Plan Review Details - Permit 16070946
Plan Review Stops For Permit 16070946
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By jwitmer Date 2016-10-24 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2016-10-25 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-14 Cont ID  
Sent By jwitmer Date 2016-08-14 Time 09:15 Rev Time  
Received By jwitmer Date 2016-08-13 Time 14:15 Sent To  
Notes
2016-08-14 09:17:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070946
 ADD: 901 45TH ST. 3RD FLOOR/ PALM BEACH CHILDREN?S
 HOSPITAL
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 1) SHEET G130 IS SCALED TO 1 INCH EQUALS 20 FEET,
 PLEASE NOTE THIS PLAN DOES NOT LABEL DOORS IN CORRIDOR
 TO STAIRWELLS ETC. THE SAME ISSUE WITH SHEET A130 THE
 OVERALL PHASING PLAN. THE SHEET A130 IS SCALED TO A
 LARGER SCALE 1/8 INCH EQUALS ONE FOOT. THIS IS THE
 MINIMUM SCALE THAT CAN BE SUBMITTED FOR REVIEW UNDER
 THE 2014 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 107.2.1.4 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM.
  
 THE SHEET A130 WOULD BE A GOOD SHEET TO USE AS THE LIFE
 SAFETY SHEET, TO ADD THE LIFE SAFETY LEGEND TO THIS
 SHEET AS WELL AS IDENTIFY THE CORRIDOR DOORS THAT ARE
 LABELED UNDER THE DOOR SCHEDULE. NOW I WOULD BE
 GUESSING WHICH DOOR IS WHICH, THE DOORS NEED
 IDENTIFICATION TAGS. 2014 FBC-B TABLE 716.5 OPENING
 PROTECTIVES.
  
 2A) SHEET A130 SHOWS (2) PATIENT ROOMS TO BE ACCESSIBLE
 ROOMS, ROOM NUMBERS 320 AND 323, BUT THE MAIN DOOR FROM
 THE CORRIDOR DOES NOT HAVE THE REQUIRED 18 INCHES ON
 THE LATCH SIDE OF THE DOOR. 2014 FBC-ACCESS. CODE
 404.2.4. NONE OF THE PATIENT ENTRY ROOMS SHOW AN 18
 INCHES MANEUVERING CLEARANCES AS WELL AS DOOR NUMBERS
 324,325, & 326.
  
 2B) SHEET A130 SHOWS DOOR NUMBERS, 303A, 304A, 305A,
 306A, 307A, 308A, 309A, 310A, 311A , 312A, 315A & 317A
 NEED TO SHOW COMPLIANCE WITH 2014 FBC-EXIST. BUILD.
 CODE 805.4.2.1 SUPPLEMENTAL REQUIREMENTS FOR DOOR
 SWINGS. 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY
 OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 3) 2014 FBC-B 449.2 ADDITIONAL CODES AND STANDARDS FOR
 THE DESIGN AND CONSTRUCTION OF GENERAL, HOSPITALS,
 INCLUDING INTENSIVE RESIDENTIAL TREATMENT FACILITIES
 (IRTF) FOR CHILDREN AND ADOLESCENTS, AND UNLESS
 EXEMPTED BY CHAPTER 395.0163, FLORIDA STATUTES. 449.2.2
 THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES (THE GUIDELINES), AS REFERENCE IN
 CHAPTER 35 OF THIS CODE.
  
 3A) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE
 ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO
 WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER THE
 HEADING SPECIAL PATIENT CARE ROOMS 2,1-2.4. PLEASE SEE
 SECTION REQUIREMENTS FOR 2.1-2.4.2 AIRBORNE INFECTION
 ISOLATION ROOMS (ALL ) ROOMS. (3) LOCATION. ALL ROOMS
 SHALL BE LOCATED WITHIN INDIVIDUAL NURSING UNITS OR
 GROUPED AS A SEPARATE ISOLATION UNIT. WHEN NOT REQUIRED
 FOR PATIENTS WITH AIRBORN INFECTIOUS DISEASES, USE OF
 THESE ROOMS FOR NORMAL ACUTE CARE PATENTS SHALL BE
 PERMITTED.
  
 3B) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE
 ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO
 WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER
 SECTION 2.1-2.4.2.2 ALL ROOM REQUIREMENTS, (3) AN AREA
 FOR GOWNING AND STORAGE OF CLEAN AND SOILED MATERIALS
 SHALL BE LOCATED EITHER DIRECTLY OUTSIDE OR INSIDE THE
 ENTRY DOOR TO THE PATIENT ROOM.
  
 3C) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE
 ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO
 WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER
 SECTION 2.1-2.4.2.4 SPECIAL DESIGN ELEMENTS SEE
 ARCHITECTURAL DETAILS (1)(A-C) , (2) (A-C) & (3).
  
 4A) SHEET A130 SHOWS VARIOUS SYMBOLS NOT FOUND ON THE
 SHEET G130 THE LIFE SAFETY SHEET LEGEND NOR ON SHEET
 A130. PLEASE INDICATE WHAT THE SYMBOLS ARE: IC,CR,KP,RS
 & PTS ? ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3.
  
 4B) SHEET A130 SHOWS VARIOUS SYMBOLS NOT FOUND ON THE
 SHEET G130 THE LIFE SAFETY SHEET LEGEND NOR ON SHEET
 A130. PLEASE INDICATE WHAT THE ASTERISK SYMBOL
 REPRESENTS? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 5) SHEET A130 ROOM 321 THE MEDS. ROOM. PLEASE IDENTIFY
 FURTHER WHICH THIS ROOM IS EITHER A MEDICATION
 DISPENSING LOCATION (2.1-2.6.6 GUIDELINE) OR A
 MEDICATION PREPARATION ROOM IN COMPLIANCE WITH
 2.1-2.6.6.1 OF THE GUIDELINE?
  
 6) PLEASE PROVIDE COMPLIANCE WITH THE GUIDELINE
 2.1-2.6.4. MULTIPURPOSE ROOM. AT LEAST ONE MULTIPURPOSE
 ROOM FOR EACH FACILITY SHALL BE PROVIDED FOR STAFF,
 PATIENTS, AND PATIENTS FAMILIES FOR PATIENT
 CONFERENCES, REPORTS, EDUCATION, TRAINING SESSIONS AND
 CONSULTATIONS.
  
 7) SHEET A130 & SHEET A730 THE SOILED LINEN ROOM
 (HOLDING) 322 DOES NOT SHOW COMPLIANCE WITH THE
 GUIDELINE SECTION 2.1-2.6.10.2. IF A FLUSHING-RIM
 CLINICAL SINK IS NOT PROVIDED IN THIS ROOM, SUCH A SINK
 OR AN ACCEPTABLE ALTERNATIVE( E.G. A WATER CLOSET WITH
 BEDPAN-RINSING DEVICE LOCATED IN A PATIENTS TOILET ROOM
 SHALL BE PROVIDED ELSEWHERE ON THE NURSING UNIT FOR THE
 CLEANING OF BEDPANS.
  
 8) SHEET A011;
 8A) THIS SHEET IS TITLED EXTERIOR GLAZED OPENINGS,
 PLEASE PROVIDE WHERE THESE OPENINGS ARE BEING REPLACED.
 NOTES C,D & E ADD ALTERNATE, PLEASE PROVIDE A NARRATIVE
 TO WHAT THIS MEANS, IS THIS INDICATING A DIFFERENT
 DESIGN FROM WINDOW TYPE A & B MAKING THE OPENINGS
 LARGER OR IS A DIFFERENT LOCATION ALL TOGETHER?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 8B) PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS
  
 8C) IDENTIFY GLAZING/ MULLIONS. 2014 FBC-B 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE.
  
 8D) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) THERE IS NO WIND DESIGN CRITERIA FOR THE EXTERIOR
 WINDOW OPENING REFERENCED ON SHEET A011.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 9.2. RISK CATEGORY.
  
 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 9.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 9.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-24 Cont ID  
Sent By albarran Date 2016-10-24 Time 15:06 Rev Time 0.00
Received By albarran Date 2016-10-24 Time 14:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-27 Cont ID  
Sent By albarran Date 2016-07-27 Time 15:30 Rev Time 0.00
Received By albarran Date 2016-07-26 Time 14:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By pleduc Date 2016-10-17 Time   Rev Time 0.00
Received By pleduc Date 2016-10-17 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By pleduc Date 2016-08-10 Time   Rev Time 0.00
Received By pleduc Date 2016-08-10 Time 08:41 Sent To  
Notes
2016-08-10 12:20:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 001 - THERE IS AN INCORRECT REFERNCE TO A
 FIRE CODE. IN THE MIDDLE OF THE PAGE UNDER "FIRE
 PROTECTION REQUIREMENT" NFPA 101, 2009 EDITION IS
 INDICATED.
  
 IT SHOULD READ "2012". PLEASE CORRECT.
  
  
  
 2) SHEET G 130 - THERE IS NO INDICATION ON THIS LIFE
 SAFETY PLAN OR ANYWHERE ELSE IF THE PROPOSED WING WILL
 BE OCCUPIED DURING ANY CONSTRUCTION PERIOD AND/OR
 PHASE.
  
 PLEASE PROVIDE A NOTE OF BRIEF NARRATIVE OF EACH PHASE
 INCLUIDNG SPECIFIC EXITING STRATEGY DETAILS FOR ALL
 PROPOSED OCCUPANTS ANS EXITS.
  
  
  
 3) SHEET A 0.11 & G 130 - THE LIFE SAFETY PLAN
 INDICATES SMOKE BARRIERS AND SMOKE PARTITIONS IN THE
 CORRIDOR OF THE PROPOSE PROJECT. THE DOOR SCHEDULE DOES
 NOT INDICATE AND PROTECTION FOR ALL THE CORRIDOR DOORS.
  
 PER NFPA 1, CHAPTER 12
  
 12.8 SMOKE PARTITIONS.
 12.8.1* GENERAL. WHERE REQUIRED ELSEWHERE IN THIS CODE,
 SMOKE PARTITIONS SHALL BE PROVIDED TO LIMIT THE
 TRANSFER OF SMOKE. [101:8.4.1]
  
 12.8.3 OPENING PROTECTIVES.
 12.8.3.1 DOORS IN SMOKE PARTITIONS SHALL COMPLY WITH
 12.8.3.2 THROUGH 12.8.3.5. [101:8.4.3.1]
 12.8.3.2 DOORS SHALL COMPLY WITH THE PROVISIONS OF
 7.2.1 OF NFPA 101. [101:8.4.3.2]
  
 12.9 SMOKE BARRIERS.
 12.9.1* GENERAL. WHERE REQUIRED BY CHAPTERS 11 THROUGH
 43 OF NFPA 101, SMOKE BARRIERS SHALL BE PROVIDED TO
 SUBDIVIDE BUILDING SPACES FOR THE PURPOSE OF
 RESTRICTING THE MOVEMENT OF SMOKE. [101:8.5.1]
  
 12.9.4 OPENING PROTECTIVES.
 12.9.4.1* DOORS IN SMOKE BARRIERS SHALL CLOSE THE
 OPENING, LEAVING ONLY THE MINIMUM CLEARANCE NECESSARY
 FOR PROPER OPERATION, AND SHALL BE WITHOUT LOUVERS OR
 GRILLES. THE CLEARANCE UNDER THE BOTTOM OF A NEW DOOR
 SHALL BE A MAXIMUM OF ? IN. (19 MM). [101:8.5.4.1]
 12.9.4.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43 OF
 NFPA 101, DOORS IN SMOKE BARRIERS THAT ARE REQUIRED TO
 BE SMOKE LEAKAGE?RATED SHALL COMPLY WITH THE
 REQUIREMENTS OF 8.2.2.5 OF NFPA 101. [101:8.5.4.2]
 12.9.4.3 LATCHING HARDWARE SHALL NOT BE REQUIRED ON
 DOORS IN SMOKE BARRIERS UNLESS SPECIFICALLY EXEMPTED BY
 CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:8.5.4.3]
 12.9.4.4* DOORS IN SMOKE BARRIERS SHALL BE SELF-CLOSING
 OR AUTOMATIC-CLOSING IN ACCORDANCE WITH 14.5.4 AND
 SHALL COMPLY WITH THE PROVISIONS OF 7.2.1 OF NFPA 101.
 [101:8.5.4.4]
  
  
 NFPA 101, CHAPTER 18
  
 18.3.6.3* CORRIDOR DOORS.
 18.3.6.3.1* DOORS PROTECTING CORRIDOR OPENINGS SHALL BE
 CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE, AND THE
 FOLLOWING ALSO SHALL APPLY:
 (1) COMPLIANCE WITH NFPA 80, STANDARD FOR FIRE DOORS
 AND OTHER OPENING PROTECTIVES, SHALL NOT BE REQUIRED.
 (2) A CLEARANCE BETWEEN THE BOTTOM OF THE DOOR AND THE
 FLOOR COVERING NOT EXCEEDING 1 IN. (25 MM) SHALL BE
 PERMITTED FOR CORRIDOR DOORS.
 (3) DOORS TO TOILET ROOMS, BATHROOMS, SHOWER ROOMS,
 SINK CLOSETS, AND SIMILAR AUXILIARY SPACES THAT DO NOT
 CONTAIN FLAMMABLE OR COMBUSTIBLE MATERIAL SHALL NOT BE
 REQUIRED TO BE CONSTRUCTED TO RESIST THE PASSAGE OF
 SMOKE.
  
 18.3.7.3 ANY REQUIRED SMOKE BARRIER SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH SECTION 8.5 AND SHALL
 HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING, UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
  
 18.3.7.6* DOORS IN SMOKE BARRIERS SHALL BE SUBSTANTIAL
 DOORS, SUCH AS 1? IN. (44 MM) THICK, SOLID-BONDED
 WOOD-CORE DOORS, OR SHALL BE OF CONSTRUCTION THAT
 RESISTS FIRE FOR A MINIMUM OF 20 MINUTES, AND SHALL
 MEET THE FOLLOWING REQUIREMENTS:
 (1) NONRATED FACTORY- OR FIELD-APPLIED PROTECTIVE
 PLATES, UNLIMITED IN HEIGHT, SHALL BE PERMITTED.
 (2) CROSS-CORRIDOR OPENINGS IN SMOKE BARRIERS SHALL BE
 PROTECTED BY A PAIR OF SWINGING DOORS OR A
 HORIZONTALSLIDING DOOR COMPLYING WITH 7.2.1.14, UNLESS
 OTHERWISE PERMITTED BY 18.3.7.7.
 (3) THE SWINGING DOORS ADDRESSED BY 18.3.7.6(2) SHALL
 BE ARRANGED SO THAT EACH DOOR SWINGS IN A DIRECTION
 OPPOSITE FROM THE OTHER.
 (4) THE MINIMUM CLEAR WIDTH FOR SWINGING DOORS SHALL BE
 AS FOLLOWS:
 (A) HOSPITALS AND NURSING HOMES ? 41? IN. (1055 MM)
 (B) PSYCHIATRIC HOSPITALS AND LIMITED CARE FACILITIES ?
 32 IN. (810 MM)
 (5) THE MINIMUM CLEAR WIDTH OPENING FOR
 HORIZONTAL-SLIDING DOORS SHALL BE AS FOLLOWS:
 (A) HOSPITALS AND NURSING HOMES ? 6 FT 11 IN. (2110 MM)
 (B) PSYCHIATRIC HOSPITALS AND LIMITED CARE FACILITIES ?
 64 IN. (1625 MM)
 (6) THE CLEARANCE UNDER THE BOTTOM OF SMOKE BARRIER
 DOORS SHALL NOT EXCEED ? IN. (19 MM).
  
 18.3.7.8* DOORS IN SMOKE BARRIERS SHALL COMPLY WITH
 8.5.4 AND ALL OF THE FOLLOWING:
 (1) THE DOORS SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH 18.2.2.2.7.
 (2) LATCHING HARDWARE SHALL NOT BE REQUIRED.
 (3) STOPS SHALL BE REQUIRED AT THE HEAD AND SIDES OF
 DOOR FRAMES.
 (4) RABBETS, BEVELS, OR ASTRAGALS SHALL BE REQUIRED AT
 THE MEETING EDGES OF PAIRS OF DOORS.
  
 8.5.4 OPENING PROTECTIVES.
 8.5.4.1* DOORS IN SMOKE BARRIERS SHALL CLOSE THE
 OPENING, LEAVING ONLY THE MINIMUM CLEARANCE NECESSARY
 FOR PROPER OPERATION, AND SHALL BE WITHOUT LOUVERS OR
 GRILLES. THE CLEARANCE UNDER THE BOTTOM OF A NEW DOOR
 SHALL BE A MAXIMUM OF ? IN. (19 MM).
 8.5.4.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43, DOORS
 IN SMOKE BARRIERS THAT ARE REQUIRED TO BE SMOKE
 LEAKAGE?RATED SHALL COMPLY WITH THE REQUIREMENTS OF
 8.2.2.4.
 8.5.4.3 LATCHING HARDWARE SHALL BE REQUIRED ON DOORS IN
 SMOKE BARRIERS, UNLESS SPECIFICALLY EXEMPTED BY
 CHAPTERS 11 THROUGH 43.
 8.5.4.4* DOORS IN SMOKE BARRIERS SHALL BE SELF-CLOSING
 OR AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8 AND
 SHALL COMPLYWITH THE PROVISIONS OF 7.2.1.
 (5) CENTER MULLIONS SHALL BE PROHIBITED.
  
