Plan Review Details - Permit 16070968
Plan Review Stops For Permit 16070968
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By cthroop Date 2016-08-24 Time 08:47 Rev Time 0.00
Received By cthroop Date 2016-08-24 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By cthroop Date 2016-08-02 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-08-02 Time 08:59 Sent To  
Notes
2016-08-02 09:01:46BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/2/16
  
 1. SCOPE OF WORK ON PLANS EXCEEDS WORK DESCRIPTION ON
 APPLICATION. NO RECORD ON FILE FOR CONVERSION OF CABANA
 INTO LIVING SPACE. BRING PROPERTY INTO COMPLIANCE WITH
 ZONING REGULATIONS.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-12-02 Cont ID  
Sent By vperez Date 2016-12-02 Time 05:53 Rev Time 0.00
Received By vperez Date 2016-12-02 Time 05:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 20:39 Rev Time 0.00
Received By albarran Date 2016-10-25 Time 17:40 Sent To I
Notes
2016-10-25 20:40:153RD ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 1724 37TH ST.
 DESCRIPTION: BRING UNPERMITTED CABANA TO CODE
 MASTER PERMIT: 16070608
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. AN ELECTRICAL SUB?PERMIT IS REQUIRED.
 A. STILL MISSING ELECTRICAL SUB PERMIT
 2. REVISE SCOPE OF WORK ON SHEET S1 TO INCLUDE
 ELECTRICAL WORK.
 A. SCOPE OF WORK AS DEFINED ON THE PERMIT OR PLANS DOES
 NOT INCLUDE ELECTRICAL WORK
 3. PLANS SHALL BE DRAWN TO SCALE AND SCALE USED
 INDICATED ON PLANS.
 A. SCALE SHOWN
 4. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FPL
 UTILITY POLE/S SERVING THE PROPERTY. INCLUDE ON PLANS
 THE OVERHEAD SERVICE DROP/S, THE LOCATION OF EVERY
 ELECTRIC METER AND DISCONNECT.
 A. FAIL TO SHOW THE ROUTE OF THE FEEDER TO SUB PANEL B.
 5. THE WORD ROMEX AS USED IN THIS NOTE IS TO IDENTIFY A
 TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE OF
 CABLE; REFER TO CABLE TYPES NM, NMC OR NMS.
 A. THE WORD ROMEX CONTINUES TO APPEAR ON THE NOTES.
 PLEASE CORRECT ACCORDINGLY
 6. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS
 ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED.
 THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND
 INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE
 SPECIFIC.
 A. THERE ARE SEVERAL THINGS INCORRECT ABOUT THE RISER
 DIAGRAM. IT IS MISSING THE EGC FOR THE MAIN FEEDER. YOU
 INDICATE A 50 AMP SUB PANEL; ACCORDING TO NEC225.39(D)
 MINIMUM FEEDER SIZE SHALL BE 60 AMP. THE CALCS FOR SUB
 PANEL B ARE INCORRECT. ASSUMING THAT THE LOADS ARE AS
 SHOWN YOU FAIL TO MAKE ADJUSTMENT FOR THE CONTINUOUS
 LOADS. TOTAL KW LOAD IS 39 AMP.
 7. FBC?RE3601.2/NEC230.2: ONE AND TWO FAMILY DWELLINGS
 SHALL BE SERVED BY ONLY ONE SERVICE.
 A. THIS MAY BE CLARIFIED WITH THE CORRECTED SUBMITTAL
 8. FBC?RE3601.6.2/NEC 230.70(A)(1): THE SERVICE
 DISCONNECTS SHALL BE LOCATED IN A READILY ACCESSIBLE
 LOCATION OUTSIDE OF THE BLDG. OR INSIDE AT THE NEAREST
 POINT OF ENTRY OF THE SERVICE CONDUCTORS.
 A. AS LONG AS THERE IS ONLY A SINGLE METER, THIS IS A
 SINGLE SERVICE AND THE MAIN IS OK INSIDE THE MAIN
 PANEL.
 9. FBC?RE3601.7/NEC 230.72: THE TWO TO SIX DISCONNECTS
 AS PERMITTED IN 230.71 SHALL BE GROUPED. EACH
 DISCONNECT SHALL BE MARKED TO INDICATE THE LOAD SERVED.
 A. ACCEPTED IF CLARIFIED WITH NEW RISER AND SITE PLAN
 10. FBC?RE3601.6.2/NEC 240.24: (A) & (B) PANELS SHALL
 BE LOCATED SUCH THAT OVER CURRENT DEVICES ARE
 ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO OCP
 DEVICES.
 A. ACCEPTED AS IS.
 11. FBC?R3706.2/NEC 408.4(A): REQUIRES THAT YOU PROVIDE
 A PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY
 INDICATING THE SPECIFIC PURPOSE OF EVERY CIRCUIT.
 A. ACCEPTED AS IS.
 12. FBC?RE3902.12/NEC 210.12B: ALL BRANCH CIRCUITS THAT
 SUPPLY 120?VOLT, SINGLE?PHASE, 15? AND 20?AMPERE
 OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS
 OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE
 ARC?FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT.
 A. ACCEPTED WITH A NOTE BUT THE ASTERIX AT THE BOTTOM
 OF THE PANEL SCHEDULES DO NOT INDICATE WHICH BREAKERS
 ARE TO BE ARC-FAULT.
 13. FBC?RE 3901/NEC210.52: CODES HAVE SPECIFIC OUTLET
 SPACING AND LOCATION REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
 A. PROPER OUTLET PLACEMENT SHALL BE INDICATED ON THE
 DRAWINGS.
 14. FBC?R303.9 REQUIRED HEATING ? WHEN THE WINTER
 DESIGN TEMPERATURE IN TABLE R301.2(1) IS BELOW 60
 DEGREE F (16 DEGREES C), EVERY DWELLING UNIT SHALL BE
 PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING
 A MINIMUM ROOM TEMPERATURE OF 68 DEGREE F (20 DEGREE C)
 AT A POINT 3 FEET (914 MM) ABOVE THE FLOOR AND 2 FEET
 (610 MM) FROM EXTERIOR WALLS IN ALL HABITABLE ROOMS AT
 THE DESIGN TEMPERATURE. THE INSTALLATION OF ONE OR MORE
 PORTABLE SPACE HEATERS SHALL NOT BE USED TO ACHIEVE
 COMPLIANCE WITH THIS SECTION.
 A. HEATING FOR THE ENTIRE OCCUPANCY IS NOT INDICATED
 NOR IS IT MENTIO0NED THAT THE WINDOW UNIT IS REVERSE
 CYCLE.
 15. FBC?R404.1 LIGHTING EQUIPMENT (MANDATORY). A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH?EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
 A. NOTHING MENTIONED ON THE PLANS TO ADDRESS THIS.
 16. FBC?R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS:
 A. NO BEDROOM IS INDICATED SO SMOKE DETECTOR IS NOT
 REQUIRED.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-23 Cont ID  
Sent By njwira Date 2016-08-16 Time 16:52 Rev Time 0.00
Received By albarran Date 2016-08-23 Time 15:30 Sent To B
Notes
2016-08-23 15:02:52IN A TELEPHONE CONVERSATION WITH THE GENERAL CONTRACTOR
 I WAS INFORMED THAT THE ACTUAL SCOPE OF THIS PERMIT IS
 TO BRING AN UNPERMITTED CONVERSION FROM A GARAGE TO A
 POOL CABANA INTO COMPLIANCE. I INFORMED THE GC THAT
 REGARDLESS OF WHEN THIS WORK WAS PERFORMED, IT IS BEING
 PERMITTED NOW, AND THEREFORE SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF THE 2014 FBC-R/2011
 NEC.. ELECTRICAL COMMENT WILL FOLLOW:
  
 ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 1724 37TH ST.
 DESCRIPTION: LEGALIZING POOL CABANA
 MASTER PERMIT: 16070968
 SUB PERMIT:
  
 BELOW PLEASE FIND THE DEFICIENCIES FOUND WITH THE ABOVE
 MENTIONED ELECTRICAL SUBMITTAL/PLANS.
  
 1. AN ELECTRICAL SUB-PERMIT IS REQUIRED.
 2. REVISE SCOPE OF WORK ON SHEET S1 TO INCLUDE
 ELECTRICAL WORK.
 3. PLANS SHALL BE DRAWN TO SCALE AND SCALE USED
 INDICATED ON PLANS.
 4. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FPL
 UTILITY POLE/S SERVING THE PROPERTY. INCLUDE ON PLANS
 THE OVERHEAD SERVICE DROP/S, THE LOCATION OF EVERY
 ELECTRIC METER AND DISCONNECT.
 5. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 6. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS
 ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED.
 THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND
 INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE
 SPECIFIC.
 7. FBC-RE3601.2/NEC230.2: ONE AND TWO FAMILY DWELLINGS
 SHALL BE SERVED BY ONLY ONE SERVICE.
 8. FBC-RE3601.6.2/NEC 230.70(A)(1): THE SERVICE
 DISCONNECTS SHALL BE LOCATED IN A READILY ACCESSIBLE
 LOCATION OUTSIDE OF THE BLDG. OR INSIDE AT THE NEAREST
 POINT OF ENTRY OF THE SERVICE CONDUCTORS.
 9. FBC-RE3601.7/NEC 230.72: THE TWO TO SIX DISCONNECTS
 AS PERMITTED IN 230.71 SHALL BE GROUPED. EACH
 DISCONNECT SHALL BE MARKED TO INDICATE THE LOAD SERVED.
 10. FBC-RE3601.6.2/NEC 240.24: (A) & (B) PANELS SHALL
 BE LOCATED SUCH THAT OVER CURRENT DEVICES ARE
 ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO OCP
 DEVICES.
 11. FBC-R3706.2/NEC 408.4(A): REQUIRES THAT YOU
 PROVIDE A PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY
 INDICATING THE SPECIFIC PURPOSE OF EVERY CIRCUIT.
 12. FBC-RE3902.12/NEC 210.12B: ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS
 OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE
 ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT.
 13. FBC-RE 3901/NEC210.52: CODES HAVE SPECIFIC OUTLET
 SPACING AND LOCATION REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
 14. FBC-R303.9 REQUIRED HEATING - WHEN THE WINTER
 DESIGN TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F
 (16?C), EVERY DWELLING UNIT SHALL BE PROVIDED WITH
 HEATING FACILITIES CAPABLE OF MAINTAINING A MINIMUM
 ROOM TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914
 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR
 WALLS IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE.
 THE INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION
 15. FBC-R404.1 LIGHTING EQUIPMENT (MANDATORY). A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS
 16. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS:
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By albarran Date 2016-07-27 Time 11:20 Rev Time 0.00
Received By albarran Date 2016-07-27 Time 10:57 Sent To  
Notes
2016-07-27 11:20:42ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME:
 JOB ADDRESS: 1724 37TH STREET
 DESCRIPTION: REPLACE OR REPAIR STUDS AND STRAP
 ACCORDING TO PLANS, INSTALL HARDY BOARD
 MAST. PERMIT: 16070968
 REVISION:
  
