Plan Review Details - Permit 16070747
Plan Review Stops For Permit 16070747
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-21 Cont ID  
Sent By albarran Date 2016-07-21 Time 15:47 Rev Time 0.00
Received By albarran Date 2016-07-21 Time 12:36 Sent To I
Notes
2016-07-21 15:49:00JOB NAME:
 JOB ADDRESS: 4010 MILLER AVE..
 DESCRIPTION: CHANGE 400 AMP SINGLE PHASE SERVICE TO 400
 AMP 3 PHASE TO ELIMINATE PHASE CONVERTER.
 MAST. PERMIT: 16070747
 REVISION/SUB-PERMIT:
  
 1. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
 2. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL
 BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS.
 3. NEC 110.27(B) IN LOCATIONS WHERE ELECTRICAL
 EQUIPMENT IS LIKELY TO BE EXPOSED TO PHYSICAL DAMAGE,
 ENCLOSURES OR GUARDS SHALL SO ARRANGED AND OF SUCH
 STRENGTH AS TO PREVENT SUCH DAMAGE. PROVIDE A
 SITE/FLOOR PLAN INDICATING THE LOCATION OF ALL THE
 SERVICE EQUIPMENT.
 4. NEC 300.5(B): THE INTERIOR OF A RACEWAY INSTALLED
 UNDERGROUND OR EXPOSED TO THE ELEMENTS SHALL BE
 CONSIDERED A WET LOCATION. THEREFORE THE SERVICE
 LATERAL CONDUCTORS SHALL BE LISTED FOR THE APPLICATION.
 5. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 6. NEC 215.2(A)(1): FEEDER CONDUCTORS SHALL BE SIZED TO
 HAVE AN AMPACITY OF THE NON-CONTINUOUS LOAD PLUS 125%
 OF THE CONTINUOUS LOAD. THE FEEDER FOR PANEL A, RATED
 AT 200 AMP IS NOT PROPER. CONNECTED LOAD FOR PANEL A AT
 37.54 KW IS 180 AMP NOT THE 104 INDICATED. CORRECT
 ACCORDINGLY.
 7. NEC 215.3 ADDRESSES THE SAME FOR THE OVER CURRENT
 PROTECTION DEVICE. ADJUST AS REQUIRED.
 8. NEC 230.23 INSTRUCTS YOU TO SIZE YOUR SERVICE
 CONDUCTORS ACCORDING TO THE LOADS CALCULATED USING
 ARTICLE 220. IN OTHER WORDS, THE PROPOSED 400 AMP
 SERVICE AS DESCRIBED DOES NOT COMPLY WITH MINIMUM CODE
 REQUIREMENTS. ACCORDING TO THE CALCULATIONS A 600 AMP
 SERVICE IS NECESSARY FOR THIS APPLICATION.
 9. NEC 376.23(B): PROVIDE THE SIZE OF THE PROPOSED
 METALLIC WIREWAY (GUTTER) TO ASCERTAIN CODE COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By albarran Date 2016-07-21 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-21 Cont ID  
Sent By albarran Date 2016-07-21 Time 15:49 Rev Time 0.00
Received By albarran Date 2016-07-20 Time 13:06 Sent To  
Notes
2016-07-21 15:51:477/21/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED DRAWER
 "F". MA
2016-07-20 13:06:39ROUTED TO ELECTRICAL INBOX