Plan Review Details - Permit 16070942
Plan Review Stops For Permit 16070942
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2016-10-14 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-21 Cont ID  
Sent By jwitmer Date 2016-09-21 Time 09:52 Rev Time 0.00
Received By jwitmer Date 2016-09-21 Time 09:52 Sent To  
Notes
2016-09-21 10:02:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070942
 ADD: 525 OKEECHOBEE BLVD. SUITE # 1500
 CONT: MC GOWAN BUILDERS
 TEL: 305-774-7100
 E-MAIL: AMCMCGOWANBUILDERS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 21/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST, NO NARRATIVE SUBMITTED FOR BUILDING!!!!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 2ND REQUEST. SHEETSA-001.00 & A-101.00 IT APPEARS
 ONE OF THE ELEVATOR LOBBY DOORS ARE MISSING. THE
 INTERIOR DEMO PLAN 16061108 DOES NOT SHOW THIS SET OF
 DOORS BEING REMOVED. SHEET A-001.00 UNDER THE HEADING
 PROJECT INFORMATION DOES NOT MENTION THE REQUIREMENT
 FOR ELEVATOR LOBBY DOORS (FBC-B 713.14.1) OR THE
 EXCEPTIONS THAT CAN BE TAKEN. PLEASE PROVIDE CODE
 COMPLIANCE.
  
 3) NEW COMMENT. SHEET 35OF 37 OUT OF
 SEQUENCE!!!107.2.1.4 QUALITY OF BUILDING PLANS
  
 4) MISSING SHEET 10 OF 37/ A-001.00 IN ONE SET!!!!
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, IN TWO OR MORE SETS WITH EACH
 PERMIT APPLICATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By jwitmer Date 2016-08-10 Time 12:25 Rev Time 0.00
Received By jwitmer Date 2016-08-10 Time 07:30 Sent To  
Notes
2016-08-10 12:25:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070942
 ADD: 525 OKEECHOBEE BLVD. SUITE # 1500
 CONT: MC GOWAN BUILDERS
 TEL: 305-774-7100
 E-MAIL: AMCMCGOWANBUILDERS.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUSUST 10/ 2016
 ACTION: DENIED
  
 1) SHEETSA-001.00 & A-101.00 IT APPEARS ONE OF THE
 ELEVATOR LOBBY DOORS ARE MISSING. THE INTERIOR DEMO
 PLAN 16061108 DOES NOT SHOW THIS SET OF DOORS BEING
 REMOVED. SHEET A-001.00 UNDER THE HEADING PROJECT
 INFORMATION DOES NOT MENTION THE REQUIREMENT FOR
 ELEVATOR LOBBY DOORS (FBC-B 713.14.1) OR THE EXCEPTIONS
 THAT CAN BE TAKEN. PLEASE PROVIDE CODE COMPLIANCE.
  
 2) SHEETSA-001.00 & A-101.00 BOTH FLOOR PLANS 1/8 INCH
 SCALE, CODE COMPLIANCE FOR MANEUVERING CLEARANCES 18
 INCHES LATCH SIDE OF THE DOOR, FBC-ACCESSIBILTY CODE
 CAN NOT BE VERIFIED FOR THE FOLLOWING DOORS. 15-015,
 15-016, 15-035, 15-060, 15-065, 15-075 & 15-076.
  
 3) SHEETSA-001.00 & A-101.00 BOTH FLOOR PLANS BOTH
 INDICATE THE USE OF HORIZONTAL SLIDDING DOORS WITH AN
 AREA WITH AN OCCUPANT LOAD GREATER THAN 10, SEE DOOR
 LOCATIONS 15-074 & 15-081. 2014 FBC-B 1008.1.2
 EXCEPTION # 9. IN OTHER THAN GROUP H OCCUPANCIES,
 MANUALLY OPERATED HORIZONTAL SLIDING DOORS ARE
 PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS.
  