 1. REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION
 TO INCLUDE THE ELECTRICAL WORK INDICATED ON PLANS.
 2. CLARIFY THE ELECTRICAL SCOPE OF WORK ON THE PLANS TO
 INDICATE WHAT IS BEING DONE.
 3. CORRECT THE CODE COMPLIANCE REFERENCE TO THE 2011
 EDITION OF THE NEC AND REVISE THE NOTES AND DRAWINGS
 ACCORDINGLY.
 4. SCOPE OF WORK MAY AFFECT THE OUTLET REQUIREMENTS IN
 THE LIVING ROOM AND KITCHEN AREAS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-02 Cont ID  
Sent By vperez Date 2016-12-02 Time 05:53 Rev Time 0.00
Received By vperez Date 2016-12-02 Time 05:53 Sent To  
Notes
2016-12-01 10:52:15RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-25 Cont ID  
Sent By albarran Date 2016-10-25 Time 20:40 Rev Time 0.00
Received By albarran Date 2016-10-19 Time 13:48 Sent To  
Notes
2016-10-25 20:46:5910/25/16 FAILED ELECTRICAL REVIEW FOR THE THIRD TIME.
 CONTRACTOR CONTACTED VIA EMAIL AND SENT A COPY OF MY
 NOTES. FILE SENT TO SMALL DENIED DRAWER E. MA
2016-10-20 13:48:48RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-24 Cont ID  
Sent By cthroop Date 2016-08-24 Time 08:05 Rev Time 0.00
Received By cthroop Date 2016-08-15 Time 12:50 Sent To  
Notes
2016-08-15 12:50:52RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-02 Cont ID  
Sent By cthroop Date 2016-08-02 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-07-25 Time 13:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-08-01 Cont ID  
Sent By hmoser Date 2016-08-01 Time 10:54 Rev Time 0.00
Received By hmoser Date 2016-08-01 Time 10:37 Sent To B
Notes
2016-08-01 10:53:59NO PLAN SUBMITTED FOR A/C ACCORDING TO THE APPLICATION
 MECHANICAL NOT REQUIRED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-16 Cont ID  
Sent By njwira Date 2016-08-16 Time 16:24 Rev Time 0.00
Received By njwira Date 2016-08-16 Time 08:23 Sent To E
Notes
2016-08-16 16:20:07PASSED

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By nwair Date 2016-07-28 Time 15:12 Rev Time 0.00
Received By njwira Date 2016-07-27 Time 15:13 Sent To M
Notes
2016-07-28 15:15:487/28/16- FAILED
  
 ZONING: SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 FAILED
 1. SECOND KITCHEN MAKES THIS A SECOND USE AND IS NOT
 PERMITTED IN THIS ZONING DISTRICT.
  
 PASSED
 1. CABANA SIDE SETBACK IS 6FT. AND MEETS THE 5FT. SIDE
 SETBACK REQUIREMENT.
 2. REAR SETBACK IS 7.62FT. AND MEETS THE SETBACK OF
 5FT.
 3. BUILDING HEIGHT MEETS THE 25FT. HEIGHT LIMIT.
 4. ACESSORY STRUCTURE IS 454.92SQFT. AND MEETS THE
 1,000SQFT. LIMIT.
 5. NO TREES BEING REMOVED SO NO TREE ALTERATION PERMIT
 REQUIRED.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved