Plan Review Details - Permit 16070516
Plan Review Stops For Permit 16070516
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time   Rev Time  
Received By jwitmer Date 2016-07-18 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-19 Cont ID  
Sent By vperez Date 2016-07-19 Time 11:58 Rev Time 0.00
Received By albarran Date 2016-07-19 Time 11:51 Sent To  
Notes
2016-07-19 11:59:14PASSED AS-BUILT REVISION ELECTRICAL REVIEW SUBJECT TO
 FIELD INSPECTOR'S APPROVAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-22 Cont ID  
Sent By scaldero Date 2016-07-22 Time   Rev Time 0.00
Received By pleduc Date 2016-07-22 Time 15:10 Sent To  
Notes
2016-07-22 15:26:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET A2 - PER NFPA 101, CHAPTER 43 BUILDING
 REHABILITATION
  
  
 43.4 RENOVATIONS.
 43.4.1 GENERAL REQUIREMENTS.
 43.4.1.3 ALL NEW WORK SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS CODE APPLICABLE TO EXISTING
 BUILDINGS.
 43.4.1.4 THE WORK SHALL NOT MAKE THE BUILDING LESS
 CONFORMING WITH OTHER SECTIONS OF THIS CODE, OR WITH
 ANY PREVIOUS APPROVED ALTERNATIVE ARRANGEMENTS, THAN IT
 WAS BEFORE THE RENOVATION WAS UNDERTAKEN, UNLESS
 OTHERWISE SPECIFIED IN 43.4.1.5.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 2) THE FIRE INSPECTOR WILL REVIEW AND VERIFY COMPLAINCE
 NOTED ABOVE. PLEASE ENSURE REVIEW AND COMPLAINCE PRIOR
 TO INSPECTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-06 Cont ID  
Sent By tklarge Date 2016-09-06 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-09-01 Time 13:09 Sent To  
Notes
2016-09-01 13:09:52RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-02 Cont ID  
Sent By tklarge Date 2016-08-02 Time 15:06 Rev Time 0.00
Received By tklarge Date 2016-07-15 Time 12:36 Sent To  
Notes
2016-07-26 15:50:27ROUTED TO B23 - 7/26/2016
2016-07-15 12:37:28B23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-01 Cont ID  
Sent By jvalido Date 2016-09-01 Time 18:14 Rev Time 0.00
Received By jvalido Date 2016-09-01 Time 18:14 Sent To  
Notes
2016-09-01 18:15:51SEE REVISION 16080665 FOR MECHANICAL CORRECTIONS
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By jvalido Date 2016-07-26 Time 15:46 Rev Time 0.00
Received By jvalido Date 2016-07-26 Time 15:37 Sent To  
Notes
2016-07-26 15:40:13CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 PROVIDE ON PLANS ANY REVISIONS REQUIRED FOR HVAC DONE.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By tklarge Date 2016-09-06 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-09-06 Time 06:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By gjohnson Date 2016-08-02 Time 15:06 Rev Time 0.00
Received By tklarge Date 2016-08-02 Time 14:19 Sent To  
Notes
2016-08-02 15:06:021) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 RELOCATION OF THE FIXTURES IN THE MASTER BATH AND THE
 DELETION OF THE SINK IN THE LAUNDRY ROOM. WPB AMEND. TO
 FBC SEC. 107.3.5.1.3.
 2) THE WATER SUPPLY VALVES FOR THE STACKED WASHER UNIT
 SHALL BE ACCESSIBLE PER 2014 FBC SEC.606.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  