 4) SHEET G-004.00 ACCESSIBLE ELEMENTS & MEASUREMENTS:
 4A) FIGURE 2 SHOWS THE GRAB BAR BEING DIMENSIONED FROM
 THE CENTERLINE, PLEASE NOTE UNDER THE 2014
 ACCESSIBILITY CODE SECTION 609.4 THE DIMENSIONS ARE
 TAKEN FROM FINISH FLOOR TO THE TOP OF THE GRASPING
 SURFACE.
  
 4B) FIGURE 3 THE 60 INCH CLEAR FLOOR SPACE FOR THE
 WATER CLOSET INCLUDES THE LAVATORY. PLEASE REVIEW THE
 2014 ACCESSIBILITY CODE SECTIONS;
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 4C) BOTH THE WALL TELEPHONE, INTERCOM AND THERMOSTATE
 WILL NEED TO BE IN THE REACH RANGES AND OPERABLE PARTS.
 2014 FBC-ACCESSIBILITY CODE309.2 CLEAR FLOOR SPACE. A
 CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL BE
 PROVIDED. 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 4D) DEADBOLT IS LISTED AT A HEIGHT OF DEAD BOLT IS
 LISTED AT 5 FEET. WILL NEED TO COMPLY WITH 2014
 FBC-ACCESSIBILITY CODE309.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL BE
 PROVIDED. 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED
 WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED IN
 308.
  
 4E) THERE ARE NO DETAILS FOR ACCESSIBLE SIGNAGE
 COMPLIANCE: ACCESS. CODE 703.1 SIGNS SHALL COMPLY WITH
 703. WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE
 REQUIRED, EITHER ONE SIGN WITH BOTH VISUAL AND TACTILE
 CHARACTERS, OR TWO SEPARATE SIGNS, ONE WITH VISUAL, AND
 ONE WITH TACTILE CHARACTERS, SHALL BE PROVIDED.
  
 703.2 RAISED CHARACTERS. RAISED CHARACTERS SHALL COMPLY
 WITH 703.2 AND SHALL BE DUPLICATED IN BRAILLE COMPLYING
 WITH 703.3. RAISED CHARACTERS SHALL BE INSTALLED IN
 ACCORDANCE WITH 703.4.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-28 Cont ID  
Sent By albarran Date 2016-09-28 Time 17:26 Rev Time 0.00
Received By albarran Date 2016-09-28 Time 09:56 Sent To  
Notes
2016-09-28 17:27:58ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By albarran Date 2016-08-04 Time 16:33 Rev Time 0.00
Received By albarran Date 2016-08-04 Time 16:33 Sent To  
Notes
2016-08-23 08:03:12RESPONDED TO PHONE CALL, LEFT MESSAGE W/RECEP. MR. AKI
 CALLED ME BACK WITH A QUESTION ON THE RECEPTACLE
 CONTROL REQUIREMENTS. HE AGREES AND WILL COMPLY.
2016-08-04 16:34:07ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: UBS FINANCIAL SERVICES, INC.
 JOB ADDRESS: 525 OKEECHOBEE BLVD., SUITE 1500
 DESCRIPTION: INTERIOR OFFICE BUILD OUT 15TH FLOOR
 MASTER PERMIT:16070942
 REVISION:
  
 1. LIGHTING SHEET E3.1 IS SO CLUTTERED THAT IT IS VERY
 DIFFICULT TO PERCEIVE ROOM DIVIDERS THUS MAKING THE
 PLACEMENT OF EMERGENCY LIGHTING DIFFICULT AS WELL.
 A) THE AREA BETWEEN GRID LINES 1/5-F/M DOES NOT APPEAR
 TO HAVE SUFFICIENT EMERGENCY LIGHTING.
 B) ROOMS 15-032, 15-028, 15-026, 15-019, 15-011,
 15-097, 15-081 AND 15-076 AMONG OTHERS NOT IDENTIFIED
 MAY REQUIRE EMERGENCY LIGHTING.
 2. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-09 Cont ID  
Sent By wjolin Date 2016-09-09 Time 14:04 Rev Time 0.00
Received By wjolin Date 2016-09-09 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By wjolin Date 2016-07-26 Time 13:41 Rev Time 0.00
Received By wjolin Date 2016-07-26 Time 12:21 Sent To  
Notes
2016-07-26 13:41:44525 OKEECHOBEE BOULEVARD - #1500
 PERMIT #16070942
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-101.00: THIS FLOOR MAY BE A STAIRWELL RE-ENTRY
 FLOOR. PLEASE VERIFY WHAT FLOORS ARE RE-ENTRY FLOORS.
 OCCUPANTS ENTERING ONTO THE 15TH FLOOR VIA STAIR A WILL
 NOT HAVE FREE ACCESS TO STAIR B IN EVENT OF AN
 EMERGENCY. THIS BUILDING WAS PREVIOUSLY SETUP WITH
 SELECTIVE STAIRWELL RE-ENTRY IN ACCORDANCE WITH NFPA
 101 SECTION 7.2.1.5.8.1 WHEREBY:
 1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER
 EXIT.
 (2) THERE SHALL BE NOT MORE THAN FOUR STORIES
 INTERVENING BETWEEN STORIES WHERE IT IS POSSIBLE TO
 LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT.
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR
 NEXT-TO-TOP STORY SERVED BY THE STAIR ENCLOSURE, AND
 SUCH STORY SHALL ALLOW ACCESS TO ANOTHER EXIT.
 (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF.
 (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE
 PROVIDED WITH A SIGN ON THE STAIR SIDE INDICATING THE
 LOCATION OF THE NEAREST DOOR OPENING, IN EACH DIRECTION
 OF TRAVEL, THAT ALLOWS RE-ENTRY OR EXIT.
  
 SHEET A-101.00: HORIZONTAL SLIDING EGRESS DOORS
 (#15-012, #15-074 AND #15-081) SERVE AN EGRESS CAPACITY
 IN EXCESS OF 10 PERSONS AND REQUIRE THE DOORS TO BE
 SIDE SWINGING PER NFPA 101 SECTION 7.2.1.4.
  
 SHEET A-101.00: HALLWAY DOORS (#15-007 AND #15-016) ARE
 TROUBLESOME AS THEY SERVE EGRESS IN BOTH DIRECTIONS
 WITH OCCUPANT LOADS EXCEEDING 50 PERSONS. WITHOUT
 DOUBLE DOORS AT THESE LOCATIONS, THIS ARRANGEMENT DOES
 NOT APPEAR TO WORK. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS PER NFPA 101 SECTION 7.2.1.4.2.
  
 SHEET A-102.00: THE MAJORITY OF THE LOBBY AND CORRIDOR
 CARD READERS WITH MAGNETIC LOCKS PROHIBIT OCCUPANTS
 FROM REACHING A SECONDARY MEANS OF EGRESS WITHOUT A
 TOOL OR SPECIAL KNOWLEDGE. ONE EXAMPLE IS WAITING AREA
 #15-009 WHICH CANNOT ACCESS STAIR B WITHOUT USING AN
 ACCESS CARD.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-10-20 Cont ID  
Sent By gjohnson Date 2016-10-20 Time 09:26 Rev Time 0.00
Received By gjohnson Date 2016-10-20 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2016-09-30 Time 14:08 Sent To  
Notes
2016-09-30 14:09:25SENT TO GJOHNSON DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-28 Cont ID  
Sent By albarran Date 2016-09-28 Time 17:28 Rev Time 0.00
Received By albarran Date 2016-09-02 Time 09:37 Sent To  
Notes
2016-09-28 18:02:449/28/16 FAILED MULTIPLE TRADE REVIEWS READY FOR
 RESUBMITTAL. CONTRACTOR NOTIFIED VIA EMAIL. FILE SENT
 TO LARGE DENIED DRAWER M. MA
2016-09-08 09:37:57C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-23 Cont ID  
Sent By tklarge Date 2016-08-23 Time 06:50 Rev Time 0.00
Received By tklarge Date 2016-07-25 Time 14:00 Sent To  
Notes
2016-07-25 14:00:41C36

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 09:46 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By ccole Date 2016-08-05 Time 08:37 Rev Time 0.00
Received By ccole Date 2016-08-05 Time 08:37 Sent To  
Notes
2016-08-05 08:55:281ST REVIEW FBC- FIFTH EDITION 2014 MECHANICAL, EXISTING
 BUILDING CODES
 PERMIT #16070942
 8/5/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS.
  
