Plan Review Details - Permit 16070909
Plan Review Stops For Permit 16070909
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-09 Cont ID  
Sent By jwitmer Date 2016-11-09 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2016-11-09 Time 08:27 Sent To  
Notes
2016-11-09 08:27:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070909
 ADD: 5112 GEORGIA AVE.
 CONT: TD GONE BUILDING
 TEL: 561-436-4047
 E-MAIL; [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED.NOV. 09 2016
 ACTION: PROVISO
  
 1) . CONTRACTOR AT OWN RISK!!!
 SHEET S1 DETAIL 3 & 4 BOTH SHOW THE USE OF A ROOF TOP
 PRESSURE TREATED 4 X 4. PLEASE NOTE PITCH PANS HAVE NOT
 BEEN USED IN THE CODE FOR SOME TIME NOW. PLEASE REVIEW
 UNDER THE 2014 FBC-B 1509.6.5 AND TABLE 1509.6.5.
 1509.6.5 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL
 UNITS SHALL BE MOUNTED ABOVE THE ROOF SURFACE, OR WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED
 EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT
 IN ACCORDANCE WITH TABLE 1509.6.5.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2016-10-14 Time 06:27 Sent To  
Notes
2016-10-14 07:11:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070909
 ADD: 5112 GEORGIA AVE.
 CONT: TD GONE BUILDING
 TEL: 561-436-4047
 E-MAIL; [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. 14/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST . ORIGINALLY 3 SETS OF PLANS SUBMITTED.
 ON THE RE-SUBMITTAL ONLY 2 SETS OF PLANS WERE
 SUBMITTED. ONLY 2 SOILS REPORTS WERE SUBMITTED. THIS IS
 A RESIDENT INSPECTOR PROJECT REQUIRING 3 SETS OF
 DOCUMENTS. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 110.3.9.
 1ST ROUND COMMENTS. FOR RESIDENT INSPECTOR PROJECTS 3
 SETS OF PLANS ARE REQUIRED. ONE FOR CITY RECORD
 RETENTION, ONE FOR THE CONTACTOR AND THE 3RD SET FOR
 THE RESIDENT INSPECTOR. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.1.
  
 2) SEMI-COMPLIED ONLY 2 SETS OF PLANS.
 1ST ROUND OF COMMENTS. THE SHEET A100 DESIGNED BY
 ANGELIO DAVILA # 16639 HAS NOT SIGNED NOR SEALED THE
 ARCHITECTURAL PLANS. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 3)COMPLIED
  
 4) COMPLIED
  
 5) 2ND REQUEST. CONTRACTOR AT OWN RISK!!!
 SHEET S1 DETAIL 3 & 4 BOTH SHOW THE USE OF A ROOF TOP
 PRESSURE TREATED 4 X 4. PLEASE NOTE PITCH PANS HAVE NOT
 BEEN USED IN THE CODE FOR SOME TIME NOW. PLEASE REVIEW
 UNDER THE 2014 FBC-B 1509.6.5 AND TABLE 1509.6.5.
 1509.6.5 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL
 UNITS SHALL BE MOUNTED ABOVE THE ROOF SURFACE, OR WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED
 EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT
 IN ACCORDANCE WITH TABLE 1509.6.5.
  
 6) COMPLIED
  
 7) 2ND REQUEST. THE RESPONSE INDICATES THE BUILDING
 PERMIT HAS TO BE ISSUED BEFORE THE FIRE SPRINKLER CAN
 APPLY FOR THEIR PERMIT. 2014 FBC-B 903.2.4.1
 WOODWORKING OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY
 FIRE AREAS THAT CONTAIN WOODWORKING OPERATIONS IN
 EXCESS OF 2,500 SQUARE FEET (232 M2) IN AREA WHICH
 GENERATE FINELY DIVIDED COMBUSTIBLE WASTE OR USE FINELY
 DIVIDED COMBUSTIBLE MATERIALS.
 THIS IS A BUILDING CODE ISSUE THAT HAS TO BE SATISFIED
 BEFORE PERMIT ISSUANCE, THE FIRE SPRINKLER DESIGN
 DOCUMENTS ARE REQUIRED TO BE SUBMITTED REVIEWED AND
 APPROVED BEFORE ISSUANCE OF A PERMIT. A SECOND SET OF
 FIRE SPRINKLER PLANS WILL BE REQUIRED, AND TO SUBMIT
 SEPARATELY UNDER A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
  
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1ST ROUND OF COMMENTS. THE ARCHITECTURAL PLANS ARE
 SILENT ABOUT THE REQUIREMENTS FOR FIRE SPRINKLERS IN
 THE RELOCATED DUST COLLECTOR DUCT. 2014 FBC-B 903.2.4.1
 WOODWORKING OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY
 FIRE AREAS THAT CONTAIN WOODWORKING OPERATIONS IN
 EXCESS OF 2,500 SQUARE FEET (232 M2) IN AREA WHICH
 GENERATE FINELY DIVIDED COMBUSTIBLE WASTE OR USE FINELY
 DIVIDED COMBUSTIBLE MATERIALS.
  
