Plan Review Details - Permit 16070875
Plan Review Stops For Permit 16070875
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By jwitmer Date 2016-07-29 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2016-07-29 Time 07:15 Sent To  
Notes
2016-07-29 07:34:27BUILDING PLAN REVIEW
 W. P. B. REVISION: 16070875
 W. P. B. PERMIT: 16020642
 ADD: 421 BELVEDERE RD.
 CONT: L B ROWE
 TEL: 835-1499
 E-MAIL: ????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 29/2016
 ACTION: DENIED
  
 1) SHEET 1.0A DETAIL WALL FAN INFILE, THE PLANS
 INDICATE TO REMOVE THE 2 WINDOWS AND INSTALLING 2
 THROUGH THE WALL FANS.
  
 PLEASE REVIEW THE 2014 FBC-M 501.3.1 501.3.2 EXHAUST
 OPENING PROTECTION. EXHAUST OPENINGS THAT TERMINATE
 OUTDOORS SHALL BE PROTECTED WITH CORROSION-RESISTANT
 SCREENS, LOUVERS OR GRILLES. OPENINGS IN SCREENS,
 LOUVERS AND GRILLES SHALL BE SIZED NOT LESS THAN 1/4
 INCH (6 MM) AND NOT LARGER THAN 1/2 INCH (13 MM).
 OPENINGS SHALL BE PROTECTED AGAINST LOCAL WEATHER
 CONDITIONS. LOUVERS THAT PROTECT EXHAUST OPENINGS IN
 STRUCTURES LOCATED IN HURRICANE-PRONE REGIONS, AS
 DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, SHALL
 COMPLY WITH AMCA STANDARD 550. OUTDOOR OPENINGS LOCATED
 IN EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR
 EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (C) PANEL WALLS: WALL LOUVERS,
 (E) SHUTTERS
  
 2) PLEASE PROVIDE THE VASD PRESSURES FOR THESE 2
 OPENINGS. 2014 FBC-B 1603.1.4 WIND DESIGN DATA (5)
 COMPONENTS AND CLADDING PRESURES.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-26 Cont ID  
Sent By vperez Date 2016-07-26 Time 06:44 Rev Time 0.00
Received By vperez Date 2016-07-26 Time 06:44 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-29 Cont ID  
Sent By vperez Date 2016-07-29 Time 06:44 Rev Time 0.00
Received By vperez Date 2016-07-26 Time 06:44 Sent To  
Notes
2016-07-22 13:08:12VPEREZ'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 14:04 Rev Time 0.00
Received By ccole Date 2016-07-26 Time 14:04 Sent To  
Notes
2016-07-26 14:16:161ST REVIEW MECHANICAL
 PERMIT #16070875
 7/26/16
  
 1) THE MECHANICAL PLAN SHOWN ON SHEET 3.0P MUST BE
 REVISED TO SHOW THE NEW WALL FAN AND FAN EQUIPMENT
 SCHEDULE.
  
 2) CLARIFY THE PURPOSE OF THE FAN AND PROVIDE SIZING
 CALCULATIONS.
  
 3) INDICATE A SEQUENCE OF OPERATION FOR THE FAN.
  
 4) PROVIDE OPENING PROTECTION FOR THE FAN AS REQUIRED
 BY SECTIONS 401.4 AND 501.3.2
  
 5) SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE GAS
 DRYERS REVIEWED AND APPROVED WITH SIGNATURE BY THE
 ENGINEER OF RECORD. IF THEY ARE EXISTING PLEASE LABEL
 THEM EXISTING ON THE PLANS.
  
 6) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR
 THE DRYERS AND PROVIDE CALCULATIONS- SEE SECTION 304
 FBC-14 FUEL GAS.
  
 7) PROVIDE DETAILS FOR THE DRYER EXHAUST DUCTS- TYPE
 AND SIZE OF DUCTS, AND DUCT SUPPORTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  