 3) SHEET M-3: PROVIDE THE EFFICIENCY RATINGS OF THE
 HEAT PUMPS IN THE SCHEDULE- SEETABLE C403.2.3(2) FBC-14
 ENERGY CONSERVATION.
  
 4) M-3: PROVIDE THE SCOP FOR THE COMPUTER ROOM AC
 SYSTEMS CRAC- 15.1 & 15.2- TABLE C403.2.3(10) FBC-14
 ENERGY CONSERVATION.
  
 5) M-2.1: PLEASE PLACE A NOTE INDICATING ABOVE CEILING
 IS A RETURN AIR PLENUM- NO COMBUSTIBLE MATERIALS
 PERMITTED PER SECTION 602.2.1.
  
 6) M-2.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXISTING AHU.
  
 7) M-4.1 & M-4.2: PLEASE ENLARGE THESE DETAILS SO THE
 PRINT IS LARGER AND LEGIBLE- #10, 21, 23, 25, 26, 30 &
 34.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-10-20 Cont ID  
Sent By gjohnson Date 2016-10-20 Time 09:26 Rev Time 0.00
Received By gjohnson Date 2016-10-20 Time 08:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-10-14 Cont ID  
Sent By gjohnson Date 2016-10-14 Time 09:11 Rev Time 0.00
Received By gjohnson Date 2016-10-14 Time 09:11 Sent To  
Notes
2016-10-14 09:16:553RD-REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 IT DOES NOT APPEAR THAT THE PREVIOUS COMMENTS DATED
 9/26/16 WERE ADDRESSED THE RESPONSE LETTER PROVIDED WAS
 FROM COMMENTS DATED 8/23/16 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 1. SHT. G-004.00 FIG.#3 CLEARANCE FOR TOILET SHOULD
 SHOW CLEARLY 60" MEASURED FROM SIDE WALL . THE PLAN
 SHOWS 60" WITH ARROW POINTING TOWARD BACK WALL OF
 TOILET PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT.G-004.00 FIG. #5 SHOWS HEIGHT OF LAV AT 34" MIN
 IT SHALL SHOW 34" MAX NOT MIN. PET FBC ACC 606.3
  
 4. 3ND REQUEST PREVIOUS COMMENT DOES NOT COMPLY. SHT.
 A205 - DETAIL #5 - THE COUNTERTOP SHALL BE A MAXIMUM OF
 34 INCHES ABOVE THE FINISH FLOOR. 2014 FAC SEC.606.3.
  
 5. 3ND REQUEST SHT. M2.2 - DRAWING NOTE #2 - THE
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 PER WPB CODE OF ORDINANCES CHAPT. 90, ART.III, SEC.
 90-126 (5).
 A) NOTE ON SHT. M-2.2 IS UNCLEAR IT INDICATES DISCHARGE
 ON CONDENSATE INTO MOP SINK WHICH IS SANITARY DRAINAGE,
 THEN IT SAYS CONDENSATE SHALL NOT DISCHARGE INTO
 SANITARY PLEASE CLARIFY.
 B) PROVIDE CONDENSATE RISER DIAGRAM SHOWING DISCHARGE
 INTO STORM DRAINAGE. PER WPB AMEND TO FBC 107.2.1
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-09-28 Cont ID  
Sent By gjohnson Date 2016-09-28 Time 09:12 Rev Time 0.00
Received By gjohnson Date 2016-09-26 Time 15:58 Sent To  
Notes
2016-09-28 09:32:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. G-004.00 FIG.#3 CLEARANCE FOR TOILET SHOULD
 SHOW CLEARLY 60" MEASURED FROM SIDE WALL . THE PLAN
 SHOWS 60" WITH ARROW POINTING TOWARD BACK WALL OF
 TOILET PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT.G-004.00 FIG. #5 SHOWS HEIGHT OF LAV AT 34" MIN
 IT SHALL SHOW 34" MAX NOT MIN. PET FBC ACC 606.3
  
 3. COMPLIANCE WITH PREVIOUS COMMENT #3 CAN NOT BE
 CHECKED SHT. A-001 IS MISSING FROM PLAN SET. PER WPB
 AMEND TO FBC 107.2.1
  
 4. 2ND REQUEST PREVIOUS COMMENT DOES NOT COMPLY. SHT.
 A205 - DETAIL #5 - THE COUNTERTOP SHALL BE A MAXIMUM OF
 34 INCHES ABOVE THE FINISH FLOOR. 2014 FAC SEC.606.3.
  
 5. 2ND REQUEST SHT. M2.2 - DRAWING NOTE #2 - THE
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 PER WPB CODE OF ORDINANCES CHAPT. 90, ART.III, SEC.
 90-126 (5).
 A) NOTE ON SHT. M-2.2 IS UNCLEAR IT INDICATES DISCHARGE
 ON CONDENSATE INTO MOP SINK WHICH IS SANITARY DRAINAGE,
 THEN IT SAYS CONDENSATE SHALL NOT DISCHARGE INTO
 SANITARY PLEASE CLARIFY.
 B) PROVIDE CONDENSATE RISER DIAGRAM SHOWING DISCHARGE
 INTO STORM DRAINAGE. PER WPB AMEND TO FBC 107.2.1
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By tklarge Date 2016-08-23 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-08-23 Time 05:00 Sent To  
Notes
2016-08-23 06:41:141)DRAWING G-004.00 - THE FOLLOWING THREE COMMENTS APPLY
 TO THE SAME SHEET.
 FIG. #2 - THE HEIGHT OF THE GRAB BAR SHALL BE MEASURED
 FROM THE FINISH FLOOR TO THE TOP OF THE GRIPPING
 SURFACE PER THE 2014 FAC SEC. 609.4.
 FIG.#3 - THE CLEAR FLOOR SPACE FOR THE WATEER CCLOSET
 SHALL CCOMPLY WITH THE FAC SEC. 604.3.
 FIG.#5 - THE MAXIMUM HEIGHT TO THE TOP OF THE LAVATORY
 SHALL BE 34 INCHES. THE DETAIL SHOWS 29 INCHES MINIMUM.
 FAC SEC. 606.3.
 2) THE COFFEE MACHINES, ICE MAKERS, ESPRESSO MACHINE,
 ETC. SHALL BE EQUIPPED WITH BACKFLOW PREVENTERS IN
 ACCORDANCE THE 2014 FPC SEC. 608.3, 608.16.10.
 3) PER TABLE 403.1 OF THE 2014 FPC AND THE OCCUPANT
 LOAD SHOWN ON THE PLANS THE TOTAL NUMBER OF SANITARY
 FACILITIES REQUIRED FOR THE MALES IS 5 WATER CLOSETS
 AND 4 LAVATORIES AND 5 WATER CLOSETS AND 4 LAVATORIES
 FOR THE FEMALES. INCLUDING THE EXISTING FACILITIES, THE
 SPACE IS DEFICIENT OF ONE WATER CLOSET EACH FOR THE
 MALES AND FEMALES AND TWO LAVATORIES EACH FOR THE MALES
 AND FEMALES. THE PROPOSED UNISEX TOILET ROOM CAN HELP
 SATISFY THE REQUIREMENTS FOR ONE GENDER ONLY.
 4) SHT. A205 - DETAIL #5 - THE COUNTERTOP SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR. 2014 FAC
 SEC.606.3.
 5) SHT. M2.2 - DRAWING NOTE #2 - THE CONDENSATE SHALL
 NOT DDISCHARGE TO THE SANITARY SYSTEM PER WPB CODE OF
 ORDINANCES CHAPT. 90, ART.III, SEC. 90-126 (5).
 6) SHT. P-2 - IDENTIFY RISERS #1 & #2 ON THE FLOOR
 PLAN.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE CHRONOMITE WATER HEATEER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 8) VENTS OTHER THAN STACK VENTS OR VENT STACKS EXCEEDIN
 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE
 NOMINAL PIPE SIZE FOR THE ENTIRE DEEVELOPED LENGTH OF
 THE VENT PIPE IN ACCORDANCE WITH THE 2014 FPC
 SEC.906.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  