Plan Review Details - Permit 16070890
Plan Review Stops For Permit 16070890
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-09 Cont ID  
Sent By skennedy Date 2016-11-09 Time 15:29 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By rmcdouga Date 2016-10-26 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2016-10-25 Time 18:44 Sent To  
Notes
2016-10-26 17:28:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE INFORMATION ON SHEET 1 INCORRECTLY
 REFERENCES THE 2016 EDITION OF THE FLORIDA BUILDING
 CODE WHICH DOES NOT EXIST. THE 2014 FLORIDA BUILDING
 CODE APPLIES TO THIS PROJECT. PLEASE REVISE.
  
 2) FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. SHOW
 COMPLIANCE. PROVIDE AN EXTERIOR WALL SECTION SHOWING
 ALL CONNECTORS THAT COMPRISE THE CONTINUOUS LOAD PATH
 FROM ROOF TO FOUNDATION. FBC 107.2.1.3
  
 3) PROVIDE ELEVATIONS OF THE PROPOSED WORK. FBC
 107.2.1.3
  
 4) IDENTIFY THE WINDOW TYPES ON THE PLANS (FOR EXAMPLE:
 SINGLE HUNG, FIXED, CASEMENT, ETC.) FBC 107.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE WINDOWS.
  
 6) SHOW COMPLIANCE WITH FBC - R301.2.1.2 PROTECTION OF
 OPENINGS.
 GLAZED OPENINGS IN BUILDINGS LOCATED IN WINDBORNE
 DEBRIS REGIONS SHALL BE PROTECTED FROM WINDBORNE
 DEBRIS. GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST
 OF ASTM E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD
 12, TAS 201, 202 AND 203 OR AAMA 506, AS APPLICABLE.
 THE APPLICABLE WIND ZONES FOR ESTABLISHING MISSILE
 TYPES IN ASTM E 1996 ARE SHOWN IN SECTION R301.2.1.2.1.
 GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE
 DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED
 IMPACT-RESISTING STANDARD OR ANSI/DASMA 115.
  
 7) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 8) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECTIONS 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 9) SPECIFY THE WALL AND CEILING INSULATION R-VALUES
 THAT CORRESPOND TO THE ENERGY FORMS ON THE PLANS. FBC
 107.2.1
  
 10) SHOW COMPLIANCE WITH FBC-R806.1 FOR REQUIRED ROOF
 VENTILATION.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-02 Cont ID  
Sent By rmcdouga Date 2016-09-02 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2016-09-01 Time 18:34 Sent To  
Notes
2016-09-01 18:45:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE PLANS THAT WERE SUBMITTED ARE MISSING TOO MUCH
 INFORMATION TO DO AN ADEQUATE PLAN REVIEW. LISTED BELOW
 ARE THE MAIN ISSUES THAT NEED TO BE ADDRESSED.
 ADDITIONAL COMMENTS MAY RESULT WHEN THE REVISED PLANS
 ARE SUBMITTED.
  
 1) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2) FBC-R 302 FIRE-RESISTANT CONSTRUCTION SUBMIT TWO
 COPIES OF A SURVEY/SITE PLAN THAT SHOWS THE LOCATION OF
 THE ENCLOSED CARPORT AND THE DISTANCES TO PROPERTY
 LINES AND OTHER STRUCTURES LOCATED ON THE SAME
 PROPERTY.
  
 3) FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE. PROVIDE TWO COPIES OF AN EXTERIOR WALL
 SECTION THAT SHOWS THE EXTERIOR GRADE, THE FINISH FLOOR
 ELEVATION AND THE CEILING ELEVATION.
  
 4) FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL
 SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND
 SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE
 TO REMAIN ON THE SITE OR PLOT. THE BUILDING OFFICIAL IS
 AUTHORIZED TO WAIVE OR MODIFY THE REQUIREMENT FOR A
 SITE PLAN WHEN THE APPLICATION FOR PERMIT IS FOR
 ALTERATION OR REPAIR OR WHEN OTHERWISE WARRANTED.
  
 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 6) SUBMIT TWO SETS OF A FLOOR PLAN OF THE EXISTING
 STRUCTURE AND PROPOSED ENCLOSED CARPORT ROOM THAT
 SPECIFIES THE ROOM TYPE (E.G. BEDROOM, LIVING ROOM,
 ETC.). THIS IS REQUIRED TO DETERMINE WHAT EFFECT IF ANY
 ENCLOSING THE CARPORT HAS ON THE ROOMS THAT ARE
 ADJACENT TO IT. FBC-R310.1 EMERGENCY ESCAPE AND RESCUE
 REQUIRED. BASEMENTS, HABITABLE ATTICS AND EVERY
 SLEEPING ROOM SHALL HAVE AT LEAST ONE OPERABLE
 EMERGENCY ESCAPE AND RESCUE OPENING.
  
 7) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND
 COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO
 FBC-R301.2 ON THE PLANS.
  
 8) FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. SHOW
 COMPLIANCE. THE CONVERSION OF THE CARPORT TO HABITABLE
 SPACE IS A CHANGE OF USE PER THE EXISTING BUILDING CODE
 THE EXISTING STRUCTURE IS REQUIRED TO BE EVALUATED FOR
 STRUCTURAL CONFORMANCE WITH THE 2014 FBC.
  
 9) DETERMINE IF THE EXISTING FOUNDATION THAT IS
 SUPPORTING THE BLOCK IN FILL WALLS IS ADEQUATE. IF IT
 IS MORE THAN JUST A 4" SLAB, SHOW THE EXISTING
 FOUNDATION ON THE PLANS. IF THE SLAB HAS TO BE CUT BACK
 TO INSTALL A NEW FOUNDATION SPECIFY THE SIZE AND
 REINFORCING ON THE PLANS. FBC R403.1
  
 10) SPECIFY THE REQUIRED EMBED DEPTH AND THE TYPE OF
 EPOXY THAT WILL BE USED TO ANCHOR THE VERTICAL
 REINFORCING BARS INTO THE FOUNDATION AND THE TIE BEAM.
 FBC 107.2.1
  
 11) SPECIFY THE LENGTH, EMBED DEPTH AND SPACING OF THE
 REBARS THAT ARE SHOWN ANCHORING THE NEW BLOCK WALL TO
 THE EXISTING WALL / COLUMNS. INDICATE THE WALL AND
 COLUMN CONSTRUCTION MATERIALS. (E.G. POURED CONCRETE,
 CONCRETE BLOCK, WOOD) FBC 107.2.1
  
 12) SPECIFY THE SIZE AND TYPE OF WINDOWS THAT WILL BE
 INSTALLED. FBC 107.2.1
  
 13) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE WINDOWS.
  
 14) SHOW COMPLIANCE WITH FBC - R301.2.1.2 PROTECTION OF
 OPENINGS.
 GLAZED OPENINGS IN BUILDINGS LOCATED IN WINDBORNE
 DEBRIS REGIONS SHALL BE PROTECTED FROM WINDBORNE
 DEBRIS. GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST
 OF ASTM E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD
 12, TAS 201, 202 AND 203 OR AAMA 506, AS APPLICABLE.
 THE APPLICABLE WIND ZONES FOR ESTABLISHING MISSILE
 TYPES IN ASTM E 1996 ARE SHOWN IN SECTION R301.2.1.2.1.
 GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE
 DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED
 IMPACT-RESISTING STANDARD OR ANSI/DASMA 115.
  
 15) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 16) FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 17) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECTIONS 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 18) SPECIFY THE WALL AND CEILING INSULATION R-VALUES
 THAT CORRESPOND TO THE ENERGY FORMS ON THE PLANS. FBC
 107.2.1
  
 19) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-11-07 Cont ID  
Sent By skennedy Date 2016-11-07 Time 15:30 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-31 Cont ID  
Sent By mvaldes Date 2016-10-31 Time 11:26 Rev Time 0.00
Received By mvaldes Date 2016-10-31 Time 10:38 Sent To  
Notes
2016-10-31 11:26:382ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] SINCE HABIATBLE SQUARE FOOTAGE IS BEING ADDED TO THE
 DWELLING PLEASE PROVIDE EXISTING ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL,
 COMPLETE LOAD CALCULATIONS INCLUDING NEW ADDED LIVING
 SPACE, AND PANEL SCHEDULES REFLECTING EXISTING
 CIRCUITS. THIS INFORMATION IS NEEDED IN ORDER TO VERIFY
 CAPACITY REQUIREMENTS FBC- 107.3.5.3.
  
 2] ADD ELECTRICAL GENERAL NOTES FOR TAMPER-RESISTANT
 RECEPTACLES AND ARC-FAULT PROTECTION PER FBC-R SECTIONS
 E4002.14 & E3902.13.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By albarran Date 2016-08-01 Time 15:47 Rev Time 0.00
Received By albarran Date 2016-08-01 Time 15:13 Sent To  
Notes
2016-08-01 15:48:47ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: MARY ANN SPAGNOLI
 JOB ADDRESS: 2036 WARE DR.
 DESCRIPTION: ENCLOSING CARPORT
 MAST. PERMIT: 16070890
 REVISION:
  
 EVEN THOUGH THE PROPOSED SCOPE OF WORK IS MINIMAL,
 THERE ARE CERTAIN REQUIREMENTS WHICH HAVE TO BE ADHERED
 TO BELOW ARE THE RESULTS OF THE FAILED REVIEW WITH AN
 EXPLANATION OF HOW TO CORRECT THE ISSUES. THE CARPORT
 NOW BECOMES HABITABLE SPACE
  
 1. NEC 210.12 REQUIRES ARC-FAULT PROTECTION ON THE
 CIRCUITS FOR THE AREA IN QUESTION. THIS CAN BE
 ADDRESSED WITH A NOTE ON THE PLANS.
 2. NEC 210.52(A) HAS SPECIFIC SPACING REQUIREMENTS FOR
 OUTLETS IN HABITABLE ROOMS. WITHOUT A SCALE IT IS
 DIFFICULT TO DETERMINE LINEAR WALL SPACE BUT THERE
 CAN?T BE MORE THAT 6? ANYWHERE ALONG THE FLOOR LINE
 BETWEEN OUTLETS. CHECK YOUR MEASUREMENT AS IT APPEARS
 THAT THERE IS A MISSING OUTLET ALONG THE FRONT WALL.
 3. NEC 210.70(A) REQUIRES THAT THERE BE ILLUMINATION ON
 THE OUTSIDE OF THE DOOR. DRAW IN THE LIGHT AND
 CORRESPONDING SWITCH.
 4. NEC 406.12 REQUIRES THAT THE NEW RECEPTACLES BE
 LISTED TAMPER-RESISTANT. THIS TOO CAN BE ADDRESSED WITH
 A NOTE ON THE PLANS.
 5. FBC-R314 REQUIRES THAT YOU COME INTO COMPLIANCE WITH
 THE SMOKE DETECTOR REQUIREMENTS FOR NEW CONSTRUCTION.
 ALSO ADDRESSED WITH A NOTE ON THE PLANS.
 6. IF THE NEW AREA WILL BE USED FOR SLEEPING PURPOSES,
 A SMOKE DETECTOR SHALL BE INSTALLED AS PER CODE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-09 Cont ID  
Sent By skennedy Date 2016-11-09 Time 15:30 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-31 Cont ID  
Sent By mvaldes Date 2016-10-31 Time 11:28 Rev Time 0.00
Received By mvaldes Date 2016-10-21 Time 10:37 Sent To  
Notes
2016-10-24 10:37:39R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-02 Cont ID  
Sent By rmcdouga Date 2016-09-02 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2016-07-28 Time 10:54 Sent To  
Notes
2016-07-29 10:54:13R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-11-09 Cont ID  
Sent By skennedy Date 2016-11-09 Time 15:29 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:30 Sent To  
Notes
2016-11-07 15:31:29APPLICANT CHECKED OUT ONE SET TO TAKE FOR IMPACT FEE
 REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By rmcdouga Date 2016-09-01 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2016-09-01 Time 18:21 Sent To  
Notes
2016-09-01 18:22:15BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-09 Cont ID  
Sent By skennedy Date 2016-11-09 Time 15:30 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By rmcdouga Date 2016-10-26 Time 18:09 Rev Time 0.00
Received By rmcdouga Date 2016-10-25 Time 18:52 Sent To  
Notes
2016-10-26 18:21:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC-R303.9
 REQUIRES THE NEW HABITABLE SPACE TO BE HEATED AND THE
 USE OF PORTABLE SPACE HEATERS CAN NOT BE USED TO
 ACHIEVE COMPLIANCE WITH THIS SECTION.
  
 3) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-01 Cont ID  
Sent By rmcdouga Date 2016-09-01 Time 18:33 Rev Time 0.00
Received By rmcdouga Date 2016-09-01 Time 18:29 Sent To  
Notes
2016-09-01 18:33:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By skennedy Date 2016-11-07 Time 15:30 Rev Time 0.00
Received By skennedy Date 2016-11-07 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By skennedy Date 2016-10-31 Time 14:30 Rev Time 0.00
Received By skennedy Date 2016-10-31 Time 14:29 Sent To  
Notes
2016-10-31 14:31:251ST REVIEW FBC-R 2014
  
 DESIGN LOOKS GOOD BUT PLEASE SUPPLY A PLUMBING RISER
 DIAGRAM.
  
 STEVEN KENNEDY
 561 805-6710
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-23 Cont ID  
Sent By njwira Date 2016-08-23 Time 16:49 Rev Time 0.00
Received By njwira Date 2016-08-22 Time 13:53 Sent To  
Notes
2016-08-23 16:50:16IF THIS IS A HOME OCCUPATION PLEASE FILL OUT A BUSINESS
 TAX
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By njwira Date 2016-08-02 Time 15:28 Rev Time 0.00
Received By njwira Date 2016-08-02 Time 14:29 Sent To M
Notes
2016-08-02 15:32:528/2/16- FAILED
  
 ZONE- SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 FAILED
  
 1. PLEASE PROVIDE TWO(2) COPIES OF A SURVEY OR SITE
 PLAN SHOWING HOW THE ADDITION RELATES TO THE SETBACK
 REQUIREMENTS.
 2. WHAT IS GOING INTO THE ENCLOSED SPACE? WHAT WILL IT
 LOOK LIKE INSIDE ONCE IT IS FINISHED.
  
 PASSED
  
 1. NO TREES BEING REMOVED SO NO TREE ALTERATION PERMIT
 IS REQUIRED.
 2. NOT BUILT INTO A HISTORIC DISTRICT.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  