Plan Review Details - Permit 16070502
Plan Review Stops For Permit 16070502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By jwitmer Date 2016-07-18 Time   Rev Time  
Received By   Date 2016-07-18 Time   Sent To  
Notes
2016-08-03 09:26:17REVIEW BY JWITMER.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-15 Cont ID  
Sent By mvaldes Date 2016-07-15 Time 11:42 Rev Time 0.00
Received By albarran Date 2016-07-15 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By skennedy Date 2016-08-03 Time 09:25 Rev Time 0.00
Received By skennedy Date 2016-07-14 Time 12:58 Sent To  
Notes
2016-07-14 12:58:24B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 08:31 Rev Time 0.00
Received By ccole Date 2016-07-26 Time 08:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 15:36 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 15:36 Sent To  
Notes
2016-07-18 15:44:311ST REVIEW MECHANICAL
 PERMIT #16070502
 7/18/16
  
 1) THE 8 " AND 6" FLEX DUCTS SUPPLYING 300 CFMS OF AIR
 TO THE KITCHEN ARE UNDERSIZED PER ASHRAE AND ACCA DUCT
 SIZING METHODOLOGY. PLEASE INCREASE THE DUCT SIZE TO 9"
 UP UNTIL THE LAST 150 CFM DROP WHICH CAN BE A 6"
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-02 Cont ID  
Sent By tklarge Date 2016-08-02 Time 13:26 Rev Time 0.00
Received By tklarge Date 2016-08-01 Time 14:24 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved