| 2016-07-22 16:34:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) IT IS UNCLEAR WITH THIS SUBMITTAL WHAT OCCUPANCY |
| | CODE YOU ARE PROPOSED TO BE COMPLYING WITH; EXIISTING |
| | APARTMENTS VS NEW APARTMENTS. |
| | |
| | PER NFPA 101, CHAPTER 43 BUILDING REHABILITATION |
| | 43.1 GENERAL. |
| | 43.1.1 CLASSIFICATION OF REHABILITATION WORK |
| | CATEGORIES. REHABILITATION WORK ON EXISTING BUILDINGS |
| | SHALL BE CLASSIFIED AS ONE OF THE FOLLOWING WORK |
| | CATEGORIES: |
| | (1) REPAIR |
| | (2) RENOVATION |
| | (3) MODIFICATION |
| | (4) RECONSTRUCTION |
| | (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION |
| | (6) ADDITION |
| | |
| | 43.2.2.1.3 MODIFICATION. THE RECONFIGURATION OF ANY |
| | SPACE; THE ADDITION, RELOCATION, OR ELIMINATION OF ANY |
| | DOOR OR WINDOW; THE ADDITION OR ELIMINATION OF |
| | LOAD-BEARING ELEMENTS; THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM; OR THE INSTALLATION OF |
| | ANY ADDITIONAL EQUIPMENT. |
| | |
| | 43.5 MODIFICATIONS. |
| | 43.5.1 GENERAL REQUIREMENTS. |
| | 43.5.1.1 A MODIFICATION, AS DEFINED IN 43.2.2.1.3, IN |
| | OTHER THAN HISTORIC BUILDINGS SHALL COMPLY WITH BOTH OF |
| | THE FOLLOWING: |
| | (1) SECTION 43.5 |
| | (2) SECTION 43.4 |
| | |
| | 43.5.1.3 NEWLY CONSTRUCTED ELEMENTS, COMPONENTS, AND |
| | SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF OTHER |
| | SECTIONS OF THIS CODE APPLICABLE TO NEW CONSTRUCTION. |
| | |
| | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN |
| | THOSE MEETING THE REQUIREMENTS OF 30.3.4.1.2, SHALL BE |
| | PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2 THROUGH |
| | 30.3.4.5. |
| | |
| | ADDITIONALLY, THIS BUILDING IS A HIGH RISE AND SHALL |
| | COMPLY WITH THE REQUIRED PROVISIONS, INCLUDING VOICE |
| | EVACUATION. |
| | |
| | 30.4.1 HIGH-RISE BUILDINGS. |
| | 30.4.1.1 HIGH-RISE BUILDINGS SHALL COMPLY WITH SECTION |
| | 11.8. THE PROVISIONS OF 30.3.5.3 AND 30.3.4.5 SHALL BE |
| | PERMITTED. |
| | |
| | PLEASE REVIEW THESE REQUIRERMENTS AND PROVIDE |
| | APPLICABLE REVISIONS. |
| | |
| | |
| | |
| | 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |