| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070797 |
| | ADD: 3400 S. DIXIE HWY. |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 561-689-8880 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 22/ |
| | 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLAN SP1 IS MISSING THE DESIGN |
| | PARAMETERS THIS ADDITION WAS DESIGNED TO? 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. 2014 FBC-EXISTING |
| | BUILDING CODE, 2014 FBC-B AND THE 2016 SUPPLEMENTS TO |
| | THE 2014 FBC. |
| | |
| | 2) THE PLAN SP-1 IS MISSING THE WIND DESIGN CRITERIA |
| | FOR THIS BUILDING AND ADDITION. 2014 FBC-B 1603.1.4 |
| | WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO |
| | WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND |
| | LOADS GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING |
| | SYSTEM OF THE STRUCTURE: |
| | |
| | 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 2.2. RISK CATEGORY. |
| | |
| | 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 3) MISSING PLAN REVIEW CRITERIA, 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS- BUILDINGS: |
| | OCCUPANCY TYPE FOR THE MAIN BUILDING & ADDITION |
| | MINIMUM BUILDING TYPE |
| | IS THE BUILDING CURRENTLY FIRE SPRINKLED OR NOT |
| | FLOOR PLAN OF THE BUILDING AND ADDITION |
| | |
| | 4) SHEET SP-1 DETAIL SECTION 1-1 INDICATE A SECTION |
| | THROUGH THE EXTERIOR WALL, THE TYPE STYLE OF |
| | CONSTRUCTION IS NOT IDENTIFIED (CBS OR WOOD FRAME), IT |
| | IS NOT CLEAR FROM THIS DETAIL IF THIS IS AN EXISTING |
| | DOOR OPENING. NONE OF THE DETAILS GIVEN SHOW THE WALL |
| | LINE OF THE EXISTING CONSTRUCTION, THE FLOOR PLAN SHOWS |
| | THE NEW COOLER DOOR SWINGING TO THE INTERIOR OF THE |
| | EXISTING BUILDING BUT THERE IS NO CORRELATION AS WHERE |
| | THE EXISTING BUILDING WALL IS IN RELATIONSHIP TO THE |
| | COOLER DOOR. TO HAVE THE COOLER DOOR SWING INTO THE |
| | INTERIOR SPACE THAT OPENING HAS TO BE LARGER THAN A |
| | 3?-0? DOOR OPENING, TO HAVE CLEARANCE FOR THE HINGES |
| | AND THE LOCKING MECHANISM ON THE OPPOSITE SIDE OF THE |
| | DOOR. PLEASE PROVIDE A DETAIL FOR THE NEW FRAMED IN |
| | OPENING WITH OPENING SIZE, SHOW HOW MANY FULL LENGTH |
| | STUDS ARE ON EACH SIDE OF THE DOOR, JACK STUDS, SIZE OF |
| | THE HEADER, SPAN OF THE HEADER, PLEASE SHOW ALL |
| | ANCHORING DEVISES SINCE THIS FRAMING IS PART OF THE |
| | MAIN WIND FORCE RESISTING SYSTEM (MWFRS). 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) SHEET SP-1 DETAIL SECTION 1-1 SHOWS A 10 INCH WIDE X |
| | 18 INCH DEEP 3 BAR CONCRETE FOOTING WHEREAS THE PLANS |
| | ARE SILENT TO WHAT IS ABOVE THE BASE ASPHALT, IT IS |
| | UNKNOWN IF THIS IS A CONCRETE SLAB OR THE BOTTOM OF THE |
| | COOLER . 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. SEE |
| | MINIMUM REQUIREMENT THICKNESS FOR CONCRETE SLABS |
| | 1907.1. |
| | |
| | 6) PLEASE NOTE MAY OR MAY NOT BE A CODE VIOLATION |
| | DEPENDING ON THE END USAGE AS A COOLER. NOT HAVING A 6 |
| | MIL POLYETHYLENE VAPOR BARRIER UNDER THE NEW ADDITION, |
| | 2014 FBC-B 1816.1, 1907.2, AND SECTION RADON APPENDIX |
| | E104.2. |
| | |
| | 6) THE PLANS SHEET SP-1 SHOWS NEW INTERIOR SQUARE |
| | FOOTAGE BEING CREATED THE DESIGNER DOES NOT INDICATE |
| | HOW COMPLIANCE WITH 2014 FBC-B SECTION ON 1816.1THROUGH |
| | 1816.2 TERMITE PROTECTION. |
| | |
| | 7) THE SHEET SP-1 SECTION 1-1 DOES NOT SHOW COMPLIANCE |
| | WITH THE 2014 FBC-B 1503.7 PROTECTION AGAINST DECAY AND |
| | TERMITES. CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL |
| | DISCHARGE AT LEAST 1 FOOT (305 MM) AWAY FROM THE |
| | STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL |
| | EXTENSIONS, OR SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS |
| | ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6 |
| | INCHES (152 MM) HORIZONTAL PROJECTION EXCEPT FOR GABLE |
| | END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 18) SHEET SP-1 THE WALL SECTION 1-1 INDICATES THE USE |
| | OF 6 IN. X 16 GAUGE TRACK / BOTTOM PLATE TO BE ANCHORED |
| | WITH (2) ? INCH X 2 INCH TAPCONS 16 INCHES O.C. THE |
| | PLANS DO NOT INDICATE HOW CLOSE (MINIMUM DISTANCE TO |
| | THE EDGE OF CONCRETE) THE TAPCONS CAN BE INSTALLED AND |
| | TAKE THE FULL VALUE OF THE SERVICE LOADS. THE PLANS ARE |
| | SILENT ON THE MINIMUM DISTANCE APART THE 2 TAPCONS CAN |
| | BE WITHIN THE 16 INCHES O. C. AND STILL TAKE THE FULL |
| | VALUE OF THE SERVICE LOAD GIVEN BY THE MANUFACTURER OF |
| | THE TAPCON. PLEASE SUPPLY TESTING REPORT FOR ALLOWABLE |
| | SERVICE DESIGN FOR THIS PRODUCT FOR SHEAR AND TENSION |
| | LOADS, ARE THE ALLOWABLE LOADS TAKEN WITH OR WITHOUT |
| | INSPECTION AT TIME OF INSTALLATION? ASTM E 488. |
| | |
| | 19) THE PLANS SHEET SP-1 DOES NOT PROVIDE A DETAIL FOR |
| | SEALING OF THE BOTTOM METAL TRACK, FLASHING DETAIL, |
| | SEALING THE PLYWOOD SHEATHING, WIRE LATH AND STUCCO |
| | FROM THE CONCRETE FOUNDATION BELOW. 2014 FBC-B |
| | 1405.4 FLASHING. FLASHING SHALL BE INSTALLED IN SUCH A |
| | MANNER SO AS TO PREVENT MOISTURE FROM ENTERING THE WALL |
| | OR TO REDIRECT IT TO THE EXTERIOR. FLASHING SHALL BE |
| | INSTALLED AT THE PERIMETERS OF EXTERIOR DOOR AND WINDOW |
| | ASSEMBLIES, PENETRATIONS AND TERMINATIONS OF EXTERIOR |
| | WALL ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH |
| | ROOFS, CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR |
| | PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR |
| | LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING |
| | WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH |
| | SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND |
| | CONTINUOUSLY ABOVE PROJECTING TRIM. |
| | |
| | 20) SHEET SP-1 DETAIL SECTION 1-1 IS ALSO MISSING A |
| | FLASHING DETAIL FOR THE NEW ROOF TO EXISTING WALL |
| | CONNECTION. 2014 FBC-B 1503.2 FLASHING. FLASHING SHALL |
| | BE INSTALLED IN SUCH A MANNER SO AS TO PREVENT MOISTURE |
| | ENTERING THE WALL AND ROOF THROUGH JOINTS IN COPINGS, |
| | THROUGH MOISTURE-PERMEABLE MATERIALS AND AT |
| | INTERSECTIONS WITH PARAPET WALLS AND OTHER PENETRATIONS |
| | THROUGH THE ROOF PLANE. |
| | |
| | 21) SHEET SP-1 DETAIL SECTION 1-1 IS ALSO MISSING THE |
| | ROOF JOIST CONNECTION TO THE EXISTING WALL IN IN SHEAR |
| | LOADS NOR THE END OF THE ROOF JOIST IN SHEAR LOAD |
| | VERTICAL LOADING (TENSION) AS WELL AS SHEAR LOADING |
| | (LATERAL LOADS) NO FASTENER INFORMATION SUPPLIED NOR IF |
| | THERE WAS TO HAVE STRAPS APPLIED TO MAKE A CONTINUOUS |
| | LOAD PATH FROM THE ROOF FRAMING MEMBERS TO THE TOP |
| | PLATE AND WALL FRAMING MEMBERS. THE SAME HOLDS TRUE FOR |
| | THE CONNECTION TO THE BOTTOM PLATE. |
| | |
| | 2014 FBC-B 2211.4 WALL STUD DESIGN. WALL STUDS SHALL BE |
| | DESIGNED IN ACCORDANCE WITH EITHER AISI S211 OR AISI |
| | S100. |
| | |
| | 2211.5 FLOOR AND ROOF SYSTEM DESIGN. FRAMING FOR FLOOR |
| | AND ROOF SYSTEMS IN BUILDINGS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH EITHER AISI S210 OR AISI S100. |
| | |
| | 2211.6 LATERAL DESIGN. LIGHT-FRAME SHEAR WALLS, |
| | DIAGONAL STRAP BRACING THAT IS PART OF A STRUCTURAL |
| | WALL AND DIAPHRAGMS USED TO RESIST WIND, SEISMIC AND |
| | OTHER IN-PLANE LATERAL LOADS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH AISI S213. |
| | |
| | 22A) SHEET SP-1 DETAIL SECTION 1-1 IS ALSO MISSING THE |
| | TYPE OF ROOF SHEATHING TO BE APPLIED TO THIS STRUCTURE, |
| | NOTE INDICATES A SINGLE PLY ROOF SYSTEM OVER 30 LB. |
| | FELT TINTAGED. 107.2.1 ADDITIONAL INFORMATION REQUIRED. |
| | / 107.3.5.1.1 MINIMUM REQUIREMENTS FOR PLAN REVIEW FOR |
| | COMMERCIAL BUILDINGS |
| | (8) STRUCTURAL REQUIREMENTS SHALL REQUIRE ROOF SYSTEMS. |
| | |
| | 22B) PLEASE NOTE A ROOFING PERMIT WILL ALSO BE |
| | REQUIRED. TO DATE NO PRODUCT APPROVALS WERE SUBMITTED |
| | WITH THIS PERMIT PACKAGE. , 1609.6.4.4.1 COMPONENTS & |
| | CLADDING . FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 23) THE PLANS INDICATE THE INSTALLATION OF A COOLER |
| | WITHIN THE NEW ADDITION. NO INFORMATION HAS BEEN |
| | SUBMITTED FOR THIS COOLER, IS IT A PREFABRICATED COOLER |
| | SYSTEM OR A SITE BUILT COOLER. PLEASE PROVIDE |
| | COMPLIANCE WITH: 2014 FBC-B 2603.4.1.2 COOLER AND |
| | FREEZER WALLS. |
| | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 |
| | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: |
| | |
| | 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4-INCH (102 MM) THICKNESS. |
| | |
| | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | |
| | 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. |
| | |
| | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE COOLER OR |
| | FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR |
| | FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS |
| | LOCATED SHALL BE SPRINKLERED. |
| | |
| | 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED |
| | BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES |
| | NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD |
| | INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER |
| | UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| | 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED |
| | BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81 |
| | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A |
| | MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A |
| | THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED |
| | WHERE PROTECTED BY A THERMAL BARRIER. |
| | |
| | 24) PLEASE NOTE COOLERS AND THEIR ASSOCIATED MECHANICAL |
| | EQUIPMENT DO REQUIRE A SEPARATE PERMIT FOR, |
| | LICENSING PURPOSES, PERMIT TRACKING OF INSPECTIONS, |
| | ETC. 105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT |
| | AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO |
| | INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, |
| | DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR |
| | STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER, |
| | REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT RESISTANT |
| | COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR |
| | FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD |
| | RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS |
| | REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE |
| | DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT. |
| | |
| | 25) SHEET SP-1 SHOWS THE COOLER CONDENSER TO BE |
| | INSTALLED ON TOP OF THE EXISTING SLOPED ROOF. PLEASE |
| | PROVIDE THE SLOPE OF THE ROOF. PLEASE SHOW COMPLIANCE |
| | WITH: 2014 FBC-B 1509.4. 1509.6.4 EQUIPMENT AND |
| | APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. SUCH ACCESS |
| | SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER |
| | THAN 30 INCHES (762 MM) HIGH OR WALKING ON ROOFS HAVING |
| | A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE). |
| | |
| | 26) SHEET SP-1 INDICATES THE NEW COOLER CONDENSER TO BE |
| | MOUNTED TO A CONDENSER STAND. PLEASE PROVIDE THE |
| | ENGINEERING FOR THE BLOCKING BENEATH THE ROOF DECK TO |
| | ANCHOR THE NEW CONDENSER UNIT TO, ALSO PROVIDE HOW A |
| | WATER TIGHT PENETRATION WILL BE ACHIEVED? 107.2.1 |
| | MISSING INFORMATION. |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | 1503.2 FLASHING. FLASHING SHALL BE INSTALLED IN SUCH A |
| | MANNER SO AS TO PREVENT MOISTURE ENTERING THE WALL AND |
| | ROOF THROUGH JOINTS IN COPINGS, THROUGH |
| | MOISTURE-PERMEABLE MATERIALS AND AT INTERSECTIONS WITH |
| | PARAPET WALLS AND OTHER PENETRATIONS THROUGH THE ROOF |
| | PLANE. |
| | |
| | 27A) MISSING THE PRODUCT APPROVAL FOR THE ROOFTOP |
| | PRE-ENGINEERED A/C STAND. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31) (G) PRE-ENGINEERED A/C STANDS. |
| | |
| | 27B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 28) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED . |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |