| 2016-07-20 08:06:12 | BUILDING PLAN REVIEW |
| | W.P.B. REVISION: 16070728 |
| | W. P. B. PERMIT: 15090101 |
| | ADD: 1301 SUMMIT BLVD. PANTHER HOLDING/ OTTER HOLDING |
| | CONT: GAST CONSTRUCTION |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 20/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE STRUCTURAL SHEET S3.0 AND ARCHITECTURAL SHEET |
| | A-300 WILL NEED TO BE CORRELATED ONCE THE OPTIONS ON |
| | SHEET A-300 ARE KNOWN. UNKNOWNS ARE: 1A) TRUSSES FOR |
| | THE PANTHER HOLDING ENCLOSURE BEING BUILT WILL BE |
| | CONSTRUCTED USING EITHER FIRE RETARDANT TREATED WOOD OR |
| | METAL TRUSSES. |
| | 1B) THE ROOFING NOTE FOUND ON SHEET A-300 NOTE # 1 |
| | INDICATES THE INSTALLATION OF V CRIMP ANODIZED ALUMINUM |
| | METAL ROOFING OVER PEEL AND STICK UNDERLAYMENT MEMBRANE |
| | ON 2 INCH RIGID ROOF INSULATION BOARD MECHANICALLY |
| | FASTENED TO THE ROUGH SAWN BOARD INSTALLED PER THE |
| | MANUFACTURERS INSTRUCTIONS. SEE STRUCTURAL DRAWINGS. |
| | THE STRUCTURAL DRAWINGS INDICATE THE USE OF 5/8 INCH |
| | PLYWOOD DECKING. |
| | |
| | 2) PLEASE CORELATE ALL OF THE MATERIALS TO BE INSTALLED |
| | AND SHOW ON THE ARCHITECTURAL & STRUCTURAL SHEETS. |
| | PLEASE BEGIN WITH THE TYPE OF TRUSS FIRE RETARDANT |
| | TREATED WOOD OR METAL, THE TYPE OF DECKING, THE 2 INCH |
| | INSULATION AND ALL ROOFING MEMBRANE MATERIALS. SUBMITED |
| | IS A PEAL AND STICK UNDERLAYMENT TU-MAX AND THE ROOFING |
| | REPORT SUBMITTED POLYGLASS MODIFIED BITUMEN ROOF SYSTEM |
| | W-106 PAGE 18 IS FOR NEW CONSTRUCTION SYSTEM E: |
| | NON-INSULATED WOOD DECK, EITHER THE PLANS NEED REVISED |
| | OR THE PRODUCT APPROVAL, PLEASE ALSO BE ADVISED THE FL. |
| | APPROVAL FL 14645 THE DECK NAILING WILL NEED TO BE |
| | REVIEWED SINCE THERE IS SHOWN TO BE 2 INCHES OF |
| | INSULATION !!!!!!!!! |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |