Plan Review Details - Permit 16070444
Plan Review Stops For Permit 16070444
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-19 Cont ID  
Sent By jwitmer Date 2016-09-19 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2016-09-19 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By albarran Date 2016-08-05 Time 06:59 Rev Time  
Received By jwitmer Date 2016-08-05 Time 06:44 Sent To  
Notes
2016-08-05 06:59:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070444
 ADD: 525 OKEECHOBEE BLVD. SUITE 1770
 CONT: HOLT LEE
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 05/2016
 ACTION: DENIED
  
 1) THE PLANS INDICATE A CONTRACT VALUE OF $174,360.00
 DOLLORS. THE FLOOR PLAN A1.1 AND LIFE SAFETY PLANS DO
 NOT SHOW ANY OTHER WORK BEING ACCOMPLISHED BUT THE
 INSTALATION OF A NEW TENANT SEPARATION WALL. THERE IS
 NO NEW PARTITIONS, NO FURNITURE LAY OUT IS SHOWN FOR
 ACCESS AISLES. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA
 FOR COMMERCIAL BUILDINGS.
 LIFE SAFETY PLAN SHOW ALL FURNATURE, STORAGE CABINETS
 EGRESS AISLES & OR CORRIDORS. ACCESSIBILITY
 REQUIREMENTS ARE ALSO MISSING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO WHOM IT MAY CONCERN:
  
 THE PERMIT SUBMITTED IS READY FOR ISSUANCE,
 FEE BALANCE LISTED BELOW CAN BE PAID AT TIME OF PERMIT
 ISSUANCE:
  
 THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-26 Cont ID  
Sent By albarran Date 2016-09-26 Time 17:15 Rev Time 0.00
Received By albarran Date 2016-09-26 Time 16:18 Sent To  
Notes
2016-09-26 17:50:40THE SCOPE OF THIS PERMIT IS LIMITED TO DEMO WORK. PER
 THE NARRATIVE SUBMITTED BY LOUCKS ENGINEERING THE
 BUILDOUT ELECTRICAL WORK WILL BE DONE BY OTHERS AND
 THEREFORE BEYOND THE SCOPE OF THIS PERMIT. THIS PERMIT
 IS BEING ISSUED EXCLUSIVE OF ANY ELECTRICAL WORK AS SO
 STATED ON THE APPROVED PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By albarran Date 2016-07-27 Time 13:53 Rev Time 0.00
Received By albarran Date 2016-07-21 Time 11:50 Sent To  
Notes
2016-07-21 12:34:35ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: CITY PLACE, SUITE 1770
 JOB ADDRESS: 525 OKEECHOBEE BLVD.
 DESCRIPTION: INTERIOR BUILD-OUT
 MAST. PERMIT: 16070444
 REVISION/SUB-PERMIT:
  
 1. THOUGH THE SCOPE OF WORK AS DESCRIBED ON THE PERMIT
 APPLICATION IS FOR AN INTERIOR BUILD-OUT, THE SUBMITTED
 ELECTRICAL DRAWINGS ONLY ENCOMPASS THE DEMO OF THE
 DESCRIBED SPACE.
 2. YOU WILL HAVE TO EITHER PROVIDE BUILD-OUT
 DOCUMENTATION OR REVISE THE PERMIT SCOPE FOR A
 SUCCESSFUL ELECTRICAL REVIEW.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By pleduc Date 2016-07-18 Time   Rev Time 0.00
Received By pleduc Date 2016-07-18 Time 15:34 Sent To  
Notes
2016-07-18 15:55:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-26 Cont ID  
Sent By albarran Date 2016-09-26 Time 17:53 Rev Time 0.00
Received By albarran Date 2016-09-07 Time 09:35 Sent To  
Notes
2016-09-26 17:53:169/26/16 THE SCOPE OF THIS PERMIT IS LIMITED TO DEMO
 WORK. PER THE NARRATIVE SUBMITTED BY LOUCKS ENGINEERING
 THE BUILDOUT ELECTRICAL WORK WILL BE DONE BY OTHERS AND
 THEREFORE BEYOND THE SCOPE OF THIS PERMIT. THIS PERMIT
 IS BEING ISSUED EXCLUSIVE OF ANY ELECTRICAL WORK AS SO
 STATED ON THE APPROVED PLANS.
2016-09-08 09:35:51B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-05 Cont ID  
Sent By jwitmer Date 2016-08-05 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2016-07-13 Time 10:45 Sent To  
Notes
2016-07-14 10:46:05B13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By ccole Date 2016-09-12 Time 12:39 Rev Time 0.00
Received By ccole Date 2016-09-12 Time 12:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-20 Cont ID  
Sent By ccole Date 2016-07-20 Time 08:01 Rev Time 0.00
Received By ccole Date 2016-07-20 Time 07:45 Sent To  
Notes
2016-07-20 08:10:431ST REVIEW MECHANICAL
 PERMIT #16070444
 7/20/16
  
 1) THE PERMIT APPLICATION IS FOR AN INTERIOR REMODEL,
 HOWEVER THE PLANS ARE INDICATING DEMOLITION ONLY.
  
 2) M1: SHOW CORRESPONDING LOCATIONS ON THE PLAN FOR
 NOTES #3 & 7.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  