FOR BUILDING 1. DEPENDING
 ON HOW AGGRESSIVE THE CONSTRUCTION SCHEDULE IS,
 APPLICANT MAY WANT TO CONSIDER USING THE SAME INSPECTOR
 FOR BUILDINGS 2, 3, 4 (PER KEN CONRAD, CHIEF BUILDING
 INSPECTOR). PLEASE CALL ME IF YOU WISH TO DISCUSS.
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-09-29 Cont ID  
Sent By shill Date 2016-09-29 Time 06:38 Rev Time 0.00
Received By shill Date 2016-09-17 Time 15:31 Sent To  
Notes
2016-09-29 06:40:15****CORRECTIONS****
 THRESHOLD INSPECTOR REQUIRED FOR PERMIT 16070916
 (BUILDING 1; 4 STORIES) ONLY
 RESIDENT INSPECTOR FOR OTHER BUILDINGS RECOMMENDED BUT
 OPTIONAL
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PERMIT INCLUDES FOUR BUILDINGS:
  
 PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES
 (BUILDING 1)
 PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES
 (BUILDING 2)
 PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 3)
 PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY
 (BUILDING 4)
  
 GOVERNING CODE: FBC 5TH EDITION (FBC 2014)
  
 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED:
  
 A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY
 THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS
 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED
 TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT
 ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL
 INFORMATION.
 FORMS WERE SENT TO: [email protected] ON 9/29/16.
  
 C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW
 BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE
 RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY
 SAMANTHA HILL), 561-805-6666, [email protected],
 [email protected]
  
 ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE
 CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN
 THE SPECIAL INSPECTOR AGREEMENT.
  
 D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO
 KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL
 ([email protected], [email protected]).
  
 E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE
 SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL
 DOCUMENTS.
  
 F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. CONFIRM
 ALL APPLICABLE PAGES INCLUDE THE REQUIRED STATEMENT.
  
 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE
 ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD AND
 THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE
 SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE
 ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO
 INSPECTION. THE CITY APPROVED (CITY STAMPED)
 SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE
 JOB AT THE TIME OF INSPECTION.
  
 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL
 DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD
 BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING.
  
 5. SPECIAL INSPECTOR REQUIRED FOR BUILDING 1. DEPENDING
 ON HOW AGGRESSIVE THE CONSTRUCTION SCHEDULE IS,
 APPLICANT MAY WANT TO CONSIDER USING THE SAME INSPECTOR
 FOR BUILDINGS 2, 3, 4 (PER KEN CONRAD, CHIEF BUILDING
 INSPECTOR). PLEASE CALL ME IF YOU WISH TO DISCUSS.
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2017-08-10 Cont ID  
Sent By jroach Date 2017-08-10 Time 14:16 Rev Time 0.00
Received By jroach Date 2017-08-10 Time 14:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2017-08-08 Cont ID  
Sent By jroach Date 2017-08-08 Time 13:00 Rev Time 0.00
Received By jroach Date 2017-08-08 Time 13:00 Sent To  
Notes
2017-08-08 13:00:51ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.08.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AT THE PROPOSED CROSSWALK BETWEEN BUILDINGS #2 AND
 #4, THE LANDSCAPE ISLANDS ON BOTH SIDES OF THE SIDEWALK
 SHALL BE EXPANDED TO A MINIMUM OF FIVE (5) FEET IN
 WIDTH. ADDITIONALLY, THE SOUTHERN-MOST PROPOSED GUMBO
 LIMBO SHALL BE PLACED IN THE ISLAND OPPOSITE THE
 PROPOSED TRAFFIC SIGN.
  
 2. PURSUANT TO RESOLUTION NO. 187-16, ALL IMPROVEMENTS
 (INCLUDING UTILITIES AND REQUIRED SCREENING) SHALL BE
 MODIFIED TO COMPLY WITH THE MAXIMUM HEIGHT PERMITTED
 WITHIN THE VISIBILITY TRIANGLE. THIS COMMENT WAS ISSUED
 PREVIOUSLY AND HAS NOT BEEN FULLY ADDRESSED. THE
 TRANSFORMER AND ASSOCIATED SCREENING LOCATED ON THE
 NORTHWEST CORNER OF DIVISION AVENUE AND 15TH STREET
 (L.A. KIRKSEY) SHALL BE RELOCATED TO COMPLY WITH SUCH
 PROVISION.
  
 3. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS
 AND OTHERS CONFLICT WITH LANDSCAPING. THIS COMMENT WAS
 ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED.
  
 4. THE LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A
 SEPARATE LANDSCAPE PERMIT APPLICATION. THIS COMMENT WAS
 ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. PLEASE
 NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THE
 BUILDING PERMIT PLANS DO NOT MATCH THE LATEST SUBMITTAL
 MADE FOR THE MINOR PD AMENDMENT. ALL PLANS NEED TO BE
 CONSISTENT.
  
 5. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
 THIS COMMENT WAS ISSUED PREVIOUSLY AND HAS NOT BEEN
 ADDRESSED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 4 Status F Date 2017-07-31 Cont ID  
Sent By jroach Date 2017-07-31 Time 11:33 Rev Time 0.00
Received By jroach Date 2017-07-31 Time 11:33 Sent To  
Notes
2017-07-31 11:33:16ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.31.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING THAT OCCURS BETWEEN THE HANDICAP
 SPACES (NORTH OF BUILDINGS III AND IV) SHOULD BE
 RECONFIGURED TO PROVIDE AN APPROPRIATE MID-BLOCK
 CROSSING WITH LANDSCAPE ISLANDS, ETC.
  
 6. CIVIL PLANS DO NOT REFLECT THE TWO (2) TREE GRATES
 PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE
 LEASING CENTER.
  
 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 8. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS
 AND OTHER CONFLICT WITH LANDSCAPING.
  
 9. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE
 ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE
 PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE
 SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2017-07-17 Cont ID  
Sent By jroach Date 2017-07-17 Time 13:04 Rev Time 0.00
Received By jroach Date 2017-07-17 Time 13:04 Sent To  
Notes
2017-07-17 13:04:24ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.17.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY
 ENTRANCE SHOULD BE REMOVED - PEDESTRIANS SHOULD USE THE
 CROSSING AT THE RIGHT-OF-WAY LINE. WHILE THE SIDEWALK
 HAS BEEN RELOCATED, A DIVIDER MEDIAN HAS BEEN REMOVED
 FROM THE ROW OF PARKING; PURSUANT TO THE CITY'S ZLDRS,
 NO MORE THAN 10 CONIGUOUS PARKING SPACES SHALL OCCUR
 WITH OUT THIS INSTALLATION OF A 5 FOOT WIDE LANDSCAPED
 DIVIDER MEDIAN WITH SHADE TREE.
  
 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE
 LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE
 INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO
 EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK.
  
 7. PAVING PLANS DO NOT REFLECT THE TWO (2) TREE GRATES
 PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE
 LEASING CENTER.
  
 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND
 LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM
 THE PROJECT.
  
 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE
 FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR
 EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT
 REFLECTED ON THE ELEVATION.
  
 11. ELEVATION D OF BUILDING II INDICATES THAT THE
 WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM,
 LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH
 ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO
 THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A
 DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE
 FIXED STOREFRONT WINDOWS.
  
 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE
 VARIOUS RETAINING WALLS?
  
 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF
 WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE
 CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE
 ADDRESSED.
  
 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A
 TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A
 LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL
 INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-14 Cont ID  
Sent By jroach Date 2017-06-14 Time 10:18 Rev Time 0.00
Received By jroach Date 2017-06-14 Time 10:18 Sent To  
Notes
2017-06-14 10:18:47ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.14.2017
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF
 RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR
 VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT
 SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN
 MADE...
  
  A. REMOVAL OF THE POOL.
  
  B. RELOCATION OF STEPS INTO UNITS FACING DIVISION
 AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT
 AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED
 AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS
 WOULD REMAIN AT THE ENTRANCES INTO THE UNITS.
  
  C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL
 NORTH/SOUTH ROAD.
  
  D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL
 ON-STREET PARKING SPACES NO LONGER PROPOSED).
  
  E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A.
 KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY
 ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND
 RIGHT-OUT ONLY.
  
 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT
 LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED
 SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH
 MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY
 TRIANGLE.
  
 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY
 ENTRANCE SHOULD BE REMOVED?PEDESTRIANS SHOULD USE THE
 CROSSING AT THE RIGHT-OF-WAY LINE.
  
 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE
 LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE
 INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO
 EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK.
  
 7. SITE PLAN, PAVING PLANS, ETC. DO NOT REFLECT THE TWO
 (2) TREE GRATES PROPOSED ALONG THE ON-STREET PARKING,
 SOUTHWEST OF THE LEASING CENTER.
  
 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND
 LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM
 THE PROJECT.
  
 9. THERE?S A LABEL ON THE SITE PLAN THAT INCORRECTLY
 STATES THAT THERE ARE 143 OFF-STREET PARKING SPACES AND
 22 ON-STREET PARKING SPACES?.THE DATA TABLE INDICATES
 ONLY 156 PARKING SPACES.
  
 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE
 FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR
 EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT
 REFLECTED ON THE ELEVATION.
  
 11. ELEVATION D OF BUILDING II INDICATES THAT THE
 WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM,
 LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH
 ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO
 THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A
 DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE
 FIXED STOREFRONT WINDOWS.
  
 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE
 VARIOUS RETAINING WALLS?
  
 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF
 WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE
 CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE
 ADDRESSED.
  
 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A
 TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A
 LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL
 INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By jroach Date 2016-10-03 Time 14:24 Rev Time 0.00
Received By jroach Date 2016-10-03 Time 14:23 Sent To  
Notes
2016-10-03 14:24:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.03.2016
 PERMIT NO.: 16070880, 16070916, 16071058, 16071059
 ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH
 STREET, 808 17TH STREET
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW MULTIFAMILY
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL ISSUES REGARDING GRADING, BUILDING ELEVATION,
 ETC. THAT HAVE BEEN DISCUSSED IN RECENT MEETINGS SHALL
 BE SATISFACTORILY ADDRESSED.
  
 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO
 OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR
 EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE
 DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED
 TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO
 DISCUSS THIS ISSUE FURTHER IF NEEDED.
  
 3. AS THE LANDSCAPE PLANS HAVE BEEN REVISED SINCE THE
 ADOPTION OF RESOLUTION NO. 187-16, A MINOR AMENDMENT TO
 THE DUNBAR VILLAGE RPD SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION.
  
 4. ON THE LANDSCAPE PLANS, THERE ARE NUMEROUS CONFLICTS
 BETWEEN PROPOSED LANDSCAPING AND PROPOSED SITE
 LIGHTING. ADDITIONALLY, SOME LIGHT POLES ARE SHOWN IN
 THE MIDDLE OF WALKWAYS, PARKING AREAS, ETC. ENSURE THAT
 ALL PLANS ARE CONSISTENT AND THAT CONFLICTS AND
 INCONSISTENCIES ARE ADDRESSED.
  
 5. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR
 BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET),
 VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM
 ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE
 SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST
 OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS,
 COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN
 EACH 3-UNIT CLUSTER.
  
 6. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE
 ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE
 PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE
 SURVEY OF EXISTING TREES TO BE REMOVED.
  
 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO
 EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION
 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD.
  
 8. ALL PLANS SHALL ACCURATELY REFLECT VISIBILITY
 TRIANGLES IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 94-305(E). THE LOCATION OF ALL IMPROVEMENTS,
 INCLUDING BUT NOT LIMITED TO ABOVE-GROUND UTILITIES AND
 REQUIRED SCREENING, SHALL BE MODIFIED ACCORDINGLY TO
 COMPLY WITH MAXIMUM HEIGHT PERMITTED WITHIN THE
 VISIBILITY TRIANGLE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved