Plan Review Details - Permit 16070980
Plan Review Stops For Permit 16070980
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-10 Cont ID  
Sent By jwitmer Date 2016-09-10 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2016-09-10 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By jwitmer Date 2016-08-02 Time 09:40 Rev Time 0.00
Received By jwitmer Date 2016-08-02 Time 07:15 Sent To  
Notes
2016-08-02 09:40:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070980
 ADD: 7402 S. DIXIE HWY. SUITE # 7434
 CONT: PRESTIGE CONSTRUCTION
 TEL: 561-844-3563
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 02/ 2016
 ACTION: DENIED
  
 1) SHEET A-2 CODE INFORMATION INDICATES THE 2014
 EXISTING BUILDING CODE. THE PLANS DO NOT MENTION THIS
 IS A PARTIAL CHANGE OF OCCUPANCY. THE PLANS WILL NEED
 TO SHOW COMPLIANCE WITH THE 2014 FBC-EXISTING BUILDING
 CODE 1001.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 1012 SHALL APPLY.
  
 2) 2014 EXISTING BUILDING CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 2014 EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
 PLEASE SHOW A BREAK DOWN LIST OF THE COST ASSOCIATED
 WITH SECTION 202.4.1 DISPROPORTIONATE COST, $110,000.00
 X 20% = $22,000.00 IN VALUE FOR ACCESSIBLE UPGRADES.
 PLEASE REVIEW THE LIST BELOW WHERE THE FUNDS ARE TO BE
 SPENT AND IN WHAT ORDER.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 3) SHEET A2 SHOWS A NEW EGRESS DOOR AT THE REAR OF THE
 TENANT SPACE. ON THE EXTERIOR A NEW DOOR LANDING AND
 RAMPS ARE PROPOSED. PLEASE NOTE THE RAMP PROTRUDES 48
 INCHES FROM THE BUILDING. PLEASE REVIEW THE 2014
 FBC-ACC. CODE SECTION 404.2.4 MANEUVERING CLEARANCES
 AND FIGURE ( E ). FIGURE ( E ) REQUIRES THE RAMP TO
 PROTRUDE 54 INCHES AWAY FROM THE BUILDING AND THE
 LANDING IS TO BE LEVEL FOR 42 INCHES PAST THE LATCH
 SIDE OF THE DOOR WAY. PLEASE NOTE FOR THIS TO BE AN
 ACCESSIBLE EXIT THE EXTERIOR LANDING WILL NEED TO BE
 EXTENDED TO A SIDEWALK AND TO THE PUBLIC WAY (GOOGLE
 MAPS). 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE
 MEANS OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION
 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF
 EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 4A) THE NEW DOOR OPENING # 1 THERE MAY BE 2 CONCERNS
 NOT CLEARLY ADDRESSED IN THE PLANS. THE DOOR SCHEDULE
 DOES INDICATE THE USE OF PANIC HARDWARE AND A CHAIN
 DOOR STOP. PLEASE NOTE IF A DOOR CLOSER IS TO BE
 INSTALLED THEN COMPLIANCE WITH THE ACCESS. CODE FIGURE
 404.2.4.1 ( C ) WOULD REQUIRE 12 INCHES CLEARANCE ON
 THE INTERIOR SIDE OF THE DOOR AT THE LATCH SIDE.
  
 4B) THE OTHER ISSUE IS THE DISTANCE FROM THE DOOR FACE
 ON THE INTERIOR SIDE OF THE DOOR TO THE FINISH WALL AND
 COMPLIANCE WITH SECTION 404.2.4.3.
  
 5) SHEET A2 THE NEW DOOR # 1 PLEASE PROVIDE THE WIND
 DESIGN CRITERIA. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A)
 EXTERIOR DOORS.
  
 6B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A2 THE PROPOSED CLOSET DOOR # 2 SWINGS INTO
 THE REQUIRED EGRESS PATH, DOORS IN ANY POSITION SHALL
 NOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 2014 FBC-B 1005.7.1.
  
 8) SHEET A2 THE EXISTING DOOR THAT LEADS FROM THE
 DINING AREA TO THE REMODELED DISH WASH ROOM IS MISSING
 THE 18INCHES ON THE LATCH SIDE OF THE DOOR. SEE 2014
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
  
 9A) SHEET A2 PLEASE SHOW COMPLIANCE WITH THE 2014
 ACCESS. CODE SECTION 226. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 9B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 9C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 9D) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES. PLEASE NOTE THE NEWLY
 PROPOSED COUNTERTOP AT 42 INCHES WILL NEED TO SHOW AN
 ACCESSIBLE COUNTER (DISPERSION).
  
 10) SHEET A2. PLEASE INDICATE THE 3 FRONT ENTRY DOORS
 ARE AT GRADE AND WILL MEET THE REQUIREMENTS FOR AN
 ACCESSIBLE ENTRANCE. 2014 FBC-ACCESSIBILITY CODE 207.1
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003
 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE
 MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1
 FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE
 SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 11) PLEASE NOTE SHEET M1 DETAIL FOR AN EXISTING A/C
 CONDENSER STAND AND NEW CONDENSER MOUNTED TO THE STAND.
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 ANCHORING OF THE UNIT TO THE STAND. 2014 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-03 Cont ID  
Sent By albarran Date 2016-10-03 Time 15:27 Rev Time 0.00
Received By albarran Date 2016-10-03 Time 14:19 Sent To I
Notes
2016-10-03 15:28:22ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By albarran Date 2016-07-27 Time 13:38 Rev Time 0.00
Received By albarran Date 2016-07-26 Time 14:03 Sent To  
Notes
2016-07-27 13:39:07ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: DELI EXPANSION
 JOB ADDRESS: 7432 & 7434 S. DIXIE HWY.
 DESCRIPTION: GENERAL ALTERATIONS TO 7432 & 7434 AND
 KITCHEN EXPANSION
 MAST. PERMIT: 16070980
 REVISION:
  
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT: EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS. THOUGH THERE IS A
 SIGN OUTLET REFLECTED ON THE PLANS, THE CODE REQUIRES A
 SIGN OUTLET AT EVERY DOOR.
 2. NEC 210.62 SHOW WINDOWS: AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED.
 3. FBC-B 1011.1: EXITS AND EXIT ACCESS SHALL BE, MARKED
 BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE
 CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL
 NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF
 EGRESS. THERE IS A REAR DOOR MISSING AN EXIT LIGHT.
 4. NEC 110.26(D) ILLUMINATION: ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. PANELS
 A & B DO NOT APPEAR TO HAVE PROPER ILLUMINATION.
 5. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 6. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 7. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 SUBMIT A LIGHTING DENSITY ALLOWANCE CHART.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-09 Cont ID  
Sent By wjolin Date 2016-09-09 Time 12:00 Rev Time 0.00
Received By wjolin Date 2016-09-09 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By wjolin Date 2016-07-26 Time 11:39 Rev Time 0.00
Received By wjolin Date 2016-07-26 Time 10:53 Sent To  
Notes
2016-07-26 11:38:577434 SOUTH DIXIE HIGHWAY
 PERMIT #16070980
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET A-2: STORAGE (#107) DOOR SWING OBSTRUCTS THE PATH
 OF EGRESS TO THE NEW DOOR. PER NFPA 101 SECTION
 7.2.1.4.3 DOOR LEAF ENCROACHMENT - DURING ITS SWING,
 ANY DOOR LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS
 THAN ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND
 SHALL PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED
 WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A
 LANDING, WHEN FULLY OPEN.
  
 SHEET A-2: DRY STORAGE (#112) DOOR SWING MAY IMPEDE
 EGRESS FROM THE EXISTING RESTROOM (#108).
  
 SHEET A-2: SUBMIT EQUIPMENT AND INSTALLATION
 SPECIFICATIONS FOR THE DECK OVEN.
  
 SHEET E-2: AN ADDITIONAL COMBINATION EXIT
 SIGN/EMERGENCY LIGHT IS NEEDED AT THE EXTERIOR DOOR OF
 OFFICE (#109) TO PREVENT OCCUPANTS FROM HAVING TO
 TRAVEL THROUGH THE DRY STORAGE ROOM TO EGRESS THE
 BUILDING.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-10-17 Cont ID  
Sent By tklarge Date 2016-10-17 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-10-17 Time 06:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-09-12 Cont ID  
Sent By tklarge Date 2016-09-12 Time 05:40 Rev Time 0.00
Received By tklarge Date 2016-09-12 Time 05:11 Sent To E
Notes
2016-09-12 05:20:281) EXPLAIN HOW YOU ARRIVED AT YOUR COMBUSTION AIR RATES
 ON M-1. WHERE ARE YOU GETTING THE 2090 SQUARE FEET
 TOTAL? SUBMIT THE DIMENSIONS OF THE ROOMS BEING USED
 FOR THE CALCULATIONS AND HOW YOU ARRIVED AT THESE
 NUMBERS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) AN AUTOMATIC GAS SHUTOFF VALVE IS REQUIRED ON THE
 GAS LINE TO THE OVEN PER NFPA 96 SEC.10.4.2ND REQUEST.
 3) THE GAS SHALL BE UNDER A SEPARATE PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-12 Cont ID  
Sent By gjohnson Date 2016-08-12 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2016-08-12 Time 11:16 Sent To  
Notes
2016-08-12 11:48:581ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 GAS COMMENTS:
  
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 2. AN AUTOMATIC FIRE EXTINGUISHING SYSTEM WITH A
 AUTOMATIC GAS SHUT OFF IS REQUIRED. PER NFPA
 96-10.2.4/10.4.1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-11-02 Time 13:34 Rev Time 0.00
Received By tklarge Date 2016-10-14 Time 16:27 Sent To  
Notes
2016-10-14 16:27:37TKLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-03 Cont ID  
Sent By albarran Date 2016-10-03 Time 15:29 Rev Time 0.00
Received By albarran Date 2016-09-01 Time 10:59 Sent To  
Notes
2016-10-03 15:33:2610/3/16 DID NOT SUCCESSFULLY PASS THROUGH ALL TRADE
 REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL./ FILE SENT TO
 LARGE READY P DRAWER. MA
2016-09-02 11:00:18B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-12 Cont ID  
Sent By gjohnson Date 2016-08-12 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2016-07-25 Time 13:38 Sent To  
Notes
2016-07-25 13:39:28B12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2016-11-22 Cont ID  
Sent By tklarge Date 2016-11-22 Time 13:13 Rev Time 0.00
Received By tklarge Date 2016-11-22 Time 13:13 Sent To  
Notes
2016-11-22 13:23:05COUNTY IMPACT FEE OFFICE STAMPED PLANS $0.00. TKL.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-11-02 Time 13:34 Rev Time 0.00
Received By tklarge Date 2016-09-10 Time 10:40 Sent To  
Notes
2016-11-02 13:39:21ONE SET OF PLANS SHALL BE TAKEN TO PALM BEACH COUNTY
 FOR PAYMENT OF IMPACT FEES.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By jwitmer Date 2016-08-02 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2016-08-02 Time 09:38 Sent To  
Notes
2016-08-02 09:38:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-09 Cont ID  
Sent By ccole Date 2016-09-09 Time 07:53 Rev Time 0.00
Received By ccole Date 2016-09-09 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By ccole Date 2016-07-27 Time 16:27 Rev Time 0.00
Received By ccole Date 2016-07-27 Time 16:27 Sent To  
Notes
2016-07-27 17:09:501ST REVIEW MECHANICAL
 PERMIT #16070980
 7/27/16
  
 1) SHEET M-1: IT APPEARS THE DUCT SMOKE DETECTOR FOR
 AHU-4 IS IN THE SUPPLY, HOWEVER IS IS REQUIRED TO BE IN
 THE RETURN SYSTEM PER SECTION 606.2.1.
  