 PLEASE PROVIDE FOR THE PROPER RATING WITHIN THE DOOR
 SCHEDULE AND CONSTRUCTION FOR CORRIDIOR DOORS.
  
  
  
 4) SHEET A 0.11- THE DOOR SCHEDULE INDICATES NUMBERED
 HARDWARE SETS; HOWEVER, NOT HARDWARE SET DETAIL IS
 PROVIDE ( OR WAS NOT CLEARLY FOUND/IDENTIFIED)
  
 PLEASE PROVIDE DETAILS OR DIRECT TO APPLICABLE SHEET.
  
  
  
 5) SHEET A 130 & A 131 - THE TLT DOOR OPENS INTO THE
 EGRESS HALLWAY POTENTIONALLY BLOCKING ACCESS TO THE
 ROOM EXIT.
  
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
  
 PLEASE CORRECT AND/OR PROVIDE JUSTIFICATION OR DOOR
 HARWARE TO ENSURE DOOR REMAINS CLOSED.
  
  
 6) SHEET E 001, 332 & 531 - THERE IS AN INDICATION OF A
 FIRE LARM; HOWEVER, THERE IS NO INDICATION THAT THE
 FIRE ALARM SHALL REMAIN ACTIVE DURING CONSTRUCTION AND
 ALL WORK SHALL BE DONE BY CERTIFIED LIFE SAFETY
 CONTRACTORS UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OR NARRATIVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 12:14 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 09:47 Sent To  
Notes
2016-11-04 09:47:33RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 09:21 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 08:48 Sent To  
Notes
2016-11-01 12:49:23RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-25 Cont ID  
Sent By tklarge Date 2016-10-25 Time 13:13 Rev Time 0.00
Received By tklarge Date 2016-09-29 Time 11:28 Sent To  
Notes
2016-09-30 11:28:59C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-23 Cont ID  
Sent By tklarge Date 2016-08-23 Time 14:50 Rev Time 0.00
Received By tklarge Date 2016-07-25 Time 10:34 Sent To  
Notes
2016-07-25 10:35:10C03

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 12:14 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 07:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 09:16 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 09:16 Sent To  
Notes
2016-11-02 09:21:243RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16070946
 11/2/16
  
 1) SHEET M131, THE 3RD FLOOR PHASE 1 DUCTWORK
 DEMOLITION AND FLOOR PLAN WAS NOT RESUBMITTED WITH THE
 CORRECTED SETS. PLEAWEE PROVIDE THE PLAN SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-14 Cont ID  
Sent By ccole Date 2016-10-14 Time 13:51 Rev Time 0.00
Received By ccole Date 2016-10-14 Time 13:51 Sent To  
Notes
2016-10-14 15:32:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16070946
 10/14/16
  
 1) 2ND REQUEST FOR COMPLETE VENTILATION CALCULATIONS.
 THE CALCULATIONS ON SHEET M001 ARE INCORRECT AND DO NOT
 INCLUDE THE ISOLATION ROOM, THE SOIL ROOM, THE CLEAN
 ROOM, THE NOUR ROOM, THE NURSES STATION, THE STAFF
 LOUNGE, THE LOBBY, AND THE PLAYROOM - PLEASE REFER TO
 TABLE 7-1 ASHRAE 170 AND SHOW THE DESIGN PARAMTERS FOR
 EACH ROOM OR SPACE ( PLEASE NOTE THAT VENTILATION RATES
 FOR SOME OF THE ROOMS AND AREAS WILL BE FOUND IN TABLE
 403.3 FBC-14 MECHANICAL) . THE AIR CHANGE RATES SHOWN
 FOR THE PATIENT ROOM, THE EXAM ROOM, AND THE MEDS ROOM
 ON M001 ARE INSUFFICENT PER TABLE 7-1.
  
 2) SHEET M131: THERE APPEARS TO BE MANY DAMPERS MISSING
 FOR DUCTS PENETRATING FIRE-RATED WALLS AND SMOKE
 PARTITIONS INCLUDING, BUT NOT LIMITED TO DUCTS
 PENETRATING THE FOLLOWING LIST OF COMMON WALLS: A)
 ISOLATION/CORRIDOR WALL, B) PATIENT ROOM 304/WAITING
 ROOM WALL. C) CORRIDOR/PATIENT ROOM 305 WALL. D)
 MEDS/NURSES STATION E) CORRIDOR/ADA ROOM WALL. F)
 CORRIDOR/EXAM ROOM WALL. G) CORRIDOR/TLT 325A ROOM
 WALL. H) THE O/A DUCTS PENETRATING CORRIDOR/PATIENT
 ROOMS. PLEASE PROVIDE DAMPER SYMBOLS AT THE SPECIFIED
 LOCATIONS AND ANY OTHER LOCATIONS THAT REQUIRE
 PROTECTION FOR THE DUCTS. PLEASE SEE SECTION 607 AND
 PROVIDE EQUIPMENT SCHEDULES FOR THE FIRE AND SMOKE
 DAMPERS, INSTALLATION DETAILS FOR EACH TYPE, AND
 LOCATIONS OF ACCESS PANELS TO DAMPERS (WHERE REQUIRED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By ccole Date 2016-08-01 Time 17:03 Rev Time 0.00
Received By ccole Date 2016-08-01 Time 17:03 Sent To  
Notes
2016-08-01 17:04:051ST REVIEW FBC-14 MECHANICAL, EXISTING BUILDING CODES.
 PERMIT #16070946
 8/1/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND
 PROVIDE VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 7-1 ASHRAE STANDARD 170-2008. PROVIDE
 A SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED OUTDOOR AIR CHANGES AND PRESSURE RELATIONSHIPS
 FOR EACH ROOM OR AREA TO ADJACENT AREAS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHEETS M131 & M132: DUCTED RETURNS ARE REQUIRED FOR
 THE PATIENT ROOMS- SECTION 2.1-8.2.4.1 GUIDELINES FOR
 DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES, AND
 SECTION 6.7.1 ASHRAE STANDARD 170-2008.
  
 4) M131 & M132: MOTORIZED DAMPERS ARE REQUIRED FOR THE
 OUTDOOR AIR INTAKES TO THE NEW FCU'S- SEE SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 5) M401: PROVIDE EQUIPMENT SCHEDULES FOR AHU3N-1 &
 AHU3N-2. REFER TO TABLE C403.2.6 FBC-14 ENERGY
 CONSERVATION AND PROVIDE ENERGY RECOVERY VENTILATION
 FOR THE SYSTEMS.
  
 6) PROVIDE SPECIFICATIONS FOR THE CHILLED AND HOT WATER
 PIPING AND PIPING INSULATION- SEE TABLE C403.2.8 FOR
 INSULATION COMPLIANCE.
  
 7) REFER TO SECTIONS 8.3, 8.5, AND 8.6 ASHRAE STANDARD
 170-2008 AND ADD NOTES ON THE PLANS TO VERIFY
 COMPLIANCE WILL BE MET FOR REQUIRED HVAC DOCUMENTS, AND
 DUCT CLEANLINESS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2016-11-14 Cont ID  
Sent By tklarge Date 2016-10-25 Time 13:24 Rev Time 0.00
Received By tklarge Date 2016-08-22 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-25 Cont ID  
Sent By tklarge Date 2016-10-25 Time 13:13 Rev Time 0.00
Received By tklarge Date 2016-10-25 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By tklarge Date 2016-08-23 Time 14:49 Rev Time 0.00
Received By tklarge Date 2016-08-22 Time 11:54 Sent To  
Notes
2016-08-23 14:49:551) SHT. P231 - PROVIDE KEY NOTES FOR THE DEMOLITION
 PRESSURE PIPING PLAN.. CLEARLY SHOW WHAT IS BEING
 REMOVED. WPB AMEND. TO FPC SEC. 107.2.1.
 2) SHT. P232 - CLEARLY SHOW WHAT IS BEING REMOVED AT
 THIS LEVEL AND PHASE. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT SANITARY AND WATER RISRES FOR THE
 CHANGES/ALTERATIONS BEING MADE TO THE EXISTING PLUMBING
 SYSTEM. WPB AMEND. TO FPC SEC. 107.3.5.1.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  