Plan Review Details - Permit 16071058
| Plan Review Stops For Permit 16071058 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2017-08-10 12:57:06 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | | | | B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A | | | 902.1 ADVISORY, ABA) PER ARCHITECT | | | | | | C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED PRIOR TO INSTALLATION. | | | | | | D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT | | | APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING | | | WILL BE REVIEWED UNDER A SEPARATE PERMIT. | | | | | | G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: | | | 1 BED 75 UNITS WITH TYPE B BATH | | | 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA | | | | | | H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY | | | CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, | | | REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING | | | DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO | | | COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON | | | SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. | | | | | | I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A | | | DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS | | | REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE | | | CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY | | | BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. | | | | | | J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058 | | | WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE | | | SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE | | | PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED) | | | DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED | | | UNDER 16071058. | | | | | | K. REGARDING THE STRUCTURAL CALCULATIONS: | | | | | | PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY. | | | PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC | | | WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE | | | APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I | | | CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR | | | WHY THEY WOULD BE DONE DIFFERENTLY. | | | PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF | | | LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS | | | UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT. | | | PLEASE PROVIDE THE WARNING NOTED. | | | | | | | | | ****************************************** | | | BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY) | | | | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 4964 | | | | | | CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B | | | UNITS: 6 | | | FLOORS: 1 | | | BEDROOMS: 8 | | | ROOMS: 22 | | | SQ FT LIVABLE: 4964 | | | SQ FT FOOTPRINT: 4964 | | | SQ FT ROOF: 4964 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 26 | | | PROP USE: APARTMENT | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 8 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-08 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2017-08-09 08:55:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE INDEX PAGE, A0.01 INDEX, HAS BEEN REPLACED BY | | | ANOTHER SHEET, A0.01 PROJECT DATA. THEREFORE, THE | | | PROJECT DATA SHEET IS IN THE PLAN TWICE, AND THE 402 | | | PAGE PLAN NOW LACKS THE FIRST PAGE OF THE INDEX. | | | | | | RESTORE THE INDEX PAGE. | | | | | | PROVISO ITEMS - **DO NOT** ADDRESS AT THIS TIME. | | | ADDRESS AFTER PERMIT ISSUANCE. | | | | | | A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | | | | B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A | | | 902.1 ADVISORY, ABA) PER ARCHITECT | | | | | | C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED PRIOR TO INSTALLATION. | | | | | | D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT | | | APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING | | | WILL BE REVIEWED UNDER A SEPARATE PERMIT. | | | | | | G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: | | | 1 BED 75 UNITS WITH TYPE B BATH | | | 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA | | | | | | H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY | | | CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, | | | REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING | | | DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO | | | COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON | | | SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. | | | | | | I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A | | | DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS | | | REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE | | | CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY | | | BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. | | | | | | J. FILES SUBMITTED UNDER PERMIT APPLICATION #16071058 | | | WERE REVIEWED. PER APPLICANT, THE SAME PLANS WERE | | | SUBMITTED FOR PERMITS 16070880, 16070916, 16071059. THE | | | PLANS APPEAR IDENTICAL. ANY (BUILDING REVIEWED) | | | DISCREPANCIES ARE SUPERSEDED BY THE PLANS REVIEWED | | | UNDER 16071058. | | | | | | K. REGARDING THE STRUCTURAL CALCULATIONS: | | | | | | PAGE 35, F27 SHOWS A 4TH FLOOR WOOD SLAB; CLARIFY. | | | PAGE 11 OF 109 AUTO WIND LOAD CALCULATION SHOWS BASIC | | | WIND SPEED AS 136MPH, BUT PAGE 9 OF 63 IS 170MPH. ONE | | | APPEARS TO BE VASD, THE OTHER APPEARS TO BE VULT, BUT I | | | CANNOT FIND WHERE IT STATES THIS, AND IT IS NOT CLEAR | | | WHY THEY WOULD BE DONE DIFFERENTLY. | | | PAGE 30 OF 109, TABLE 4.5 STEEL FRAME SUMMARY, ROOF | | | LABEL C46 HAS A STATUS OF "WARNING: SEE MESSAGE". I WAS | | | UNABLE TO LOCATE THE MESSAGE IN THE 833 PAGE DOCUMENT. | | | PLEASE PROVIDE THE WARNING NOTED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-28 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-27 |
Time |
17:51 |
Sent To |
|
|
| Notes |
| 2017-07-28 10:32:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS FILE STILL HAS DUPLICATE RECORDS; DOCUMENTS | | | PREVIOUSLY DENIED AND RESUBMITTED DOCUMENTS WHICH | | | SHOULD HAVE SUPERSEDED THE DENIED DOCUMENTS (BUT ARE | | | NOW IN THE PERMIT RECORD TWICE - THE NON COMPLIANT ONE | | | AND THE CURRENT ONE). | | | | | | FOR INSTANCE, SEE ENERGY CALCS - THERE IS ONE DATED | | | "BLDG 2 ENERGY CALCS SIGNED" DATED 7/18/17. THERE IS | | | ANOTHER ENERGY CALC FOR THE SAME BUILDING NAMED | | | "BUILDING 2 ENERGY SIGNED" DATED 12/5/16. THIS IS ONE | | | EXAMPLE; THERE ARE MORE DUPLICATES IN THE PERMIT | | | RECORD. | | | | | | PLEASE COORDINATE WITH CAROLINE AND LAURA (DIGITAL | | | LIBRARIANS) TO CLEAN UP THE FOUR PERMITS PRIOR TO | | | ISSUANCE. ALL NEW FILES SHOULD BE NAMED IDENTICALLY TO | | | THE OLD DENIED DIGITAL FILE, SO WHEN UPLOADED IT | | | SUPERSEDES THE DENIED DOCUMENT. | | | | | | THIS IS ONLY ONE EXAMPLE. THE SOILS REPORT IS IN THE | | | FILE THREE TIMES. PLEASE RETAIN ONLY THE MOST CURRENT | | | VERSION; FOR PERMITTING PURPOSES, THE TWO OTHERS APPEAR | | | UNNECESSARY. EITHER RENAME SO THEY CAN BE PROPERLY | | | VERSIONED (SUBSEQUENT VERSIONS OVERWRITING PREVIOUS | | | VERSIONS), OR HAVE THE DOCUMENTS NOT NEEDED REMOVED. | | | | | | THE LARGE NUMBER OF SUPPORTING DOCUMENTS, WHICH ARE NOT | | | IN ANY PARTICULAR ORDER AND DO NOT HAVE A CONSISTENT | | | NAMING CONVENTION, MAKES IT VERY DIFFICULT TO LOCATE | | | INFORMATION. | | | | | | 2. STRUCTURAL CALCS WERE MADE AVAILABLE TO ME VIA | | | DROPBOX. I REQUESTED THAT THEY BE UPLOADED TO THE | | | PERMIT RECORD. BUILDING OFFICIAL AND I REVIEWED A | | | CALCULATION REPORT WHICH WAS 541 PAGES LONG (ALL | | | BUILDINGS), COVER PAGE ETABS 2016, DATED 11/27/16. | | | ENGINEER LATER SENT ADDITIONAL REPORTS WHICH INCLUDED | | | THE SLAB, GENERATED FROM OTHER SOFTWARE PROGRAMS. THIS | | | IS NOT WHAT IS NOW IN PROJECTDOX - THERE IS ONLY ONE | | | CALC REPORT IN THE FILE, 62 PAGES, ETABS 2013, BUILDING | | | 3 ONLY, NAMED 8/10/16 BUT WITH A DATE ON THE COVER PAGE | | | OF 7/14/2017. | | | | | | THE ISSUE IS NOT THAT THE REPORT HAS ONLY ONE BUILDING, | | | BUT THAT THE BUILDING OFFICIAL AND I SPENT CONSIDERABLE | | | TIME REVIEWING A REPORT SENT BY THE ENGINEER. THE | | | ENGINEER STATED THAT THE REPORT I FAILED PREVIOUSLY WAS | | | "THE WRONG REPORT". PLEASE COORDINATE WITH HIM TO | | | ENSURE THAT THE REPORTS UPLOADED ARE THE CORRECT | | | STRUCTURAL CALCULATIONS. | | | | | | ALSO, IT IS MY UNDERSTANDING THAT THE PLANS IN EACH | | | PERMIT ARE IDENTICAL AND HAS BEEN REVIEWED THIS WAY | | | (REVIEW DONE ON 16071058 ONLY, AS OTHER PERMITS SHOULD | | | HAVE THE SAME DOCUMENTS). IS THIS NO LONGER THE CASE? | | | PRIOR TO ISSUANCE, A CHECK WILL BE DONE TO VERIFY THAT | | | ALL FOUR PERMITS HAVE THE SAME DOCUMENTS. PLEASE ENSURE | | | THAT THIS IS THE CASE PRIOR TO NEXT REVIEW. | | | | | | IF THE OTHER PERMITS DO NOT HAVE THE SAME DOCUMENTS AS | | | THIS ONE, PLEASE ADVISE SO ADDITIONAL REVIEW CAN BE | | | DONE. | | | | | | 3. PROVISO, A DUMPSTER ENCLOSURE DETAIL WAS ADDED ON | | | SHEET A1.01A. THIS IS SUBJECT TO ENGINEERING | | | DEPARTMENT'S APPROVAL. | | | | | | 4. SEE PREVIOUS LIST, ITEM 13. A6.11, OTHER LOCATIONS, | | | PLANS STILL REFER TO JOHNSONITE PROFILE SLT-XX-C 2MM | | | QT-SCU UNDERLAYMENT. PREVIOUS LIST STATED TO EITHER | | | REMOVE THE REFERENCE TO SPECIFIC PRODUCTS OR PROVIDE | | | THE 3 TEST REPORTS (STC, IIC, FLAME SPREAD) AT THIS | | | TIME. TO MY KNOWLEDGE ONLY ONE PRODUCT HAS ALL THREE | | | TEST REPORTS, ANOTHER MANUFACTURER MAY BE HAVING THEIR | | | PRODUCT TESTED. SPECIFIC UNDERLAYMENT AND TEST REPORTS | | | CAN BE A PROVISO ITEM, BUT THE PERMIT WILL NOT BE | | | ISSUED WITH A SPECIFICATION FOR A PRODUCT FOR WHICH | | | CODE COMPLIANCE HAS NOT BEEN DEMONSTRATED. PLEASE | | | REMOVE REFERENCE TO SPECIFIC PRODUCT SO THAT THIS CAN | | | BE A PROVISO ITEM. | | | | | | 5. PLEASE EXPLAIN WHY SHEET S-B1-2.3 AND OTHER S SHEETS | | | WERE REVISED. DOES THE STRUCTURAL CHANGE REQUIRE NEW | | | CALCULATIONS? IT IS SUGGESTED THAT ANY ADDITIONAL VE BE | | | DONE AFTER PERMIT ISSUANCE, AS A REVISION, TO AVOID NEW | | | COMMENTS. | | | | | | PENDING ADDITIONAL INFORMATION (NARRATIVE FOR | | | STRUCTURAL CHANGES, COMPLETE CALCULATIONS) | | | | | | 6. APPLICANT MAY CONSIDER APPLYING FOR A FOUNDATION | | | PERMIT TO MAINTAIN CONSTRUCTION SCHEDULE, IF DESIRED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-12 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-12 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2017-07-12 12:49:48 | ****CORRECTIONS**** | | | IF ALL OTHER TRADES PASS REVIEW, PLEASE CONTACT ME | | | REGARDING A POSSIBLE PROVISO | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PERMIT INCLUDES FOUR BUILDINGS: | | | | | | PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES | | | (BUILDING 1) THRESHOLD BUILDING | | | PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES | | | (BUILDING 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 4) | | | | | | ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT | | | NUMBER. | | | | | | COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED: | | | | | | 1-10. OK | | | | | | 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED | | | 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT | | | APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO, | | | THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS | | | (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO | | | SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM | | | ALLOWED"). | | | | | | PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL | | | DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE | | | REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR | | | MESSAGES ARE NOT RELEVANT. | | | | | | 3RD REVIEW, THE SAME REPORT WAS PROVIDED (WITH A VALID | | | SIGNATURE & SEAL). THEREFORE, THE SAME ERRORS ARE IN | | | THE REPORT. THE STRUCTURAL DESIGN CHANGED AFTER THIS | | | REPORT WAS PREPARED; IT APPEARS THAT A NEW REPORT IS | | | REQUIRED. REPORT SHOWS AN 8" SLAB (SEE TABLE 2.2 SHELL | | | SECTIONS SUMMARY), PLAN WAS REVISED TO 6". COLUMN AND | | | FOOTING LOCATIONS AND SIZES WERE REVISED. | | | | | | 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED | | | SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. | | | | | | 3RD REVIEW, THIS REPORT HAS BEEN UPLOADED TWICE BUT IS | | | NOT DIGITALLY OR ELECTRONICALLY SIGNED AND SEALED. A | | | PAPER ORIGINAL MAY BE SUBMITTED, OR A DIGITALLY OR | | | ELECTRONICALLY SIGNED AND SEALED REPORT CAN BE UPLOADED | | | TO PROJECTDOX. | | | | | | 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS | | | REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12 | | | (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU | | | UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE | | | THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT | | | THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR | | | THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED | | | PRIOR TO INSTALLATION. | | | | | | 3RD REVIEW, NOT ADDRESSED. | | | | | | 14-17. OK | | | | | | 18. SEE IMPACT FEE REVIEW. | | | | | | 19-21. OK | | | | | | 22-30. OK | | | | | | WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR | | | BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE | | | PLAN TO SHOW COMPLIANCE WITH FBC B 603. | | | | | | 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT | | | ADDRESS AT THIS TIME): | | | | | | A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | | | | B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A | | | 902.1 ADVISORY, ABA) PER ARCHITECT | | | | | | C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED PRIOR TO INSTALLATION. | | | | | | D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT | | | APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING | | | WILL BE REVIEWED UNDER A SEPARATE PERMIT. | | | | | | G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: | | | 1 BED 75 UNITS WITH TYPE B BATH | | | 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA | | | | | | H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY | | | CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, | | | REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING | | | DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO | | | COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON | | | SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. | | | | | | I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A | | | DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS | | | REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE | | | CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY | | | BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. | | | | | | ****************************************** | | | BUILDING DATA FOR CO & REPORTING (INTERNAL USE ONLY) | | | | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 4964 | | | | | | CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B | | | UNITS: 6 | | | FLOORS: 1 | | | BEDROOMS: 8 | | | ROOMS: 22 | | | SQ FT LIVABLE: 4964 | | | SQ FT FOOTPRINT: 4964 | | | SQ FT ROOF: 4964 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 26 | | | PROP USE: APARTMENT | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 8 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-23 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-21 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2017-06-23 09:54:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PERMIT INCLUDES FOUR BUILDINGS: | | | | | | PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES | | | (BUILDING 1) THRESHOLD BUILDING | | | PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES | | | (BUILDING 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 4) | | | | | | ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT | | | NUMBER. | | | | | | 1. FA1.00A (AND POSSIBLY OTHER PLACES) GOVERNING CODE | | | IS INCORRECT, REVISE AND CHECK ALL SHEETS. | | | | | | 2-9. OK | | | | | | 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY | | | COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW, | | | FBC 5TH EDITION ACCESSIBILITY. | | | | | | 11. FS471, FBC CHAPTER 16, THE STRUCTURAL REPORT DATED | | | 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, HOWEVER, IT | | | APPEARS THAT THE STRUCTURAL DESIGN HAS CHANGED. ALSO, | | | THE STRUCTURAL REPORT PREVIOUSLY UPLOADED HAS ERRORS | | | (FOR EXAMPLES SEE SHEETS 145, 146, "SHEAR STRESS DUE TO | | | SHEAR FORCE AND TORSION TOGETHER EXCEEDS MAXIMUM | | | ALLOWED"). | | | | | | PROVIDE UPDATED REPORT CONSISTENT WITH NEW STRUCTURAL | | | DESIGN, CONFIRM THERE ARE NO ERROR MESSAGES IN THE | | | REPORT PRIOR TO SUBMITTAL, OR EXPLAIN WHY ANY ERROR | | | MESSAGES ARE NOT RELEVANT. | | | | | | 12. FBC B 1803, FS471, PROVIDE THE SIGNED AND SEALED | | | SOILS REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. | | | | | | 13. SEE PREVIOUS LIST REGARDING THE THREE TEST REPORTS | | | REQUIRED FOR FLOORING UNDERLAYMENT. SHEET A6.11, 6.12 | | | (AND POSSIBLY OTHER PAGES) SPECS ARDEX SD-P AND QT-SCU | | | UNDERLAYMENT. EITHER REMOVE THE NOTE OR PROVIDE THE | | | THREE TEST REPORTS AT THIS TIME. IT IS RECOMMENDED THAT | | | THE NOTE BE REMOVED BUT INCORPORATE THE REQUIREMENT FOR | | | THE THREE TEST REPORTS TO BE SUBMITTED AND REVIEWED | | | PRIOR TO INSTALLATION. | | | | | | 14. OK | | | | | | 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING, | | | FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. | | | | | | 2ND REVIEW, ENGINEER'S RESPONSE IS THAT THIS IS ON | | | SHEET S0, UNABLE TO LOCATE. PLEASE CLOUD ALL CHANGES | | | FBC 107. THIS STATEMENT IS REQUIRED BY THE ARCHITECT | | | AND BY THE ENGINEER FOR BUILDING 1. | | | | | | 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79. | | | | | | RESPONSE STATES THIS IS ATTACHED, UNABLE TO LOCATE. | | | | | | 18. SEE IMPACT FEE REVIEW. | | | | | | 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109. | | | WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS | | | JOB VIA EMAIL OR AT TIME OF RESUBMITTAL. | | | | | | 20. OK | | | | | | 21. A8.00, CLUB ROOM DOORS TO HAVE PANIC OR FIRE EXIT | | | HARDWARE, 1008.1.10. THE HARDWARE REQUIREMENT IS | | | APPLICABLE FOR ALL DOORS IN THE MEANS OF EGRESS. | | | | | | 2ND REVIEW, I WAS UNABLE TO LOCATE DOOR LABELS. SEE | | | A8.00, ONLY ONE DOOR (6A) HAS PANIC HARDWARE NOTE 19, | | | BUT CLUB ROOM IS ASSEMBLY OCCUPANCY AND HAS TWO EXITS | | | (ONE DOUBLE DOOR, ONE SINGLE DOOR). REVISE AND CLARIFY. | | | | | | 22-30. OK | | | | | | NEW COMMENTS: | | | | | | PROJECT DATA A0.01, TRAVEL DISTANCE FOR RESIDENTIAL | | | SHOULD BE 250' MAX PER FBC B TABLE 1016.2; PLAN APPEARS | | | TO COMPLY BUT PLEASE CORRECT THE TABLE (325' STATED AS | | | MAX). | | | | | | WOOD TRUSSES ARE PROPOSED OVER THE CONCRETE ROOF. FOR | | | BUILDINGS 1 AND 2, WHICH ARE TYPE IIA BUILDINGS, REVISE | | | PLAN TO SHOW COMPLIANCE WITH FBC B 603. | | | | | | 31. THIS PERMIT WILL BE ISSUED WITH PROVISOS (DO NOT | | | ADDRESS AT THIS TIME): | | | | | | A. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | | | | B. WORK AREAS TO COMPLY WITH FBC ACCESSIBILITY (FBC A | | | 902.1 ADVISORY, ABA) PER ARCHITECT | | | | | | C. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | (1) FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | (2) FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | (3) FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | TEST REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED PRIOR TO INSTALLATION. | | | | | | D. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION. COMPONENTS AND CLADDING ARE TO COMPLY | | | WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | E. A SEPARATE ROOF PERMIT IS REQUIRED. THE PRODUCT | | | APPROVAL REVIEWED BY DOR IS TO BE SUBMITTED PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | F. CIVIL PAGES WERE NOT REVIEWED BY BUILDING; PAVING | | | WILL BE REVIEWED UNDER A SEPARATE PERMIT. | | | | | | G. FAIR HOUSING COMPLIANCE; SHEET A1.00 HAS A NOTE: | | | 1 BED 75 UNITS WITH TYPE B BATH | | | 2 BED 50 UNITS WITH ONE TYPE A AND ONE TYPE B PER FHA | | | | | | H. SHORING/RESHORE PLANS AND ENGINEERING REVIEWED BY | | | CONTRACTOR AND SPECIAL INSPECTOR ARE TO BE SUBMITTED, | | | REVIEWED AND ISSUED (AS A "SUBMITTAL" TO THE BUILDING | | | DIVISION) PRIOR TO INSTALLATION. NO AFFECTED WORK TO | | | COMMENCE WITHOUT THE SHORING/RESHORE ENGINEERING ON | | | SITE, REVIEWED AND ISSUED BY BUILDING DIVISION. | | | | | | I. A CONSTRUCTION GUARDRAIL DETAIL, PREPARED BY A | | | DESIGN PROFESSIONAL LICENSED UNDER FS471 OR FS481, IS | | | REQUIRED TO BE SUBMITTED, REVIEWED, AND ISSUED BY THE | | | CITY. SUBJECT TO FIELD INSPECTOR'S DISCRETION, THIS MAY | | | BE ACCEPTED IN THE FIELD AT TIME OF INSPECTION. | | | | | | | | | | | | | | | ****************************** | | | INFORMATION FOR C.O.: | | | | | | 16071058 BLDG 3 | | | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS | | | SQUARE FEET - 4964 | | | | | | CONSTRUCTION TYPE: 14-V-B - 5TH ED TYPE V-B | | | UNITS: 6 | | | FLOORS: 1 | | | BEDROOMS: 8 | | | ROOMS: 22 | | | SQ FT LIVABLE: 4964 | | | SQ FT FOOTPRINT: 4964 | | | SQ FT ROOF: 4964 | | | | | | OCC LOAD: 26 | | | PROP USE: APARTMENT | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 8 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED R-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-05 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-03 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2016-10-05 08:02:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PERMIT INCLUDES FOUR BUILDINGS: | | | | | | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 4) | | | | | | ALL FOUR BUILDINGS WILL BE REVIEWED UNDER THIS PERMIT | | | NUMBER. | | | | | | 1. A0.01, FA1.00A (AND OTHER PLACES) GOVERNING CODE IS | | | INCORRECT, REVISE AND CHECK ALL SHEETS. | | | | | | 2. A0.01 INCLUDES ONLY R2 OCCUPANCY WHEN SHOWING | | | COMPLIANCE WITH BUILDING HEIGHT AND AREA. REVISE PLAN | | | TO INCLUDE THE BUSINESS AND ASSEMBLY OCCUPANCIES. | | | REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE 503. | | | | | | 3. A0.01 FBC 508 BUILDING 2 IS A MIXED OCCUPANCY | | | BUILDING. INDICATE WHETHER THIS IS SEPARATED OR NON | | | SEPARATED MIXED USE. | | | | | | 4. A0.01 TRAVEL DISTANCE DOES NOT INCLUDE ASSEMBLY | | | OCCUPANCIES IN THE TABLE, REVISE, FBC 1016. | | | | | | 5. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR | | | HOUSING IS NOT CLEAR. IF USING THE FAIR HOUSING DESIGN | | | MANUAL, REVISE PLAN TO SHOW COMPLIANCE WITH | | | SPECIFICATION A, SPECIFICATION B, NUMBER OF EACH. | | | | | | 6. A1.00, COMPLIANCE WITH REQUIREMENTS FOR ACCESSIBLE | | | PARKING SPACES IS NOT CLEAR. PLANS STATE COMPLIANCE | | | WITH ADA, BUT DOES NOT COMPLY WITH THE PARKING REQUIRED | | | BY FBC ACCESSIBILITY 208.2. | | | | | | REVISE PLAN TO CLEARLY INDICATE WHICH SPACES SERVE THE | | | AMENITY, RESIDENTIAL, LEASING, AMENITY, EMPLOYEES. | | | PROVIDE THE NUMBER FOR EACH AS WELL AS NUMBER OF | | | ACCESSIBLE SPACES FOR THE SEPARATE USES. LEASING OFFICE | | | TO COMPLY WITH ADA, RESIDENTIAL TO COMPLY WITH FHA | | | UNLESS DESIGNER IS OPTING FOR ADA AS AN ALTERNATE | | | DESIGN METHOD (IN WHICH CASE, NOT ENOUGH ACCESSIBLE | | | PARKING IS PROVIDED). AT THIS POINT IT IS DIFFICULT TO | | | DETERMINE REQUIREMENTS DUE TO LACK OF FAIR HOUSING | | | INFORMATION. | | | | | | 7. GENERAL COMMENT RE WORK AREAS, FBC ACCESSIBILITY | | | 902.1 ADVISORY, ABA ALSO APPLIES TO FACILITIES | | | DESIGNED, BUILT, ALTERED, OR LEASED WITH FEDERAL FUNDS. | | | EITHER CONFIRM COMPLIANCE OR CONFIRM NO FEDERAL FUNDS | | | WERE USED. THIS MAY BE ADDRESSED IN THE RESPONSE | | | LETTER. | | | | | | 8. S0 HAS TEXT WHICH IS ILLEGIBLE (DESIGN CRITERIA), | | | REVISE. | | | | | | 9. SB3 2.1 IS NAMED CORRECTLY (ROOF) BUT THE DETAIL IS | | | LABLED GROUND FLOOR FRAMING PLAN, REVISE, FBC 107. | | | | | | 10. REVISE PLAN TO ADDRESS PLUMBING ACCESSIBILITY | | | COMMENTS WHICH ARE ALSO APPLICABLE FOR BUILDING REVIEW, | | | FBC 5TH EDITION ACCESSIBILITY. | | | | | | 11. FS471, FBC 1609, THE STRUCTURAL REPORT DATED | | | 8.10.2016 HAS AN INVALID DIGITAL SIGNATURE, UPLOAD A | | | CORRECTLY SIGNED AND SEALED REPORT. | | | | | | 12. FBC 1803, PROVIDE THE SIGNED AND SEALED SOILS | | | REPORT PREPARED BY ARDAMAN & ASSOCIATES 3/28/16. IT IS | | | INCLUDED IN THE STRUCTURAL REPORT BUT THE SOILS REPORT | | | NEEDS TO BE SIGNED AND SEALED BY THE ENGINEER ON THE | | | SOILS REPORT TITLE BLOCK, FS 471. | | | | | | 13. FLOORING ACOUSTICAL INSULATION REQUIRED BY FBC 1207 | | | IS TO COMPLY WITH THE FOLLOWING: | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | PROVIDE A COPY OF THE TEST REPORT (WITHOUT A DROPPED | | | GYPSUM CEILING ASSEMBLY). | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT (WITHOUT | | | A DROPPED GYPSUM CEILING ASSEMBLY). | | | | | | C. FBC 720.2, FLAME SPREAD INDEX OF NOT MORE THAN 25 | | | AND SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 | | | REQUIRED. PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | | 84 OR UL 723. | | | | | | THIS MAY BE A DEFERRED SUBMITTAL UPON REQUEST. TEST | | | REPORTS, REVIEWED BY DESIGNER OF RECORD, ARE TO BE | | | SUBMITTED AS A REVISION PRIOR TO INSTALLATION. | | | | | | 14. PRODUCT APPROVALS ARE REQUIRED FOR ALL COMPONENTS | | | AND CLADDING, FBC 1609. THIS MAY BE A DEFERRED | | | SUBMITTAL UPON REQUEST. PRODUCT APPROVALS, REVIEWED BY | | | DESIGNER OF RECORD, ARE TO BE SUBMITTED AS A REVISION | | | PRIOR TO INSTALLATION. COMPONENTS AND CLADDING ARE TO | | | COMPLY WITH THE DESIGN PRESSURES SHOWN ON SHEET S0. THE | | | OPTIONS SELECTED ARE TO BE MARKED ON THE PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | 15. A SEPARATE ROOF PERMIT IS REQUIRED. IF THIS | | | SUBMITTAL IS DEFERRED, THE PRODUCT APPROVAL REVIEWED BY | | | DOR IS TO BE SUBMITTED AS A REVISION PRIOR TO | | | INSTALLATION. THE APPROVED ASSEMBLY PROPOSED IS TO BE | | | INDICATED AND ENGINEERING, IF APPLICABLE, SUBMITTED. | | | | | | 16. 16070916 (BUILDING 1) IS A THRESHOLD BUILDING, | | | FS553.79(7)(D). ALL PLANS FOR THE BUILDING WHICH ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. | | | | | | CONFIRM ALL APPLICABLE PAGES INCLUDE THE REQUIRED | | | STATEMENT. | | | | | | 17. THRESHOLD INSPECTION PLAN REQUIRED, FS 553.79. | | | | | | 18. SEE IMPACT FEE REVIEW. | | | | | | 19. VALUE HAS BEEN ADJUSTED PER ICC TABLES, FBC 109. | | | WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR THIS | | | JOB VIA EMAIL OR AT TIME OF RESUBMITTAL. | | | | | | 20. FBC 107, FOR INFORMATION REQUIRED FOR C.O., PROVIDE | | | A TOTAL PER BUILDING: | | | | | | ROOMS | | | BATHROOMS | | | BEDROOMS | | | | | | 21. A8.00, CLUB ROOM DOORS TO SWING IN THE DIRECTION OF | | | EGRESS TRAVEL AND TO HAVE PANIC OR FIRE EXIT HARDWARE, | | | 1008.1.10. THE HARDWARE REQUIREMENT IS APPLICABLE FOR | | | ALL DOORS IN THE MEANS OF EGRESS. REVISE DOOR SCHEDULE | | | TO CLARIFY. | | | | | | 22. FBC 603, BUILDINGS 1 AND 2, IT IS NOT CLEAR UNDER | | | WHAT EXEMPTION THE COMBUSTBLE OUTLOOKERS ARE PROPOSED, | | | A3.00 AND OTHER SHEETS. SEE ALSO FBC 1406. | | | | | | 23. FBC 603, SHEETS A3.00, 3.01, BUILDINGS 1 AND 2, FBC | | | 603.1(3), NOTE COMPLIANCE WITH REQUIREMENTS FOR FOAM | | | PLASTICS FOR THE FOAM COLUMNS (OR REVISE PLAN TO SHOW | | | APPLICABLE EXEMPTION). | | | | | | 24. A2.05, THE WALL BETWEEN UNIT AND AMENITIES LACK THE | | | WALL TAG, FBC 107. | | | | | | A0.01 INDICATES THAT BUILDINGS 3 AND 4 WILL BE | | | SPRINKLERED, BUT I WAS UNABLE TO LOCATE FIRE SPRINKLER | | | PLANS FOR THESE BUILDINGS, FBC 107, 903.2.8. | | | | | | 25. S 0, WIND DESIGN CRITERIA INCLUDES HVHZ. THIS | | | PROJECT IS NOT LOCATED IN HIGH VELOCITY, REMOVE NOTE. | | | PLEASE NOTE THAT HIGH VELOCITY IS NOT MORE STRINGENT | | | THAN NON HVHZ IN ALL CASES. THE MINIMUM REQUIREMENTS OF | | | THE FBC NON HVHZ ARE TO BE MET OR EXCEEDED. | | | | | | 26. ENERGY CALCS REQUIRED FBC 5TH EDITION ENERGY | | | CONSERVATION C103 (BUILDING 1), R103 (BUILDINGS 2, 3, | | | 4). | | | | | | 27. A1.00, LEGEND 10 REFERS TO THE WRONG BUILDING CODE | | | AND ALSO REFERS TO ASCE 7 10. CLARIFY; IS THE POOL | | | FENCE TO RESIST WIND LOADS? IF SO, WHAT WIND LOADS? | | | | | | 28. A1.00, FBC 107, FBC 1004, OCCUPANT LOAD NOT SHOWN | | | FOR THE POOL DECK AREA. FBC TABLE 1004, POOL DECK IS TO | | | BE CALCULATED AT 15 SF PER PERSON, POOL SURFACE AT 50 | | | SF. IT APPEARS THAT THE OCCUPANT LOAD WILL EXCEED 50. | | | | | | 29. A1.00, POOL GATES ARE TO COMPLY WITH THE | | | REQUIREMENTS FOR DOORS, FBC 1008.2. THE FOLLOWING IS | | | REQUIRED: | | | SWING IN THE DIRECTION OF EGRESS TRAVEL | | | INCLUDE PANIC OR FIRE EXIT HARDWARE | | | SWING AWAY FROM THE POOL AND COMPLY WITH ALL | | | REQUIREMENTS OF FBC 454.2.17.1.8 | | | THE TWO PAIRS OF GATES ARE NOT REMOTELY LOCATED AS | | | REQUIRED BY | | | | | | 30. CLARIFY DOOR AND GATE OBSTRUCTION INTO THE EGRESS | | | PATH BETWEEN THE FOOD PREP ROOM AND POOL DECK, FBC 107. | | | | | | 31. SEPARATE PERMITS REQUIRED FOR SITE AMENITIES, POOL, | | | POOL DECK, FENCING, PAVING, SIDEWALKS, FIRE ALARM, FIRE | | | SPRINKLER, FIRE UNDERGROUND, PARKING LOT & STRIPING, | | | TEMPORARY TRAILER, CONSTRUCTION OFFICES, SIGNS. | | | SEPARATE PLANS, PERMITS, REVIEWS, AND FEES REQUIRED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-08-10 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-08-10 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-21 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-21 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-07-12 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-07-12 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-06-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-06-16 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-16 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2017-06-16 08:24:40 | APPROVED WITH EXCEPTION. NEED AIC CALCULATIONS FOR EACH | | | SERVICE PRIOR TO ROUGH INSPECTION TO CONFIRM SIZING OF | | | SERVICE EQUIPMENT. NEC 110.9, 110.10 | | | REVIEWED PER PREVIOUS COMMENTS ONLY, WITH ASSISTANCE | | | FROM JAKE LEAHY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-08-29 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-08-26 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2016-08-29 09:37:25 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS: | | | PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | | SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED | | | EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT | | | LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV, | | | PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL | | | SUFFICE. | | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP | | | AND COMPLETIONS DOCUMENTS. | | | 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE | | | PERMIT. | | | 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY | | | STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA. | | | 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING | | | REQUIREMENTS. | | | 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION | | | PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC | | | 107. | | | 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM | | | FOR A COMPLETE REVIEW. FBC 107.3.5 | | | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2017-07-18 |
|
|
Cont ID |
|
| Sent By |
SQ |
Date |
2017-07-17 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
squinone |
Date |
2017-07-18 |
Time |
09:02 |
Sent To |
I |
|
| Notes |