 2) M-1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD AND DUCT, HOWEVER BECAUSE THESE
 SYSTEMS WILL IMPACT THE MAIN PERMIT PLANS, PLEASE
 PROVIDE- A) KITCHEN HOOD AND EXHAUST FAN EQUIPMENT
 SCHEDULES. B) MAKEUP AIR FOR THE SYSTEMS SECTIONS 508.1
 INCLUDING COMPLIANCE FOR MAKEUP AIR TEMPERATURE PER
 SECTION 508.1.1. C) AIR BALANCE CALCULATIONS.
  
 3) M-1: PROVIDE A TYPE II EXHAUST HOOD FOR THE
 RELOCATED CONVECTION OVEN- SECTION 507.2.2.
  
 4) M-1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO
 THE NEW GAS-FIRED APPLIANCES- SHOW THE MEANS AND
 PROVIDE CALCULATIONS PER SECTION 304 FBC-14 FUEL GAS.
  
 5) M-1: SHOW THE O/A CONNECTION FOR THE RELOCATED AHU-1
 OR ADD A NOTE.
  
 6) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-4.
  
 7) M-1: PROVIDE A MECHANICAL ROOF PLAN WITH CLEARANCE
 MEASUREMENTS FOR AIR INTAKES, AND FROM EQUIPMENT TO
 ROOF EDGES.
  
 8) M-1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 MOUNTING THE CONDENSER TO THE EXISTING ROOF STAND-
 SECTION 301.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-10-17 Time 13:31 Rev Time 0.00
Received By tklarge Date 2016-10-17 Time 06:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-09-12 Cont ID  
Sent By tklarge Date 2016-09-12 Time 05:10 Rev Time 0.00
Received By tklarge Date 2016-09-12 Time 04:19 Sent To  
Notes
2016-09-12 05:10:471) THE EXISTING DINING AREA SHOWS 67 SEATS AND THE
 PROPOSED DINING AREA SHOWS 9 NEW SEATS.THIS ADDS UP TO
 76 SEATS WITHOUT THE KITCHEN AND OFFICE AREA SO HOW CAN
 THE OCCUPANT LOAD BE 73 PERSONS? CLARIFY.
 2) SUBMIT FLOW CALCULATIONS FOR THE GREASE TRAP. HOW
 DID YOU ARRIVE AT THIS SIZE GREASE TRAP? 2014 FPC SEC.
 1003.3.4.
 3) THE PREP SINK SHALL DISCHARGE THROUGH THE GREASE
 INTERCEPTOR. 2ND REQUEST.FPC 1003.3.1.
 4) SUBMIT A DETAIL FOR THE RECIRCULATION SYSTEM
 CONNECTION TO THE WATER HEATER. COMPLY WITH FPC
 SEC.607.2, 607.2.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-12 Cont ID  
Sent By gjohnson Date 2016-08-12 Time 10:56 Rev Time 0.00
Received By gjohnson Date 2016-08-11 Time 14:37 Sent To  
Notes
2016-08-12 11:15:541ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. THE PREP SINK 3 COMPARTMENT SINK AND THE FLOOR SINK
 FOR DECK OVEN ARE REQUIRED TO DRAIN THROUGH A GREASE
 INTERCEPTOR.
 PER FBC PL 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR.
  
 2. THE FLOOR SINK FOR 3 COMPARTMENT SINK SHALL BE
 INDIVIDUALLY CONNECTED TO BUILDING DRAIN. I T CAN NOT
 CONNECT TO ANOTHER FIXTURE DRAIN.
 PER FBC PL 915.2.5 FIXTURE BRANCH OR DRAIN.
 THE FIXTURE BRANCH OR FIXTURE DRAIN SHALL CONNECT TO
 THE COMBINATION WASTE AND VENT WITHIN A DISTANCE
 SPECIFIED IN TABLE 909.1. THE COMBINATION WASTE AND
 VENT PIPE SHALL BE CONSIDERED THE VENT FOR THE FIXTURE.
  
 3. A RECIRCULATION SYSTEM IS REQUIRED ON THE HOT WATER
 SYSTEM TO COMPLY WITH FBC PL 607.2 HOT OR TEMPERED
 WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.