Plan Review Details - Permit 16070802
Plan Review Stops For Permit 16070802
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-12 Cont ID  
Sent By cpuell Date 2016-08-12 Time 09:03 Rev Time 0.00
Received By cpuell Date 2016-08-10 Time 13:12 Sent To  
Notes
2016-08-10 13:13:00RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By cpuell Date 2016-07-25 Time 16:42 Rev Time 0.00
Received By cpuell Date 2016-07-21 Time 11:00 Sent To  
Notes
2016-07-21 11:00:59MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-11 Cont ID  
Sent By jvalido Date 2016-08-11 Time 17:58 Rev Time 0.00
Received By jvalido Date 2016-08-11 Time 17:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By jvalido Date 2016-07-25 Time 16:07 Rev Time 0.00
Received By jvalido Date 2016-07-25 Time 14:38 Sent To  
Notes
2016-07-25 15:51:13SECTION M1602 RETURN AIR
 M1602.2 PROHIBITED SOURCES.
  
 3. A ROOM OR SPACE, THE VOLUME OF WHICH IS LESS THAN 25
 PERCENT OF THE ENTIRE VOLUME SERVED BY THE SYSTEM.
 WHERE CONNECTED BY A PERMANENT OPENING HAVING AN AREA
 SIZED IN ACCORDANCE WITH ACCA MANUAL D, ADJOINING ROOMS
 OR SPACES SHALL BE CONSIDERED AS A SINGLE ROOM OR SPACE
 FOR THE PURPOSE OF DETERMINING THE VOLUME OF THE ROOMS
 OR SPACES.
  
 RETURN AIR MUST BE PERMANENTLY DUCTED FROM AHU CLOSET
 TO COMMON AREA (LIVING ROOM). CANNOT RETURN THRU A
 LOUVERED DOOR THRU A BEDROOM TO ANOTHER LOUVERED DOOR
 TO A AHU.
  
 AS PER THE SCALE LEGEND ON THE PLANS BEDROOM #1 IS 88
 SQFT (INCLUDING THE AHU CLOSET). BEDROOM #2 IS 88 SQFT.
 THE HVAC LOAD CALCULATIONS STATES 120 SQFT FOR EACH
 BEDROOM #1 AND #2..
 REVIEW YOUR LOAD CALCULATIONS AND MAKE ALL THE
 CORRECTIONS NECESSARY.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  