Plan Review Details - Permit 16070559
Plan Review Stops For Permit 16070559
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 08:25 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By cthroop Date 2016-07-26 Time 08:57 Rev Time 0.00
Received By cthroop Date 2016-07-26 Time 08:57 Sent To  
Notes
2016-07-26 09:03:30BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/26/16
  
 1. PROVIDE DETAIL W/DEMENSIONS FOR GRADE BEAMS.
 2. SECTION 2, PG S-3 STATES "GRADE BEAM 1" WIDE AT
 BOTTOM" AND "6" AT TOP". PLEASE CLARIFY.
 3. PROVIDE DETAIL FOR ALL WELDED CONNECTIONS.
 CONTRACTOR TO VERIFY WELDER CERTIFICATIONS.
 4. ANCHOR BOLT SCHEDULE ON PG S-3 SPECIFIES BOLTS TO BE
 A36. BOLTS SPECIFIED IN SECTION 2, PG S-3 ARE STAINLESS
 STEEL. PLEASE CLARIFY.
 5. RESIDENT INSPECTOR REQUIRED.
 6. VALUE APPEARS LOW.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 08:25 Rev Time 0.00
Received By cthroop Date 2016-08-05 Time 08:45 Sent To  
Notes
2016-08-08 08:45:55RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-26 Cont ID  
Sent By cthroop Date 2016-07-26 Time 08:57 Rev Time 0.00
Received By cthroop Date 2016-07-15 Time 13:36 Sent To  
Notes
2016-07-15 13:36:52BLDG MISC 1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 08:25 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 08:25 Sent To  
Notes
2016-08-09 08:37:06NO NOTES
2016-08-09 08:36:53 
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By cthroop Date 2016-07-26 Time 09:03 Rev Time 0.00
Received By cthroop Date 2016-07-26 Time 09:03 Sent To  
Notes
2016-07-26 09:16:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/26/16
  
 1. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
  
 2. THE RESIDENT INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE IN TRIPLICATE AND REVIEWED AND
 APPROVED BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
 CONTACT KEN CONRAD, MANAGER OF SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 3. FOR THE SPECIAL INSPECTOR & DESIGNATED JOB
 INSPECTORS - PLEASE PROVIDE A RESUME? OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME? MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME?. AFTER THE RESUME? IS REVIEWED, AN INTERVIEW
 MAY BE SCHEDULED.
  
 4. THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 5. THE SPECIAL INSPECTOR, UPON COMPLETION OF THE
 BUILDING AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY OR COMPLETION, FILE A SIGNED AND SEALED
 STATEMENT WITH THE ENFORCEMENT AGENCY IN SUBSTANTIALLY
 THE FOLLOWING FORM: ?TO THE BEST OF MY KNOWLEDGE AND
 BELIEF, THE ABOVE DESCRIBED CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS COMPLIES WITH THE
 PERMITTED DOCUMENTS AND THE SHORING AND RESHORING
 CONFORMS TO THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY?.
  
 6. NOTICE ONLY - 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN
 ALTERNATE STRUCTURAL PRODUCT OR SYSTEM TO WHICH
 BUILDING CODES APPLY SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR REVIEW FOR COMPLIANCE WITH THE
 CODES AND MADE PART OF THE ENFORCEMENT AGENCY?S
 RECORDED SET OF PERMIT DOCUMENTS. 110.3.7.4.3 ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 RECORDKEEPING. EACH SHORING AND RESHORING INSTALLATION
 SHALL BE SUPERVISED, INSPECTED AND CERTIFIED TO BE IN
 COMPLIANCE WITH THE SHORING DOCUMENTS BY THE
 CONTRACTOR.
  
 7. NOTICE ONLY - PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561)
 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES
 IN 6 MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB,
 NO INSPECTION ACTIVITY?. THE PERMIT WILL BECOME
 EXPIRED.
  
 8. NOTICE ONLY - MAINTENANCE OF MEANS OF EGRESS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS AND ADDITIONS TO ANY BUILDING.
  
 9. NOTICE ONLY - )PROVIDE COMPLIANCE WITH FBC 3309.1
 WHERE REQUIRED. ALL STRUCTURES UNDER CONSTRUCTION,
 ALTERATION OR DEMOLITION SHALL BE PROVIDED WITH NO
 FEWER THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER IN
 ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS THAN
 ORDINARY HAZARD AS FOLLOWS:
  
 A) AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 B) IN EVERY STORAGE AND CONSTRUCTION SHED.
 C) ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
  
  
  
  
  