 8-10) COMPLIED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-08-01 Time 07:04 Sent To  
Notes
2016-08-01 08:43:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070909
 ADD: 5112 GEORGIA AVE.
 CONT: TD GONE BUILDING
 TEL: 561-436-4047
 E-MAIL; [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 01/ 2016
 ACTION: DENIED
  
 1) FOR RESIDENT INSPECTOR PROJECTS 3 SETS OF PLANS ARE
 REQUIRED. ONE FOR CITY RECORD RETENTION, ONE FOR THE
 CONTACTOR AND THE 3RD SET FOR THE RESIDENT INSPECTOR.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.1.
  
 2) THE SHEET A100 DESIGNED BY ANGELIO DAVILA # 16639
 HAS NOT SIGNED NOR SEALED THE ARCHITECTURAL PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
  
 3) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS
 INDICATE UNDER WHICH CODES AND EDITIONS THE PLANS WERE
 CREATED. PLEASE NOTE ON JULY 01/2016 THE 2016
 SUPPLEMENTS TO THE 5TH EDITION (2014) OF THE FLORIDA
 BUILDING CODE FAMILY OF CODES.
  
 4) PLEASE PROVIDE UNDER THE 2014/ 2016 FBC- EXISTING
 BUILDING CODE WHICH COMPLIANCE METHODS WERE USED IN
 DEVELOPING THESE DRAWINGS. 2014 FBC-EXISTING BUILDING
 CODE SECTION 301 COMPLIANCE METHODS. 301.1. THE REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS
 SELECTED BY THE APPLICANT. APPLICATION OF A METHOD
 SHALL BE THE SOLE BASIS FOR ASSESSING THE COMPLIANCE OF
 WORK PERFORMED UNDER A SINGLE PERMIT.
  
 5) SHEET S1 DETAIL 3 & 4 BOTH SHOW THE USE OF A ROOF
 TOP PRESSURE TREATED 4 X 4. PLEASE NOTE PITCH PANS HAVE
 NOT BEEN USED IN THE CODE FOR SOME TIME NOW. PLEASE
 REVIEW UNDER THE 2014 FBC-B 1509.6.5 AND TABLE
 1509.6.5. 1509.6.5 MECHANICAL UNITS. ROOF MOUNTED
 MECHANICAL UNITS SHALL BE MOUNTED ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.6.5.
  
 6) SHEET S1 DETAIL # 3 INDICATES THE 33 INCH DUST
 COLLECTOR DUCT TO BE SUPPORTED BY 2 X2 X ? INCH L
 ANGLE. PLEASE NOTE THE PLANS DO NOT PROVIDE HOW THE
 ANGLE IS TO BE ANCHORED TO THE DUST COLLECTOR DUCT.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) THE ARCHITECTURAL PLANS ARE SILENT ABOUT THE
 REQUIREMENTS FOR FIRE SPRINKLERS IN THE RELOCATED DUST
 COLLECTOR DUCT. 2014 FBC-B 903.2.4.1 WOODWORKING
 OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY FIRE AREAS
 THAT CONTAIN WOODWORKING OPERATIONS IN EXCESS OF 2,500
 SQUARE FEET (232 M2) IN AREA WHICH GENERATE FINELY
 DIVIDED COMBUSTIBLE WASTE OR USE FINELY DIVIDED
 COMBUSTIBLE MATERIALS.
  
 8) PLEASE NOTE UNDER THE 2014 FBC-B TABLE 307.1(1)
 COMBUSTIBLE DUST WHEN THE MAXIMUM ALLOWABLE QUANTITIES
 ARE EXCEEDED THEN CLASSIFIED AS A H-2 OCCUPANCY. PLEASE
 SHOW HOW COMPLIANCE WILL BE ACHIEVED.
  
 9) THERE IS NO INFORMATION AS TO THE SILOS FRAME EXCEPT
 FOR THE SIZE OF THE LEG W6 X 25 (VERIFY) HOW WILL THE
 SILO BE ATTACHED TO THE FRAME WORK. 2014 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 10) PLEASE INDICATE WHAT PART OF THE DUST COLLECTION
 SYSTEM IS EXISTING AND WHAT PART IS NEW. 2014 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-09 Cont ID  
Sent By vperez Date 2016-11-09 Time 11:32 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-25 Cont ID  
Sent By vperez Date 2016-07-25 Time 06:52 Rev Time 0.00
Received By vperez Date 2016-07-25 Time 06:42 Sent To  
Notes
2016-07-25 06:52:43INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. MAINTAIN MINIMUM BURIAL DEPTHS FOR RELOCATED
 CONDUIT. NEC 300.5
 2. NEC 110.26- PROVIDE PROPER CLEARANCE FOR RELOCATED
 EQUIPMENT AND LABELING, TO BE FIELD VERIFIED. FBC
 107.3.5
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By scaldero Date 2016-11-07 Time 10:11 Rev Time 0.00
Received By scaldero Date 2016-11-07 Time 10:11 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-25 Cont ID  
Sent By scaldero Date 2016-07-25 Time 11:13 Rev Time 0.00
Received By scaldero Date 2016-07-25 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-09 Cont ID  
Sent By vperez Date 2016-11-09 Time 11:32 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 11:32 Sent To  
Notes
2016-11-01 13:40:18RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2016-09-26 Time 10:16 Sent To  
Notes
2016-09-27 10:16:19B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-01 Cont ID  
Sent By jwitmer Date 2016-08-01 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-07-22 Time 12:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By ccole Date 2016-10-04 Time 16:46 Rev Time 0.00
Received By ccole Date 2016-10-04 Time 16:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 06:53 Rev Time 0.00
Received By ccole Date 2016-07-26 Time 06:51 Sent To  
Notes
2016-07-26 07:44:551ST REVIEW MECHANICAL
 PERMIT #16070909
 7/26/16
  
 1) SHEET A100: THE ARCHITECT OF RECORD MUST PLACE HIS
 SIGNATURE AND SEAL ON THE PLANS AS REQUIRED BY SECTION
 481.221(2) FLORIDA STATUTES, AND SECTION 61G1-16.001
 FLORIDA ADMINISTRATIVE CODE.
  
 2) A100: THE DUST COLLECTOR IS IDENTIFIED AS BOTH "NEW"
 AND "RELOCATED". PLEASE CLARIFY. IF THE COLLECTOR IS
 NEW, PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN,
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH SHOP
 DRAWING APPROVAL SIGNATURE BY THE ARCHITECT OF RECORD.
  
 3) A100: PLEASE ENLARGE THE MEASUREMENTS SHOWN ON THE
 BETWEEN THE DUST COLLECTOR AND SHAVING HOUSE, AND FROM
 THE TWO STRUCTURES TO WHAT APPEARS TO BE A PROPERTY
 LINE OR RIGHT OF WAY LINE. REFER TO SECTIONS 501.3.1(1)
 & 511.1 AND PROVIDE A CLEARANCE DISTANCE MEASUREMENT TO
 THE EXISTING BUILDING, AND HEIGHT MEASUREMENTS FOR THE
 COLLECTOR, SHAVING HOUSE, AND THE EXISTING BUILDING.
  
 4) A100: SHOW THE POINT OF CONNECTION FOR THE NEW
 EXHAUST DUCT TO THE EXISTING, AND PROVIDE THE LENGTH OF
 THE DUCT RUNS; THE TYPE, SIZE, AND GAGE OF DUCTWORK;
 SPECIFICATIONS FOR DUCT SUPPORTS INCLUDING SPACINGS,
 HEIGHT OF THE DUCTWORK ABOVE THE ROOF.
  
 5) A100: INDICATE IF A NEW, LARGER CAPACITY EXHAUST FAN
 IS TO BE INSTALLED DUE TO THE INCREASED LENGTH OF THE
 DUCT RUN AND PROVIDE A FAN SCHEDULE AND CALCULATIONS IF
 APPLICABLE. OTHERWISE, PLEASE INDICATE THE MAKE AND
 MODEL AND CFM CAPACITY OF THE EXISTING EXHAUST FAN.
  
 6) A100: PROVIDE VENTING DETAILS FOR THE DUST COLLECTOR
 AND SHAVING HOUSE.
  
 7) REFER TO SECTION 301.15 AND PROVIDE WIND LOAD
 ENGINEERING FOR INSTALLATION OF THE DUCT WORK AND DUCT
 WORK SUPPORTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-03 Cont ID  
Sent By njwira Date 2016-10-03 Time 16:39 Rev Time 0.00
Received By njwira Date 2016-09-30 Time 15:15 Sent To  
Notes
2016-10-03 16:40:2510/3/16- PASSED
  
 SITE PLAN RECEIVED SHOWING THAT THE MECHANICAL
 EQUIPMENT IS NOT LOCATED IN A REQUIRED SETBACK.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By nwair Date 2016-07-27 Time 15:36 Rev Time 0.00
Received By njwira Date 2016-07-27 Time 15:12 Sent To B
Notes
2016-07-27 15:37:227/26/16- FAILED
  
 1. PLEASE PROVIDE DRAWINGS IN THE SITE PLAN SHOWING
 WHERE THE EQUIPMENT IS BEING REMOVED AND WHERE IT IS
 GOING.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  