| 2017-07-18 14:59:52 | NO CIVIL SHEETS PROVIDED. PROJECT UNDER REVIEW THROUGH | | | ENGINEERING SERVICES. | | 2017-07-18 09:03:07 | PROVIDE STATUS OF E16120006 | | | ENGINEERING DEPARTMENT APPROVAL REQUIRED PRIOR TO | | | PERMIT ISSUANCE | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2017-06-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-23 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-23 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2017-06-23 11:42:23 | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | ADVISE AS TO STATUS OF ENGINEERING PERMIT APPLICATION | | | E16120006 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2017-05-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-05-11 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-11 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2017-05-11 08:28:19 | ENGINEERING APPROVAL REQUIRED VIA A SEPARATE | | | ENGINEERING SUBMITTAL TO THE ENGINEERING DEPARTMENT | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2017-07-21 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-07-21 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-07-21 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2017-07-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-07-05 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-07-05 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2017-07-05 12:48:48 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND | | | STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2017-05-31 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2017-05-31 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2017-05-31 11:55:40 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND | | | STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-08-18 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-08-18 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-08-18 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2016-08-18 15:02:25 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING | | | 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING | | | 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) | | | | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION | | | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND | | | IN SERVICE PRIOR TO CONSTRUCTION WORK. | | | | | | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION | | | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 | | | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | SHEET WS-1 & WS-2: PROVIDE CHAIN WITH LOCK AND TAMPER | | | SWITCHES FOR SUPERVISING THE BACKFLOW PREVENTER IN THE | | | OPEN POSITION. PROVIDE LOCKING KNOX CAPS ON FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | SHEET WS-2: NO FIRE MAINS OR FIRE DEPARTMENT | | | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. | | | | | | SHEET PD-2: THE SOUTH ENTRANCE OFF 15TH STREET IS ONLY | | | 12 FEET WIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE | | | DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED | | | TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 | | | TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF | | | NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL | | | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. | | | | | | SHEET LS1.05: THE CLUB ROOM IS AN ASSEMBLY ROOM WITH A | | | POSSIBLE OCCUPANT LOAD OF 60 TO140 PERSONS DEPENDING | | | UPON THE OCCUPANT LOAD FACTOR USED. DOOR C WILL NEED TO | | | HAVE THE SWING REVERSED TO SWING WITH EGRESS. DOORS C | | | AND D WILL NEED PANIC HARDWARE IF NOT ALREADY EQUIPPED. | | | | | | SHEET LS1.05: WHEN OCCUPANTS LEAVE THE EXERCISE ROOM, | | | WHAT ROUTE IS BEING UTILIZED FOR THE SECONDARY MEANS OF | | | EGRESS? THE PRIMARY MEANS OF EGRESS IS TO THE EAST. | | | | | | EXIT SIGNAGE: SOME OF THE CORRIDORS HAVE AN | | | INSUFFICIENT AMOUNT OF EXIT SIGNS. PER NFPA 101 SECTION | | | 7.10.1.5.2 NEW SIGN PLACEMENT SHALL BE SUCH THAT NO | | | POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE | | | RATED VIEWING DISTANCE OR 100 FEET, WHICHEVER IS LESS, | | | FROM THE NEAREST SIGN. | | | | | | EMERGENCY LIGHTING: BUILDING 1 APPEARS TO ONLY HAVE | | | EMERGENCY LIGHTING IN THE STAIRS AND ELEVATOR LOBBY | | | AREAS. PER NFPA 101 SECTION 30.2.9 EMERGENCY LIGHTING | | | SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR MORE STORIES | | | IN HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS | | | EVERY DWELLING UNIT HAS A DIRECT EXIT TO THE OUTSIDE OF | | | THE BUILDING AT THE FINISHED GROUND LEVEL. | | | | | | SHEET FA-1.00A: ALL OF THE CODES AND STANDARDS | | | REFERENCED IN NOTE #34 ARE OUT OF DATE. | | | | | | FIRE ALARM ADA: NO VISUAL DEVICES PROVIDED IN THE ADA | | | UNITS. | | | | | | FIRE SPRINKLERS: BUILDINGS 3 AND 4 ARE NOT PROTECTED BY | | | AN AUTOMATIC FIRE SPRINKLER SYSTEM. PER NFPA 101 | | | SECTION 30.3.5.1 ALL NEW APARTMENT BUILDINGS SHALL BE | | | PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED | | | AUTOMATIC SPRINKLER SYSTEM. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ | | | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE | | | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION | | | 1.14.4). | | | | | | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. | | | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND | | | PRIVATE UNDERGROUND FIRE MAINS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2017-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-09 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-04 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2017-08-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-08-04 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-08-04 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-07-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-31 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-19 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2017-07-17 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2017-07-03 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-24 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-05-18 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-10-20 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-08-15 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2017-08-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-07 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-07 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2017-08-07 16:51:12 | MU-2017-021132 | | | 125 UNITS | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-09-17 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-17 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2016-09-17 13:05:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED | | | PRIOR TO PERMIT ISSUANCE. THE PLANS ARE TO BE STAMPED | | | AND THE RECEIPT SHOWING THAT THE FEES HAVE BEEN PAID IS | | | TO BE PROVIDED. | | | | | | THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW | | | PROCESS, AND MAY BE DONE AFTER ALL OTHER PLAN REVIEWS | | | HAVE PASSED. | | | | | | CONTACT 561-233-5025 FOR MORE INFORMATION. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2017-07-20 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-20 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-20 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2017-07-20 12:54:17 | MECHANICAL PROVISOS | | | PERMIT #16071058 | | | BUILDING #3 | | | 7/20/2017 | | | | | | 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER | | | SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING | | | CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-07-14 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-07-14 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2017-07-14 15:45:03 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071058 | | | BUILDING #3 | | | 7/14/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS | | | HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I | | | AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3 | | | REMOVED- PLEASE COMPLY. | | | | | | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071058 | | | 6/8/17 | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- MISSING | | | DOCUMENTS: THE SUBMITTED AC CALCULATION PACKET DOES NOT | | | INCLUDE THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, | | | SYSTEMS, AND ARE LISTING MIAMI AS THE LOCATION. A) | | | REVIEW THE AC SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM | | | AHU-1 SYSTEM DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON | | | SHEET M-2.00 IN TERMS OF CAPACITY. B) | | | | | | REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A | | | COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR | | | EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY | | | CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL | | | BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. | | | | | | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, | | | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH | | | THE MECHANICAL CLOSETS PER SECTION 504.4. | | | | | | 4) MISSING DOCUMENTS: PROVIDE ENERGY COMPLIANCE FORM | | | R405-2014 FOR UNIT A1, AND FOR ENTIRE BUILDING #3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-06-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-06-08 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-06-08 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2017-06-08 07:27:27 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071058 | | | 6/8/17 | | | | | | RESULTS: DENIED. | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- THE | | | SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE THE | | | AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS, AND | | | ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC | | | SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM | | | DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00 | | | IN TERMS OF CAPACITY. B) | | | | | | REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A | | | COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR | | | EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY | | | CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL | | | BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. | | | | | | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, | | | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH | | | THE MECHANICAL CLOSETS PER SECTION 504.4. | | | | | | 3) M-2.01, UNIT B-1: AS PREVIOUSLY NOTED IN THE 1ST | | | REVIEW DRYER BOOSTER FANS ARE NO LONGER PERMITTED BY | | | CODE. | | | | | | 4) PROVIDE ENERGY COMPLIANCE FORM R405-2014 FOR UNIT | | | A1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-08-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-08-29 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-08-29 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2016-08-29 12:05:55 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071058 | | | ROYAL PALM PLACE, BUILDING-3. | | | | | | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE | | | THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, SYSTEMS, | | | AND ARE LISTING MIAMI AS THE LOCATION. A) REVIEW THE AC | | | SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM | | | DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON SHEET M-2.00 | | | IN TERMS OF CAPACITY. B) REFER TO SECTION C403.2.1 | | | FBC-14 ENERGY | | | | | | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL | | | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL | | | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER | | | SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE | | | ALSO SECTION C407.5.2.3 IF SUBMITTING A TOTAL BUILDING | | | PERFORMANCE ENERGY COMPLIANCE METHOD. | | | | | | 2) SHEETS M-1.09, M-2.00, & M-400: THE SPLIT AC | | | SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, & | | | AHU-B3 SYSTEMS. | | | | | | 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION | | | 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS | | | BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE | | | SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT | | | INSTALLATION INSTRUCTIONS. | | | | | | 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH | | | THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS | | | C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE | | | MATERIALS AND FORMS. | | | | | | 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT | | | OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE | | | CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES- | | | SECTION 401.4 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2017-07-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-07-20 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-07-20 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2017-07-20 09:40:23 | APPROVED UNDER 3RD REVIEW WITH PROVISOS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-07-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-07-14 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-07-14 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2017-07-14 14:58:54 | 1) SHT. A6.08 - THE CLEAR FLOOR SPACE FOR THE LAVATORY | | | SHALL BE CENTERED ON THE FIXTURE PER THE FAIR HOUSING | | | ACCESSIBILITY GUIDELINES.IN ADDITION, PROVIDE THE CLEAR | | | LENGTH X WIDTH DIMENSIONS OF ALL REQUIRED CLEAR FLOOR | | | SPACE DIMENSIONS FOR THE FIXTURES PER THE FHAG. | | | 2) SHT. A6.10 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR | | | SPACE FOR THE WATER CLOSET IN THE A1 UNIT MODEL. COMPLY | | | WITH FHAG. | | | 3) SHT. A 6.10 - UNITS A1 & B1 ARE SHOWN AS A TYPE "A" | | | & "B" DESIGN SPECIFICATION BATHROOM PER THE FHAG. IF | | | THESE ARE "UFAS" UNITS, IDENTIFY THEM AS SUCH. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) THE LETTTER FROM THE ARCHITECT REGARDING THE TOILET | | | FACILITIES FOR WORKERS IS VAGUE AND IS UNACCEPTABLE. | | | REFERENCE IS MADE TO A MAINTENANCE RESTROOM BUT THERE | | | IS NO MAINTENANCE RESTROOM IN BUILDING #1.SANITARY | | | FACILITIES FOR WORKERS IN THE MAINTENANCE AND TRASH | | | AREAS OF BUILDING #1 SHALL BE PROVIDED WITHIN 500 FEET | | | OF THESE AREAS. 2014 FBC SEC. 403.3.3 | | | 5) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET VENT | | | THE RISER SHOWS THE URINAL IN THE MEN'S RESTROOM ACROSS | | | FROM THE EXERCISE ROOM DISCHARGING INTO A VERTICAL WET | | | VENT ABOVE THE LAVATORY. THE URINAL IS TO BE INSTALLED | | | ON IT'S OWN STACK & VENTED. 2014 FBC SECS.912.1, | | | 912.1.1. 3RD REQUEST. | | | 6) SHT. P2.05B - THE MEN'S AND WOMEN'S RESTROOMS ACROSS | | | FROM THE EXERCISE ROOM ARE STILL MISLABELED.PLEASE | | | REVISE. | | | 7) THE LOCATION OF SANITARY RISERS S/24 & S/25 LOCATED | | | ACROSS FROM THE LAUNDRY ROOM ON SHT. P2.05B ARE | | | REVERSED AS TO THE LAYOUT ON SHT. P4.05, REFER TO | | | BUILDING # II, UNIT B1.2ND REQUEST. | | | 8) THE DETAIL FOR THE "PLENUM RATED" WATER METERS ON | | | SHEET P5.00 WILL REQUIRE ADDITIONAL DOCUMENTATION FROM | | | THE MANUFACTURER CWE. INFORMATION ON THEIR WEBSITE | | | INDICATES THEY DO NOT MANUFACTURE "PLENUM RATED WATER | | | METERS". THE MATERIAL COMPOSITION OF THE WATER METERS | | | SHALL MEET THE SMOKE- DEVELOPED INDEX AND FLAME SPREAD | | | RATING REQUIREMENTS OF ASTM E84 OR UL 723. THE FLAME | | | SPREAD INDEX SHALL BE NOT MORE THAN 25 AND THE | | | SMOKE-DEVELOPED INDEX SHALL NOT BE MORE THAN 50. 2014 | | | FBC - MECHANICAL SEC. 602.2.1.2ND REQUEST. | | | 9) SHT. P1.00 - THE ORIENTATION OF BUILDING # II IN | | | RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT | | | CORRELATE WITH THE ORIENTATION OF BULDING II ON SHT. | | | P2.05. CLARIFY. 2ND REQUEST. | | | | | | NOTE: THE ABOVE CONDITIONS ARE PROVISOS FOR APPROVAL OF | | | THESE PLANS FOR PLUMBING PLAN REVIEW. REVISED PLANS | | | SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE | | | ISSUANCE OF THE PLUMBING PERMIT. | | | T.LARGE, CHIEF PLUMBING INSPECTOR | | | JULY 14TH, 2017. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-06-20 |
Time |
6:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-06-20 |
Time |
05:44 |
Sent To |
|
|
| Notes |
| 2017-06-19 14:26:19 | 1) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND - | | | THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES | | | FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF | | | THE FIRST TOILET PAPER DISPENSER, NOT TO THE CENTERLINE | | | OF THE UNIT AS SHOWN. 2014 FBC-ACCESS. SEC.604.7. | | | 2) SHT.A6.15 - USABLE BATHROOM FIGURES - IDENTIFY ON | | | THE PLANS WHICH BATHROOMS ARE DESIGN SPECIFICATION "A" | | | OR "B" OF THE FHA. THIS SHEET HAS NOT BEEN REVISED AS | | | NOTED IN THE RESPONSE NARRATIVE. 2ND REQUEST. | | | 3) SUBMIT A SEPARATE LETTER FROM THE DESIGN | | | PROFESSIONAL OF RECORD STATING THAT SANITARY FACILITIES | | | FOR THE MAINTENANCE WORKERS ARE LOCATED WITHIN 500 FEET | | | OF THE TRASH ROOMS, MAINTENANCE ROOMS, ETC., PER 2014 | | | FBC-PLUMBING SEC.403.3.3. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR | | | SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST. | | | 5) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE | | | SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.2014 | | | FBC-PLUMBING.2ND REQUEST. | | | 6) ACCESS SHALL BE PROVIDED TO THE WATER SUPPLY VALVES | | | FOR THE STACKED WASHERS/DRYERS. I COULD NOT FIND THE | | | REVISED NOTE ON THE PLANS. CLARIFY. 2014 FPC | | | SEC.606.3.2ND REQUEST | | | 7) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET | | | VENT. 2014 FBC-PLUMBING SEC.912.1, 912.1.1. THE ADDED | | | STACK APPEARS TO HAVE A CLEANOUT ON IT BUT NO URINAL. | | | CLARIFY. | | | 8) SHT.P2.05 - THE MEN'S AND WOMENS RESTROOMS ACROSS | | | FROM THE EXERCISE ROOM ARE STILL MISLABELED.THE SAME | | | ISSUE OCCURS ON SHT. P2.05B AND ON THE ENLARGED PLAN ON | | | P2.05B AND ALSO THERE ARE NO PLUMBING FIXTURES SHOWN IN | | | THE MEN'S RESTROOM ON SHT. P2.05B. | | | 9) THE LOCATION OF THE SANITARY RISERS S/24 & S/25 ON | | | SHT. P2.05 B ARE REVERSED AS TO THE LAYOUT ON | | | SHT.P4.05. BUILDING # II, SEE UNIT B1. | | | 10) THE LOCATION OF SANITARY RISERS S/24 & S/25 ON | | | SHT.SHT. P2.05 A DOES NOT CORRELATE WITH THE LOCATION | | | SHOWN ON SHT. P4.05.THE RISERS ARE REVERSED. | | | 11) SUBMIT A DETAIL FOR THE SUB-WATER METERS IF THEY | | | ARE BEING INSTALLED IN THESE BUILDINGS. SHOW THE | | | LOCATION OF THE SUB-METERS IF APPLICABLE. MATERIALS | | | PLACED WITHIN RETURN AIR PLENUMS SHALL BE | | | NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING | | | A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED | | | IN ACCORDANCE WITH ASTM E84 OR UL 723.2014 | | | FBC-MECHANICAL SEC. 602.2.1. | | | 12) SHT. P4.06 - A SHUTOFF VALVE IS REQUIRED ON THE 2 | | | INCH WATER MAIN SUPPLY TO THE AMENITIES/LEASING AREA | | | PER 2014 FBC-PLUMBING SEC.606.2. | | | 13) SHT.P1.00 - THE ORIENTATION OF BUILDING II IN | | | RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT | | | CORRELATE WITH THE ORIENTATION OF BUILDING II ON SHT. | | | P2.05. CLARIFY. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-09-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-09-26 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-09-24 |
Time |
04:32 |
Sent To |
|
|
| Notes |
| 2016-09-24 09:18:23 | 1) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE | | | 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014) | | | VERSION OF THE FBC. REVISE THE NOTE. | | | 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE - | | | FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN | | | ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING | | | CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY | | | VOLUME. | | | 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT | | | (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE | | | DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR | | | B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS. | | | WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND | | | SEALED AS REQUIRED BY FL. ADDMIN. CODE 61G15-23.001. | | | 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER | | | AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF | | | THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE | | | PLAN/CIVIL DRAWINGS FOR THIS DRAIN. | | | 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL | | | COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE | | | OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF | | | DRAINING INTO THE GUTTERS. | | | 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND - | | | THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES | | | FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF | | | THE DISPENSER. FAC SEC. 604.7. | | | 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE | | | REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE | | | FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2, | | | 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE | | | DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH | | | THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14. | | | 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED | | | CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS, | | | AND APPLIANCES PER REQUIREMENT #7 OF THE FHA | | | GUIDELINES. | | | 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY | | | WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B. | | | 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS, | | | ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS | | | SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF | | | THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3. | | | 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE | | | LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG. | | | #2) ? CLARIFY. | | | 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE | | | CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC | | | CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR | | | THE CATCH BASINS. CLARIFY. | | | 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES | | | NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS | | | THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW | | | "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1. | | | 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS | | | ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1. | | | 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR | | | THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN | | | WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER | | | LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT | | | SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING | | | /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES | | | SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR | | | SHAFT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE | | | EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4. | | | 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE | | | SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2. | | | 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE | | | LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO | | | SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE | | | NOTE TO REFER TO CORRECT SHEET. | | | 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH | | | IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS | | | INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED. | | | CLARIFY. | | | 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC | | | SEC. 107.2.1 | | | 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR | | | THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3. | | | 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 ) | | | BUT THIS RISER IS NOT ON THE COOLECTION SYSTEM ON | | | SHT.P-4.01 - CLARIFY. | | | 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) - | | | THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON | | | THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE | | | PLAN VIEW ON SHT. P-2.00. CLARIFY. | | | 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT | | | SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY. | | | 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN | | | SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED | | | FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PERR | | | HOUR. 2014 FPC SEC.1106.1. | | | 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE | | | STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2 | | | & 1106.3. | | | 32) SHT. P-4.05 - A URINAL IS NOT PERNITTED ON A WET | | | VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN | | | THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE | | | WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP" | | | IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC. | | | 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE | | | MISLABELED. | | | 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT. | | | P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05. | | | SEE BUILDING #2 - UNIT B1 ( UNIT #115 ). | | | 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A | | | MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2. | | | 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE | | | NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE | | | SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON | | | SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF | | | THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE | | | LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 ( | | | A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY | | | COLLECTION ISOMETRIC ON SHT. P-4.05. | | | 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED | | | S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A). | | | SEE UNIT B1 (#100). | | | 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN | | | VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON | | | SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 ) | | | AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS | | | THERE IS A RISER S/23 FURTHER UPSTREAM. | | | 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS | | | IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE | | | DETAIL PER THE 2014 FPC SEC.405.8. | | | 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER | | | ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH | | | DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A | | | QUICK CLOSING VALVE. 2014 FPC SEC. 604.9. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-05 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-05 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2016-10-05 06:53:01 | ROOF INFORMATION NOT PROVIDED | | | | | | THE PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD AND SUBMITTED PRIOR TO INSTALLATION. THIS IS | | | TYPICALLY SUBMITTED WITH THE ROOF SUB PERMIT | | | APPLICATION. | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2017-08-10 13:01:56 | NEW SHEETS VERIFIED, ALL TRADES | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-08 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-08 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2017-08-08 09:23:35 | PAPER PAGES 6.11, 6.12, 6.13 | | | NEW SHEETS VERIFIED | | | ORIGINAL SOILS VERIFIED | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-28 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-28 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2017-07-28 07:33:09 | SOILS REPORT DATED 1/6/17 IS DIGITALLY SIGNED AND | | | SEALED; REQUESTED THAT THE OTHERS BE REMOVED (OR | | | VERSIONED). | | | | | | SIGNATURE REVIEW REQUIRED FOR REVIEW CYCLE #5 | | | | | | | | | | | | | | 2017-07-20 12:56:22 | MECHANICAL DIG/SIGS VERIFIED. CCOLE- 7/20/2017 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2017-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-19 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-19 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2017-07-17 09:34:49 | MECH DIG/SIGS VERIFIED- CCOLE | | | 7/17/17 | | 2017-07-12 13:05:00 | SIGNATURE REVIEW REVISED 7/12/17, S.HILL | | | | | | NEW SHEETS SUBMITTED FOR 4TH REVIEW CYCLE NEED REVIEW, | | | IF APPLICABLE | | | | | | THE SOILS IS NOT DIGITALLY SIGNED AND SEALED. EITHER | | | UPLOAD A DIGITALLY SIGNED AND SEALED SOILS REPORT OR | | | THE ORIGINAL PAPER SIGNED AND SEALED SOILS REPORT WILL | | | BE REQUIRED TO BE SUBMITTED PRIOR TO PERMIT ISSUANCE. | | | | | | CIVIL PAGES OK | | | STRUCTUAL PLAN PAGES OK | | | ARCHITECTURAL PLAN PAGES OK | | | FIRE ALARM, FIRE PROTECTION PAGES OK | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2017-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-16 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-06-16 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2017-06-16 08:25:27 | ELECTRICAL SHEETS APPROVED. | | 2016-08-17 15:14:09 | SIGNATURE REVIEW REVISED 6/23/17, S.HILL | | | | | | NEW SHEETS SUBMITTED FOR 3RD REVIEW CYCLE NEED REVIEW | | | | | | STRUCTURAL REPORT (SUPPORTING DOCUMENTS FOLDER) | | | PREPARED BY ALISINA MALEK, PE HAS A DIGITAL SIGNATURE | | | WITH AN ERROR. CORRECT AND RESUBMIT. | | | | | | THE SOILS IS NOT DIGITALLY SIGNED AND SEALED. EITHER | | | UPLOAD A DIGITALLY SIGNED AND SEALED SOILS REPORT OR | | | THE ORIGINAL PAPER SIGNED AND SEALED SOILS REPORT WILL | | | BE REQUIRED TO BE SUBMITTED PRIOR TO PERMIT ISSUANCE. | | | | | | CIVIL PAGES OK | | | STRUCTUAL PLAN PAGES OK | | | ARCHITECTURAL PLAN PAGES OK | | | FIRE ALARM, FIRE PROTECTION PAGES OK | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
5 |
Status |
N |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-10 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-10 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2017-08-10 13:07:25 | APPLICANT ELECTS TO USE CITY INSPECTORS AT THIS TIME | | | PER KEN CONRAD, RESIDENT INSPECTOR IS VOLUNTARY FOR | | | THIS BUILDING (NOT THRESHOLD) |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
F |
Date |
2017-08-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-08-07 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-08-07 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2017-08-07 14:37:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | WASEEN QUADRI, PE HAS BEEN APPROVED BY K.CONRAD | | | GISELLE BARRERA, BN7157 HAS BEEN PRELIMINARILY APPROVED | | | BY K.CONRAD PENDING RECEIPT OF RESUME | | | | | | AS RESIDENT INSPECTOR IS VOLUNTARY, IT IS POSSIBLE THAT | | | THIS PERMIT CAN BE ISSUED WITH THE UNDERSTANDING THAT | | | ALL INSPECTIONS WILL BE PERFORMED BY CITY STAFF UNTIL | | | APPLICANT PROVIDES ALL REQUIRED RESIDENT INSPECTOR | | | DOCUMENTS. | | | | | | GENERAL COMMENT: NOTARIAL CERTIFICATES AND NOTARY | | | PRACTICE TO BE IN ACCORDANCE WITH LAW, WHETHER | | | SPECIFICALLY MENTIONED IN THIS LIST OR NOT. NEARLY | | | EVERY PAGE HAS AN ERROR. THIS INFORMATION (ACCEPTABLE | | | METHODS FOR NOTARIAL CERTIFICATE, OTHER REQUIREMENTS) | | | IS READILY AVAILABLE ONLINE. TO EXPEDITE REVIEW, PRIOR | | | TO SUBMITTING THE AGREEMENTS TO ME FOR REVIEW, | | | APPLICANT IS TO CONFIRM THAT THIS BASIC INFORMATION IS | | | CORRECT. | | | | | | PLEASE RESOLVE THE FOLLOWING ISSUES WITH DOCUMENT "B.1 | | | SPECIAL INSPECTOR AGREEMENT.PDF" (SI AGREEMENT FOR | | | PERMIT #16070916): | | | | | | 1. AS DISCUSSED WITH CHARLES DURING A PRELIMINARY | | | REVIEW OF THE SPECIAL INSPECTOR AGREEMENT, THE | | | INSPECTOR'S SIGNATURE IS REQUIRED TO BE NOTARIZED. | | | GISELLE BARRERA HAS SIGNED THE AGREEMENT, BUT HER | | | SIGNATURE IS NOT NOTARIZED. | | | | | | THE PAGE WITH WASEEM QUADRI, PE'S SIGNATURE MAY REMAIN | | | IN THE PACKAGE. ADD ANOTHER PAGE WITH GISELLE BARRERA'S | | | NOTARIZED SIGNATURE. ENGINEER SIGNS AT THE TOP OF EACH | | | INSPECTOR PAGE. | | | | | | 2. THE NOTARIAL CERTIFICATE FOR CONTRACTOR STATES THAT | | | "LEN RICARDO SAEZ" SIGNED, BUT MR. SAEZ APPEARS TO BE | | | THE NOTARY, NOT THE CONTRACTOR. PROVIDE A PERMIT | | | APPLICATION, NOTARIZED BY THE CONTRACTOR (THIS | | | APPLICATION IS STILL "TBD" IN OUR SYSTEM), AND PROVIDE | | | THE CONTRACTOR'S NOTARIZED SIGNATURE ON THE SPECIAL | | | INSPECTOR AGREEMENT. | | | | | | 3. PLEASE REMOVE THE FORM "AFFIDAVIT CERTIFICATE OF | | | CODE COMPLIANCE". THIS IS REQUIRED TO BE SUBMITTED | | | AFTER CONSTRUCTION, BEFORE C.O. | | | | | | 4. I AM UNABLE TO LOCATE A RESUME FOR THE PROPOSED | | | INSPECTOR, GISELLE BARRERA. | | | | | | 5. I AM UNABLE TO LOCATE A RESUME OF EXPERIENCE FOR THE | | | PROPOSED CONTRACTOR, CHRISTOPHER MORAN, LYNX | | | CONSTRUCTION MANAGEMENT. | | | | | | 6. ONLY ONE INSPECTOR HAS SIGNED THE AGREEMENT. IN OUR | | | EXPERIENCE, A BACKUP INSPECTOR IS RECOMMEDED AS NO | | | OTHER INSPECTOR WILL BE PERMITTED ON THE JOB WITHOUT | | | PRIOR APPROVAL. AS DISCUSSED WITH CHARLES, SOME | | | COMPANIES HAVE ALL OF THEIR (LICENSED) EMPLOYEES SIGN | | | THE AGREEMENT. WHETHER THIS WILL BE A RECOMMENDATION OR | | | A REQUIREMENT WILL BE AT KEN CONRAD'S DISCRETION. NOTE | | | THAT ADDITIONAL INSPECTORS MAY SIGN ON AT ANY TIME, BUT | | | PRIOR TO PERFORMING INSPECTIONS ON THIS PROJECT. | | | | | | 7. AS DISCUSSED, A COMPLETE THRESHOLD PACKAGE IS | | | REQUIRED. AFTER A COMPLETE PACKAGE IS PROVIDED, THE | | | PACKAGE WILL BE FORWARDED TO KEN CONRAD FOR APPROVAL. | | | | | | IF INFORMATION IS SENT VIA EMAIL RATHER THAN VIA | | | RESUBMITTAL, PLEASE SEND A COMPLETE PACKAGE - SIGNED | | | AGREEMENTS, RESUMES FOR ALL PARTIES. THE COMPLETE | | | PACKAGE WILL BE FORWARDED TO KEN CONRAD. HE DOES NOT | | | HAVE ACCESS TO PROJECTDOX. | | | | | | (NOTE - THRESHOLD INSPECTION PLAN OK, LOCATED IN | | | SUPPORTING DOCUMENTS "THRESHOLD INSPECTION GUID LINE") | | | | | | *************************************************** | | | REVIEW FOR DOCUMENTS "B.2 RESIDENT INSPECTOR | | | AGREEMENT.PDF", "B.3 RESIDENT INSPECTOR AGREEMENT", | | | "B.4 RESIDENT INSPECTOR AGREEMENT". | | | | | | 1. CLARIFY RELATIONSHIP OF YASMIN K QUADRI (NOTARY) TO | | | WASEEM QUADRI, PE. THIS MAY BE DONE WITH A LETTER WHICH | | | DOES NOT NEED TO BE NOTARIZED, BUT PLEASE INCLUDE IN | | | THE AGREEMENT, FLORIDA STATUTE 117.107(11). | | | | | | 2. NOTARIAL CERTIFICATE FOR THE ENGINEER IS INCORRECT; | | | THIS LACKS A NAME ON THE LINE WHICH STATES WHO SIGNED | | | THE DOCUMENT. | | | | | | 3. NOTARIAL CERTIFICATE FOR THE CONTRACTOR IS | | | INCORRECT; NOTARY'S NAME IS INCLUDED RATHER THAN | | | CONTRACTOR'S NAME. CONTRACTOR'S NOTARIZED SIGNATURE IS | | | REQUIRED FOR THE AGREEMENT. | | | | | | 4. OWNER SIGNATURE OK. | | | | | | 5. ONLY THE ENGINEER, WASEEM QUADRI, PE HAS SIGNED THE | | | RESIDENT INSPECTOR AGREEMENT. CONFIRM THAT NO OTHER | | | INDIVIDUALS WITH BE PERFORMING INSPECTIONS FOR THIS | | | PERMIT, OR ADD ANY PROPOSED INSPECTORS TO THE | | | AGREEMENT. USE PAGE 1 FOR EACH INSPECTOR. A RESUME IS | | | REQUIRED FOR EACH. | | | | | | 6. A RESIDENT INSPECTOR INSPECTION PLAN IS REQUIRED. IT | | | IS POSSIBLE THAT THIS MAY BE A PROVISO ITEM. | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2017-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-28 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-28 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2017-07-28 10:38:20 | IF AVAILABLE, PLEASE UPLOAD THE THRESHOLD PACKAGE TO | | | PROJECTDOX WHEN RESUBMITTING. | | | | | | SI AGREEMENT SIGNED BY ALL PARTIES | | | RESUMES FOR SI, INSPECTORS, CONTRACTOR | | | COPIES OF LICENSES (OR PRINT PAGE FROM | | | WWW.MYFLORIDALICENSE.COM) | | | | | | THIS MAY ALSO BE SENT VIA EMAIL ([email protected]). AFTER | | | RECEIPT OF THE COMPLETE PACKAGE, IT WILL BE FORWARDED | | | TO KEN CONRAD FOR FINAL APPROVAL. PRIOR TO | | | CONSTRUCTION, SCHEDULE A PRE-CONSTRUCTION MEETING WITH | | | CONTRACTOR, KEN CONRAD, AND SI. | | | | | | PLEASE ADVISE, IS APPLICANT USING A RESIDENT INSPECTOR | | | FOR THE NON-THRESHOLD BUILDINGS? IF YES, PLEASE PROVIDE | | | THAT AGREEMENT AS WELL. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2017-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-07-12 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-07-12 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2017-07-12 13:03:17 | ****CORRECTIONS**** | | | THRESHOLD INSPECTOR REQUIRED FOR PERMIT 16070916 | | | (BUILDING 1; 4 STORIES) ONLY | | | RESIDENT INSPECTOR FOR OTHER BUILDINGS RECOMMENDED BUT | | | OPTIONAL | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PERMIT INCLUDES FOUR BUILDINGS: | | | | | | PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES | | | (BUILDING 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES | | | (BUILDING 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 4) | | | | | | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) | | | | | | 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A | | | THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA | | | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: | | | | | | A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE | | | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO | | | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING | | | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY | | | THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY | | | THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS | | | 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED | | | TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT | | | ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL | | | INFORMATION. | | | FORMS WERE SENT TO: [email protected] ON 9/29/16. | | | | | | C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW | | | BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE | | | RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY | | | SAMANTHA HILL), 561-805-6666, [email protected], | | | [email protected] | | | | | | ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE | | | CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN | | | THE SPECIAL INSPECTOR AGREEMENT. | | | | | | D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO | | | KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL | | | ([email protected], [email protected]). | | | | | | E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE | | | SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL | | | DOCUMENTS. | | | | | | F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. CONFIRM | | | ALL APPLICABLE PAGES INCLUDE THE REQUIRED STATEMENT. | | | | | | 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE | | | ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD AND | | | THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE | | | SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE | | | ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO | | | INSPECTION. THE CITY APPROVED (CITY STAMPED) | | | SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE | | | JOB AT THE TIME OF INSPECTION. | | | | | | 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL | | | DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD | | | BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. | | | | | | 5. SPECIAL INSPECTOR REQUIRED FOR BUILDING 1. DEPENDING | | | ON HOW AGGRESSIVE THE CONSTRUCTION SCHEDULE IS, | | | APPLICANT MAY WANT TO CONSIDER USING THE SAME INSPECTOR | | | FOR BUILDINGS 2, 3, 4 (PER KEN CONRAD, CHIEF BUILDING | | | INSPECTOR). PLEASE CALL ME IF YOU WISH TO DISCUSS. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2016-09-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-09-29 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-09-17 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2016-09-29 06:40:15 | ****CORRECTIONS**** | | | THRESHOLD INSPECTOR REQUIRED FOR PERMIT 16070916 | | | (BUILDING 1; 4 STORIES) ONLY | | | RESIDENT INSPECTOR FOR OTHER BUILDINGS RECOMMENDED BUT | | | OPTIONAL | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THIS PERMIT INCLUDES FOUR BUILDINGS: | | | | | | PERMIT #16070916 906 17TH STREET - 68 UNITS, 4 STORIES | | | (BUILDING 1) | | | PERMIT #16071059 808 17TH STREET - 45 UNITS, 3 STORIES | | | (BUILDING 2) | | | PERMIT #16071058 811 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 3) | | | PERMIT #16070880 805 15TH STREET - 6 UNITS, 1 STORY | | | (BUILDING 4) | | | | | | GOVERNING CODE: FBC 5TH EDITION (FBC 2014) | | | | | | 1. FLORIDA STATUTE 553.71, THIS BUILDING QUALIFIES AS A | | | THRESHOLD BUILDING; ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SF IN AREA | | | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 2. AS A THRESHOLD BUILDING, THE FOLLOWING IS REQUIRED: | | | | | | A. THRESHOLD INSPECTION PLAN; FS 553.79(5)(A), CITY OF | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1. THE | | | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO | | | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING | | | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY | | | THE ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO AND APPROVED BY | | | THE ENFORCING AGENCY BEFORE THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | | | B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FS | | | 553.79(5)(A) TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES, NOTARIZED AND RETURNED | | | TO THIS OFFICE, REVIEWED AND APPROVED PRIOR TO PERMIT | | | ISSUANCE. CONTACT KEN CONRAD, MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM, AT 561-805-6666 FOR ADDITIONAL | | | INFORMATION. | | | FORMS WERE SENT TO: [email protected] ON 9/29/16. | | | | | | C. SPECIAL INSPECTOR RESUME': PROVIDE A RESUME' OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECTS FOR REVIEW | | | BY THE BUILDING OFFICIAL OR HIS DESIGNEE. AFTER THE | | | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. | | | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED | | | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. THE | | | RESUME' IS TO BE SUBMITTED TO KEN CONRAD (AND COPY | | | SAMANTHA HILL), 561-805-6666, [email protected], | | | [email protected] | | | | | | ALL PROSPECTIVE INSPECTORS ARE TO BE APPROVED BY THE | | | CHIEF BUILDING INSPECTOR AND ALL ARE REQUIRED TO SIGN | | | THE SPECIAL INSPECTOR AGREEMENT. | | | | | | D. CONTRACTOR RESUME': PROVIDE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO | | | KEN CONRAD, (PLEASE COPY SAMANTHA HILL) VIA E-MAIL | | | ([email protected], [email protected]). | | | | | | E. PERMIT DOCUMENTS: PAPER SUBMITTALS REQUIRE THREE | | | SIGNED AND SEALED (IF APPLICABLE) ORIGINAL SETS OF ALL | | | DOCUMENTS. | | | | | | F. FS553.79(7)(D)ALL PLANS FOR THE BUILDING WHICH ARE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633. CONFIRM | | | ALL APPLICABLE PAGES INCLUDE THE REQUIRED STATEMENT. | | | | | | 3. ADVISORY ONLY; PER FS 553.79, ALL SHORING/RE-SHORE | | | ENGINEERING IS TO BE REVIEWED BY ENGINEER OF RECORD AND | | | THREE SIGNED AND SEALED ORIGINAL SETS ARE TO BE | | | SUBMITTED FOR PLAN REVIEW. THE SHORING/RESHORE | | | ENGINEERING IS TO BE REVIEWED AND APPROVED PRIOR TO | | | INSPECTION. THE CITY APPROVED (CITY STAMPED) | | | SHORING/RE-SHORE ENGINEERING IS TO BE AVAILABLE ON THE | | | JOB AT THE TIME OF INSPECTION. | | | | | | 4. ADVISORY ONLY; PRIOR TO INSTALLATION, A GUARD RAIL | | | DETAIL IS TO BE SUBMITTED FOR PLAN REVIEW. THIS SHOULD | | | BE SUBMITTED WITH THE SHORING/RESHORE ENGINEERING. | | | | | | 5. SPECIAL INSPECTOR REQUIRED FOR BUILDING 1. DEPENDING | | | ON HOW AGGRESSIVE THE CONSTRUCTION SCHEDULE IS, | | | APPLICANT MAY WANT TO CONSIDER USING THE SAME INSPECTOR | | | FOR BUILDINGS 2, 3, 4 (PER KEN CONRAD, CHIEF BUILDING | | | INSPECTOR). PLEASE CALL ME IF YOU WISH TO DISCUSS. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2017-08-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-08-10 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-08-10 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2017-08-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-08-08 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-08-08 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2017-08-08 13:00:51 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.08.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. AT THE PROPOSED CROSSWALK BETWEEN BUILDINGS #2 AND | | | #4, THE LANDSCAPE ISLANDS ON BOTH SIDES OF THE SIDEWALK | | | SHALL BE EXPANDED TO A MINIMUM OF FIVE (5) FEET IN | | | WIDTH. ADDITIONALLY, THE SOUTHERN-MOST PROPOSED GUMBO | | | LIMBO SHALL BE PLACED IN THE ISLAND OPPOSITE THE | | | PROPOSED TRAFFIC SIGN. | | | | | | 2. PURSUANT TO RESOLUTION NO. 187-16, ALL IMPROVEMENTS | | | (INCLUDING UTILITIES AND REQUIRED SCREENING) SHALL BE | | | MODIFIED TO COMPLY WITH THE MAXIMUM HEIGHT PERMITTED | | | WITHIN THE VISIBILITY TRIANGLE. THIS COMMENT WAS ISSUED | | | PREVIOUSLY AND HAS NOT BEEN FULLY ADDRESSED. THE | | | TRANSFORMER AND ASSOCIATED SCREENING LOCATED ON THE | | | NORTHWEST CORNER OF DIVISION AVENUE AND 15TH STREET | | | (L.A. KIRKSEY) SHALL BE RELOCATED TO COMPLY WITH SUCH | | | PROVISION. | | | | | | 3. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS | | | AND OTHERS CONFLICT WITH LANDSCAPING. THIS COMMENT WAS | | | ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. | | | | | | 4. THE LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A | | | SEPARATE LANDSCAPE PERMIT APPLICATION. THIS COMMENT WAS | | | ISSUED PREVIOUSLY AND HAS NOT BEEN ADDRESSED. PLEASE | | | NOTE THAT THE LANDSCAPE PLANS SUBMITTED WITH THE | | | BUILDING PERMIT PLANS DO NOT MATCH THE LATEST SUBMITTAL | | | MADE FOR THE MINOR PD AMENDMENT. ALL PLANS NEED TO BE | | | CONSISTENT. | | | | | | 5. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | THIS COMMENT WAS ISSUED PREVIOUSLY AND HAS NOT BEEN | | | ADDRESSED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2017-07-31 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-07-31 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-07-31 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2017-07-31 11:33:16 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.31.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING THAT OCCURS BETWEEN THE HANDICAP | | | SPACES (NORTH OF BUILDINGS III AND IV) SHOULD BE | | | RECONFIGURED TO PROVIDE AN APPROPRIATE MID-BLOCK | | | CROSSING WITH LANDSCAPE ISLANDS, ETC. | | | | | | 6. CIVIL PLANS DO NOT REFLECT THE TWO (2) TREE GRATES | | | PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE | | | LEASING CENTER. | | | | | | 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 8. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF WALKWAYS | | | AND OTHER CONFLICT WITH LANDSCAPING. | | | | | | 9. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE | | | ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE | | | PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE | | | SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2017-07-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-07-17 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-07-17 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2017-07-17 13:04:24 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.17.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY | | | ENTRANCE SHOULD BE REMOVED - PEDESTRIANS SHOULD USE THE | | | CROSSING AT THE RIGHT-OF-WAY LINE. WHILE THE SIDEWALK | | | HAS BEEN RELOCATED, A DIVIDER MEDIAN HAS BEEN REMOVED | | | FROM THE ROW OF PARKING; PURSUANT TO THE CITY'S ZLDRS, | | | NO MORE THAN 10 CONIGUOUS PARKING SPACES SHALL OCCUR | | | WITH OUT THIS INSTALLATION OF A 5 FOOT WIDE LANDSCAPED | | | DIVIDER MEDIAN WITH SHADE TREE. | | | | | | 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE | | | LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE | | | INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO | | | EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK. | | | | | | 7. PAVING PLANS DO NOT REFLECT THE TWO (2) TREE GRATES | | | PROPOSED ALONG THE ON-STREET PARKING, SOUTHWEST OF THE | | | LEASING CENTER. | | | | | | 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND | | | LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM | | | THE PROJECT. | | | | | | 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE | | | FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR | | | EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT | | | REFLECTED ON THE ELEVATION. | | | | | | 11. ELEVATION D OF BUILDING II INDICATES THAT THE | | | WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM, | | | LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH | | | ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO | | | THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A | | | DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE | | | FIXED STOREFRONT WINDOWS. | | | | | | 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE | | | VARIOUS RETAINING WALLS? | | | | | | 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF | | | WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE | | | CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE | | | ADDRESSED. | | | | | | 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A | | | TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A | | | LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL | | | INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2017-06-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-06-14 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-06-14 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2017-06-14 10:18:47 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 06.14.2017 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 2. AS THE PLANS HAVE BEEN REVISED SINCE THE ADOPTION OF | | | RESOLUTION NO. 187-16, A MINOR AMENDMENT TO THE DUNBAR | | | VILLAGE RPD SHALL BE SUBMITTED TO AND APPROVED BY THE | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION. IT | | | SEEMS THAT THE FOLLOWING MODIFICATIONS HAVE BEEN | | | MADE... | | | | | | A. REMOVAL OF THE POOL. | | | | | | B. RELOCATION OF STEPS INTO UNITS FACING DIVISION | | | AVENUE ? IT WAS EXPRESSED TO STAFF THAT THE ISSUES THAT | | | AROSE WITH SILVER PALM PLACE WOULD NOT BE EXPERIENCED | | | AT ROYAL PALM PLACE, AND THAT THE LOCATION OF THE STEPS | | | WOULD REMAIN AT THE ENTRANCES INTO THE UNITS. | | | | | | C. MODIFICATION TO ON-STREET PARKING ALONG INTERNAL | | | NORTH/SOUTH ROAD. | | | | | | D. REDUCTION IN THE AMOUNT OF PARKING (SEVERAL | | | ON-STREET PARKING SPACES NO LONGER PROPOSED). | | | | | | E. MODIFICATION TO THE INGRESS/EGRESS POINT AT L.A. | | | KIRKSEY (15TH STREET). HAS THIS BEEN APPROVED BY | | | ENGINEERING? I THOUGHT THIS WAS TO BE A RIGHT-IN AND | | | RIGHT-OUT ONLY. | | | | | | 3. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 4. THE LOCATION OF ALL IMPROVEMENTS, INCLUDING BUT NOT | | | LIMITED TO ABOVE-GROUND UTILITIES AND REQUIRED | | | SCREENING, SHALL BE MODIFIED ACCORDINGLY TO COMPLY WITH | | | MAXIMUM HEIGHT PERMITTED WITHIN THE VISIBILITY | | | TRIANGLE. | | | | | | 5. SIDEWALK CROSSING AT DIVISION AVENUE DRIVEWAY | | | ENTRANCE SHOULD BE REMOVED?PEDESTRIANS SHOULD USE THE | | | CROSSING AT THE RIGHT-OF-WAY LINE. | | | | | | 6. LOCATION OF THE MECHANICAL EQUIPMENT NORTH OF THE | | | LEASING OFFICE, IMMEDIATELY ADJACENT TO THE ENTRANCE | | | INTO THE EXERCISE ROOM? MECHANICAL EQUIPMENT IS NOT TO | | | EXTEND MORE THAN FOUR (4) FEET INTO THE SETBACK. | | | | | | 7. SITE PLAN, PAVING PLANS, ETC. DO NOT REFLECT THE TWO | | | (2) TREE GRATES PROPOSED ALONG THE ON-STREET PARKING, | | | SOUTHWEST OF THE LEASING CENTER. | | | | | | 8. POOL EQUIPMENT IS STILL BEING SHOWN ON THE SITE AND | | | LANDSCAPE PLANS, DESPITE THE REMOVAL OF THE POOL FROM | | | THE PROJECT. | | | | | | 9. THERE?S A LABEL ON THE SITE PLAN THAT INCORRECTLY | | | STATES THAT THERE ARE 143 OFF-STREET PARKING SPACES AND | | | 22 ON-STREET PARKING SPACES?.THE DATA TABLE INDICATES | | | ONLY 156 PARKING SPACES. | | | | | | 10. ELEVATION D OF BUILDING II DOES NOT MATCH THE | | | FLOOR/SITE PLAN. THE PLANS INDICATE A DOUBLE-DOOR | | | EXITING THE EXERCISE ROOM ONTO 17TH STREET; THIS IS NOT | | | REFLECTED ON THE ELEVATION. | | | | | | 11. ELEVATION D OF BUILDING II INDICATES THAT THE | | | WINDOWS ALONG NORTH FA?ADE OF THE EXERCISE ROOM, | | | LEASING CENTER, ETC. ARE S-1 TYPE STOREFRONTS, WHICH | | | ARE IDENTIFIED AS HAVING A DOOR OPENING. ACCORDING TO | | | THE SITE PLAN, ONLY ONE OPENING IS TO HAVE A | | | DOUBLE-DOOR, WHILE THE OTHER OPENINGS APPEAR TO BE | | | FIXED STOREFRONT WINDOWS. | | | | | | 12. WHAT IS THE PROPOSED TREATMENT FOR THE FACES OF THE | | | VARIOUS RETAINING WALLS? | | | | | | 13. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 14. SOME LIGHT POLES ARE SHOWN IN THE MIDDLE OF | | | WALKWAYS, PARKING AREAS, ETC. ENSURE THAT ALL PLANS ARE | | | CONSISTENT AND THAT CONFLICTS AND INCONSISTENCIES ARE | | | ADDRESSED. | | | | | | 15. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A | | | TREE ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A | | | LANDSCAPE PERMIT. THE TREE ALTERATION PERMIT SHALL | | | INCLUDE A TREE SURVEY OF EXISTING TREES TO BE REMOVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-03 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-10-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-10-03 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2016-10-03 14:24:09 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.03.2016 | | | PERMIT NO.: 16070880, 16070916, 16071058, 16071059 | | | ADDRESS: 805 15TH STREET, 906 17TH STREET, 811 15TH | | | STREET, 808 17TH STREET | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: NEW MULTIFAMILY | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL ISSUES REGARDING GRADING, BUILDING ELEVATION, | | | ETC. THAT HAVE BEEN DISCUSSED IN RECENT MEETINGS SHALL | | | BE SATISFACTORILY ADDRESSED. | | | | | | 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. IF THE DESIRE IS TO | | | OBTAIN CERTIFICATES OF OCCUPANCY AT DIFFERENT TIMES FOR | | | EACH BUILDING, A LANDSCAPE PHASING PLAN MAY NEED TO BE | | | DEVELOPED TO DISTINGUISH WHICH LANDSCAPING IS REQUIRED | | | TO BE INSTALLED WITH EACH BUILDING. STAFF IS WILLING TO | | | DISCUSS THIS ISSUE FURTHER IF NEEDED. | | | | | | 3. AS THE LANDSCAPE PLANS HAVE BEEN REVISED SINCE THE | | | ADOPTION OF RESOLUTION NO. 187-16, A MINOR AMENDMENT TO | | | THE DUNBAR VILLAGE RPD SHALL BE SUBMITTED TO AND | | | APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ? | | | PLANNING DIVISION. | | | | | | 4. ON THE LANDSCAPE PLANS, THERE ARE NUMEROUS CONFLICTS | | | BETWEEN PROPOSED LANDSCAPING AND PROPOSED SITE | | | LIGHTING. ADDITIONALLY, SOME LIGHT POLES ARE SHOWN IN | | | THE MIDDLE OF WALKWAYS, PARKING AREAS, ETC. ENSURE THAT | | | ALL PLANS ARE CONSISTENT AND THAT CONFLICTS AND | | | INCONSISTENCIES ARE ADDRESSED. | | | | | | 5. PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT FOR | | | BUILDINGS #3 & #4 (STRUCTURES FRONTING 15TH STREET), | | | VARIATION SHALL BE PROVIDED TO DIFFERENTIATE THEM FROM | | | ONE ANOTHER. SUCH VARIATIONS DO NOT HAVE TO BE | | | SUBSTANTIAL STRUCTURAL MODIFICATIONS, BUT MAY CONSIST | | | OF DIFFERENT ARCHITECTURAL DETAILING, RAILINGS, | | | COLUMNS, ETC. VARIATIONS SHOULD BE PROVIDED BETWEEN | | | EACH 3-UNIT CLUSTER. | | | | | | 6. THE APPLICANT/PROPERTY OWNER SHALL SUBMIT FOR A TREE | | | ALTERATION PERMIT, PRIOR TO THE ISSUANCE OF A LANDSCAPE | | | PERMIT. THE TREE ALTERATION PERMIT SHALL INCLUDE A TREE | | | SURVEY OF EXISTING TREES TO BE REMOVED. | | | | | | 7. ALL SITE LIGHTING SHALL BE DESIGNED SO AS NOT TO | | | EXCEED 0.5 FOOTCANDLES, IN ACCORDANCE WITH SECTION | | | 94-310(D), WHEN MEASURED AT THE BOUNDARY OF THE RPD. | | | | | | 8. ALL PLANS SHALL ACCURATELY REFLECT VISIBILITY | | | TRIANGLES IN ACCORDANCE WITH THE REQUIREMENTS OF | | | SECTION 94-305(E). THE LOCATION OF ALL IMPROVEMENTS, | | | INCLUDING BUT NOT LIMITED TO ABOVE-GROUND UTILITIES AND | | | REQUIRED SCREENING, SHALL BE MODIFIED ACCORDINGLY TO | | | COMPLY WITH MAXIMUM HEIGHT PERMITTED WITHIN THE | | | VISIBILITY TRIANGLE. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy