| 2016-08-14 09:17:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070946 |
| | ADD: 901 45TH ST. 3RD FLOOR/ PALM BEACH CHILDREN?S |
| | HOSPITAL |
| | CONT: WESTBROOKE CORP. |
| | TEL: 561-395-4126 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. AUGUST 13/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET G130 IS SCALED TO 1 INCH EQUALS 20 FEET, |
| | PLEASE NOTE THIS PLAN DOES NOT LABEL DOORS IN CORRIDOR |
| | TO STAIRWELLS ETC. THE SAME ISSUE WITH SHEET A130 THE |
| | OVERALL PHASING PLAN. THE SHEET A130 IS SCALED TO A |
| | LARGER SCALE 1/8 INCH EQUALS ONE FOOT. THIS IS THE |
| | MINIMUM SCALE THAT CAN BE SUBMITTED FOR REVIEW UNDER |
| | THE 2014 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 107.2.1.4 QUALITY OF |
| | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| | MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| | OTHER ACCEPTABLE MEDIUM. |
| | |
| | THE SHEET A130 WOULD BE A GOOD SHEET TO USE AS THE LIFE |
| | SAFETY SHEET, TO ADD THE LIFE SAFETY LEGEND TO THIS |
| | SHEET AS WELL AS IDENTIFY THE CORRIDOR DOORS THAT ARE |
| | LABELED UNDER THE DOOR SCHEDULE. NOW I WOULD BE |
| | GUESSING WHICH DOOR IS WHICH, THE DOORS NEED |
| | IDENTIFICATION TAGS. 2014 FBC-B TABLE 716.5 OPENING |
| | PROTECTIVES. |
| | |
| | 2A) SHEET A130 SHOWS (2) PATIENT ROOMS TO BE ACCESSIBLE |
| | ROOMS, ROOM NUMBERS 320 AND 323, BUT THE MAIN DOOR FROM |
| | THE CORRIDOR DOES NOT HAVE THE REQUIRED 18 INCHES ON |
| | THE LATCH SIDE OF THE DOOR. 2014 FBC-ACCESS. CODE |
| | 404.2.4. NONE OF THE PATIENT ENTRY ROOMS SHOW AN 18 |
| | INCHES MANEUVERING CLEARANCES AS WELL AS DOOR NUMBERS |
| | 324,325, & 326. |
| | |
| | 2B) SHEET A130 SHOWS DOOR NUMBERS, 303A, 304A, 305A, |
| | 306A, 307A, 308A, 309A, 310A, 311A , 312A, 315A & 317A |
| | NEED TO SHOW COMPLIANCE WITH 2014 FBC-EXIST. BUILD. |
| | CODE 805.4.2.1 SUPPLEMENTAL REQUIREMENTS FOR DOOR |
| | SWINGS. 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY |
| | OPENED, SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN 7 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT |
| | REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF. |
| | |
| | 3) 2014 FBC-B 449.2 ADDITIONAL CODES AND STANDARDS FOR |
| | THE DESIGN AND CONSTRUCTION OF GENERAL, HOSPITALS, |
| | INCLUDING INTENSIVE RESIDENTIAL TREATMENT FACILITIES |
| | (IRTF) FOR CHILDREN AND ADOLESCENTS, AND UNLESS |
| | EXEMPTED BY CHAPTER 395.0163, FLORIDA STATUTES. 449.2.2 |
| | THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH |
| | CARE FACILITIES (THE GUIDELINES), AS REFERENCE IN |
| | CHAPTER 35 OF THIS CODE. |
| | |
| | 3A) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE |
| | ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO |
| | WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER THE |
| | HEADING SPECIAL PATIENT CARE ROOMS 2,1-2.4. PLEASE SEE |
| | SECTION REQUIREMENTS FOR 2.1-2.4.2 AIRBORNE INFECTION |
| | ISOLATION ROOMS (ALL ) ROOMS. (3) LOCATION. ALL ROOMS |
| | SHALL BE LOCATED WITHIN INDIVIDUAL NURSING UNITS OR |
| | GROUPED AS A SEPARATE ISOLATION UNIT. WHEN NOT REQUIRED |
| | FOR PATIENTS WITH AIRBORN INFECTIOUS DISEASES, USE OF |
| | THESE ROOMS FOR NORMAL ACUTE CARE PATENTS SHALL BE |
| | PERMITTED. |
| | |
| | 3B) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE |
| | ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO |
| | WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER |
| | SECTION 2.1-2.4.2.2 ALL ROOM REQUIREMENTS, (3) AN AREA |
| | FOR GOWNING AND STORAGE OF CLEAN AND SOILED MATERIALS |
| | SHALL BE LOCATED EITHER DIRECTLY OUTSIDE OR INSIDE THE |
| | ENTRY DOOR TO THE PATIENT ROOM. |
| | |
| | 3C) SHEET A130 INDICATES TO OF THE PATENT ROOMS ARE |
| | ISOLATION ROOMS. THERE IS NO MORE DESCRIPTION AS TO |
| | WHAT TYPE OF ISOLATION ROOM. THE GUIDELINES UNDER |
| | SECTION 2.1-2.4.2.4 SPECIAL DESIGN ELEMENTS SEE |
| | ARCHITECTURAL DETAILS (1)(A-C) , (2) (A-C) & (3). |
| | |
| | 4A) SHEET A130 SHOWS VARIOUS SYMBOLS NOT FOUND ON THE |
| | SHEET G130 THE LIFE SAFETY SHEET LEGEND NOR ON SHEET |
| | A130. PLEASE INDICATE WHAT THE SYMBOLS ARE: IC,CR,KP,RS |
| | & PTS ? ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. |
| | |
| | 4B) SHEET A130 SHOWS VARIOUS SYMBOLS NOT FOUND ON THE |
| | SHEET G130 THE LIFE SAFETY SHEET LEGEND NOR ON SHEET |
| | A130. PLEASE INDICATE WHAT THE ASTERISK SYMBOL |
| | REPRESENTS? ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.2.1.3. |
| | |
| | 5) SHEET A130 ROOM 321 THE MEDS. ROOM. PLEASE IDENTIFY |
| | FURTHER WHICH THIS ROOM IS EITHER A MEDICATION |
| | DISPENSING LOCATION (2.1-2.6.6 GUIDELINE) OR A |
| | MEDICATION PREPARATION ROOM IN COMPLIANCE WITH |
| | 2.1-2.6.6.1 OF THE GUIDELINE? |
| | |
| | 6) PLEASE PROVIDE COMPLIANCE WITH THE GUIDELINE |
| | 2.1-2.6.4. MULTIPURPOSE ROOM. AT LEAST ONE MULTIPURPOSE |
| | ROOM FOR EACH FACILITY SHALL BE PROVIDED FOR STAFF, |
| | PATIENTS, AND PATIENTS FAMILIES FOR PATIENT |
| | CONFERENCES, REPORTS, EDUCATION, TRAINING SESSIONS AND |
| | CONSULTATIONS. |
| | |
| | 7) SHEET A130 & SHEET A730 THE SOILED LINEN ROOM |
| | (HOLDING) 322 DOES NOT SHOW COMPLIANCE WITH THE |
| | GUIDELINE SECTION 2.1-2.6.10.2. IF A FLUSHING-RIM |
| | CLINICAL SINK IS NOT PROVIDED IN THIS ROOM, SUCH A SINK |
| | OR AN ACCEPTABLE ALTERNATIVE( E.G. A WATER CLOSET WITH |
| | BEDPAN-RINSING DEVICE LOCATED IN A PATIENTS TOILET ROOM |
| | SHALL BE PROVIDED ELSEWHERE ON THE NURSING UNIT FOR THE |
| | CLEANING OF BEDPANS. |
| | |
| | 8) SHEET A011; |
| | 8A) THIS SHEET IS TITLED EXTERIOR GLAZED OPENINGS, |
| | PLEASE PROVIDE WHERE THESE OPENINGS ARE BEING REPLACED. |
| | NOTES C,D & E ADD ALTERNATE, PLEASE PROVIDE A NARRATIVE |
| | TO WHAT THIS MEANS, IS THIS INDICATING A DIFFERENT |
| | DESIGN FROM WINDOW TYPE A & B MAKING THE OPENINGS |
| | LARGER OR IS A DIFFERENT LOCATION ALL TOGETHER? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8B) PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS |
| | |
| | 8C) IDENTIFY GLAZING/ MULLIONS. 2014 FBC-B 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. |
| | |
| | 8D) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 9) THERE IS NO WIND DESIGN CRITERIA FOR THE EXTERIOR |
| | WINDOW OPENING REFERENCED ON SHEET A011. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 9.2. RISK CATEGORY. |
| | |
| | 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 9.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 9.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |